ADJUSTABLE PARAMETERS (Configuration editor)
(Factory default settings are shown in bold italicised text)
Parameter as shown on display
Language English - Others
LCD Page Timer hh:mm:ss (5m)
Auto Scroll Delay 1s - 1hr (2s)
Default Config Default Config
Oil Pressure Low Shutdown 0bar - 9.97bar (1.03bar)
Coolant Temperature High Shutdown 2ºC - 140ºC (95ºC)
Start Delay Timer 0 - 10hr (5s)
Pre Heat Timer 0 - 5m (0s)
Crank Duration Timer 0 - 1m (10s)
Crank est Timer 0 - 1m (10s)
Safety On Delay 0 - 1m (10s)
Smoke Limiting 0 - 15m (0s)
Smoke Limiting Off 0 - 1m (0s)
Warm Up Timer 0 -1hr (0s)
Cool Down Timer 0 - 1hr (1m)
Speed Low Shutdown Active, Inactive
Speed Low Shutdown 0RPM - 6000RPM (1270RPM)
Speed High Shutdown 0RPM - 6000RPM (1740RPM)
Speed Overshoot Delay 0-10s (2s)
Speed Overshoot 0% - 10% (0s)
Fail To Stop Delay 0 - 2m (30s)
Battery Voltage Low Warning Active, Inactive
Battery Low Voltage 0V – 40V (10V)
Battery voltage Low Warning Delay 0 - 24hr (1m)
Battery Voltage High Warning Active, Inactive
Battery Voltage High Warning Delay 0V - 24hr (1m)
Battery Voltage High Warning 0V – 40V (30V)
Charge Alternator Failure Warning Active, Inactive
Charge Alternator Failure Warning 0V – 39V (6V)
Charge Alternator Failure Warning Delay 0 - 24hr (5s)
Charge Alternator Failure Shutdown Active, Inactive
Charge Alternator Failure Shutdown 0V – 5.9V (4.0V)
Charge Alternator Failure Shutdown Delay 0 - 24hr (5s)
Voltage Low Shutdown 50V – 360V (184V)
Voltage Nominal 50V – 276V (230V)
Voltage High Shutdown 231V – 360V (277V)
Frequency Low Shutdown 0Hz - 75Hz (43Hz)
Frequency Nominal 0Hz - 75Hz (50Hz)
Frequency High Shutdown 0Hz - 75Hz (58Hz)
Full Load ating 5A – 6000A (500A)
Delayed Over Current Active, Inactive
Delayed Over Current 50% - 120% (100%)
AC System Single Phase, 2 Wire
3 Phase, 4 Wire
3 Phase, 4 Wire3 Phase, 4 Wire
3 Phase, 4 Wire
2 Phase, 3 Wire (L1 & L3)
3 Phase, 4 Wire (Delta)
2 Phase, 3 Wire (L1 & L2)
CT Primary 5A - 6000A (600A)
Generator Transient Delay 0 - 10m (0.7s)
ront Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Section
Parameter as shown on display
Values
MAINS Voltage Low Trip 50V – 360V (184V)
Voltage High Trip 50V – 360V (276V)
Frequency Low Trip 0Hz - 75Hz (45Hz)
Frequency High Trip 0Hz - 75Hz (55Hz)
Mains Transient Delay 0 - 30s (2s)
eturn Delay 0 - 1hr (30s)
Mains Transfer Time 0 - 10m (0.7s)
TIMERS LCD Page Timer hh:mm:ss (5m)
Auto Scroll Delay 1s - 1hr (2s)
Pre Heat Timer 0 - 5m (0s)
Crank Duration Timer 0 - 1m (10s)
Crank est Timer 0 - 1m (10s)
Safety On Delay 0 - 1m (10s)
Smoke Limiting 0 - 15m (0s)
Smoke Limiting Off 0 - 1m (0s)
Warm Up Timer 0 -1hr (0s)
Cool Down Timer 0 - 1hr (1m)
Fail To Stop Delay 0 - 2m (30s)
Battery voltage Low Warning Delay 0 - 24hr (1m)
Battery Voltage High Warning Delay 0V - 24hr (1m)
Return Delay 0 - 5hr (30s)
Generator Transient Delay 0.1s - 2m (30s)
Mains Transient Delay 0 - 30s (2s)
Mains Transfer Time 0 - 10m (0.7s)
DIMENSIONS AND MOUNTING
DIMENSIONS
216mm x 158mm x 42mm
(8.5” x 6.2” x 1.6”)
PANEL CUTOUT
182mm x 137mm
(7.2” x 5.4”)
1.1.1 WEIGHT
510g (0.51kg)
1.1.2 FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips.
•Withdrawthe fixing clip screw(turn anticlockwise) until only the pointed end is protruding from the clip.
•Insert the three ‘prongs’ of the fixing clip into the slots in the side of the 6000 series module case.
•Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are
inside their allotted slots.
•Turn the fixing clip screws clockwise until they make contact with the panel fascia.
•Turn the screws a little more to secure the module into the panel fascia. Care should be taken not to over
tighten the fixing clip screws.
NOTE:- In conditions of excessive vibration, mount the panel on suitable
anti-vibration mountings.