manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eastron
  6. •
  7. Measuring Instrument
  8. •
  9. Eastron SDM630MCT-RJV-333mV User manual

Eastron SDM630MCT-RJV-333mV User manual

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
SDM630MCT-RJV-333mV
SDM630MCT-RJA-100mA
Three phase multifunction din rail energy meter
Plug-in solution; labor saving; wiring mistake free
Measures kWh KVarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, THD,etc.
Bi-directional measurement IMP & EXP
Plug-in RJ-12 CT connection
Two pulse outputs
RS485 Modbus RTU
Din rail mounting 35mm
Better than Class 1 / B accuracy
USER MANUAL
2016 V1.1
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 1 -
1.1 Introduction
This document provides operating, maintenance and installation instructions. The unit measures
and displays the characteristics of three phase four wires supplies, including voltage, frequency,
current, power, active and reactive energy, imported or exported. Energy is measured in terms of
kWh, kVarh. Maximum demand current can be measured over preset periods of up to 60minutes.
The meter uses self-power supply module, the power is getting from L1.
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of
operation. Built-in interfaces provide pulse and Modbus outputs. Configuration is password
protected.
The meter has RJ-12 terminal for current inputs. And voltage terminals, Pulse outputs and RS485
terminals are all plug-in types. The plug-in solution is user-friendly and mistake-free. It can also
save much labor work in wiring.
1.2 Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Demand Interval time
Reset for demand measurements
Pulse output duration
RS485 Communication
CT and PT setting
Two pulse output indicates real-time energy measurement. A Modbus output allows remote
monitoring from another display or a computer.
1.3 Current inputs
The unit can be configured to operate with CT ratio between primary current and secondary
current. The secondary current is 333mV(SDM630MCT-RJV only). The secondary current is
100mA(SDM630MCT-RJA only).
1.4 Modbus
This uses a RS485 port with Modbus RTU protocol to provide a means of remotely monitoring
and controlling the Unit.
Set-up screens are provided for setting up the RS485 port.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 2 -
1.5Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The Pulse
output 1 is configurable. The pulse output 2 is fixed for the active energy, constant is
3200imp/kWh.
2. Start Up Screens
1
The first screen lights up all display segments
and can be used as a display check.
2
The second screen indicates the firmware
installed in the unit and its build number.
3
The interface performs a self-test and
indicates
The result if the test passes.
*After a short delay, the screen will display active energy measurements.
2.1 Measurements
The buttons operate as follows:
1
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back”
button.
2
Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 3 -
3
Select the Power display screens
In Set-up Mode, this is the “Down” button
4
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right”
button
Voltage and Current
Each successive pressing of the button selects a new range:
1-1
Phase to neutral voltages
2
Current on each phase
3-1
Phase to neutral voltage THD%
4
Current THD% for each phase
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 4 -
Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
1
Frequency and Power Factor (total)
2
Power Factor of each phase
3
Maximum Power Demand
4
Maximum Current Demand
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 5 -
Power
Each successive pressing of the button select a new range:
1
Instantaneous Active Power in kW
2
Instantaneous Reactive Power in kVar
3
Instantaneous Volt-amps in KVA
4
Total kW, kVarh, kVA
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 6 -
Energy Measurements
Each successive pressing of the button selects a new range:
1-1
Imported active energy in kWh
1-2
Exported active energy in kWh
2-1
Imported reactive energy in kVarh
2-2
Exported reactive energy in kVarh
3-1
Total active energy in kWh
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 7 -
3-2
Total reactive energy in kVarh
Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing.
If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Set-up Entry Methods
Some menu items, such as password and CT, require a four-digit number entry while others, such
as supply system, require selection from a number of menu options.
Menu Option Selection
1) Use the buttons and to select the required item from the menu. Selection
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 8 -
does not roll over between bottom and top of list
2) Press to confirm your selection
3) If an item flashes, then it can be adjusted by the buttons and . If not, there may
be a further layer.
4) Having selected an option from the current layer, press to confirm your selection. The
SET indicator will appear.
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the buttons of and
for further menu selection.
6) On completion of all setting-up, press repeatedly until the measurement screen is
restored.
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3) After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
Change password
1
Use the and to choose
the change password option
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 9 -
2-1
Press the button to enter the
change password routine. The new
password screen will appear with the first
digit flashing
2-2
Use and to set the first
digit and press to confirm your
selection. The next digit will flash.
2-3
Repeat the procedure for the remaining
three digits
2-4
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 10 -
DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
maximum demand measurement. The options are: off, 5, 8, 10, 15, 20, 30, 60 minutes
1
From the set-up menu, use and
buttons to select the DIT option.
The screen will show the currently
selected integration time.
2-1
Press to enter the selection
routine. The current time interval will
flash
2-2
Use and to select the time
required.
2-3
Press to confirm the selection.
SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 11 -
Backlit set-up
The meter provides a function to set the blue backlit lasting time.
1
The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s set as 5, the backlit
will be off in 5minutes from the last time
operation on the meter.
Notes: If it’s set as 0, the backlit will
always be on.
2
Press to enter the selection
routine. The current time interval will
flash
The options can be:
0/5/10/30/60/120minutes
Use and buttons to select the time required. Then press to confirm
the set-up,
CT(For SDM630MCT-RJV only)
The CT option sets the Primary current (CT1) of the current transformer (CT) that wires to the
meter.
1
From the Set-up menu, use and
buttons to select the CT option.
the CT secondary Voltage:0.333V
2
Set CT Ratio value
Press to enter the Primary
current screen. The range is from 0005 to
9999A.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 12 -
CT (For SDM630MCT-RJA only)
The CT option sets the Primary current (CT1) of the current transformer (CT) that wires to the
meter.
1
From the Set-up menu, use and
buttons to select the CT option.
the CT secondary Voltage:0.1A
2
Set CT Ratio value
Press to enter the Primary
current screen. The range is from 0005 to
9999A.
PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
1
From the Set-up menu, use and
buttons to select the PT option.
The screen will show the voltage PT
secondary voltage value. The default
value is 400V
2
Secondary PT setting
Press to enter the PT secondary
voltage selection routine. The range is
from 100 to 500V
3
Set PT ratios value
Press to enter the PT ratio
screen.
The range is from 0001 to 2000
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 13 -
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVarh
1
From the Set-up menu, use and
buttons to select the Pulse
output option.
2
Press to enter the selection
routine. The unit symbol will flash.
3
Use and buttons to
choose kWh or kVarh.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 14 -
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100/1000kWh.
(It shows 1 impulse = 10kWh/kVarh)
1
From the Set-up menu, use and
buttons to select the Pulse Rate
option.
2
Press to enter the selection
routine. The current setting will flash.
0.01/0.1/1/10/100/1000kWh/kVarh per
pulse
Use and buttons to choose pulse rate. On Completion of the entry procedure,
press to confirm the setting and press to return to the main set up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be 200, 100 or 60ms.
(It shows pulse width of 200ms)
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 15 -
1-1
From the Set-up menu, use and
buttons to select the Pulse width
option.
1-2
Press to enter the selection
routine. The current setting will flash.
Use and buttons to
choose pulse width.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Communication
There is a Modbus port can be used for communication using Modbus protocol. For Modbus
communication, parameters are selected from Front panel.
Modbus Address
1
From the Set-up menu, use and
buttons to select the first
Address
2-1
Press button to enter the
selection routine. The current setting
will be flashing.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 16 -
2-2
Use and buttons to
choose the first Address(001 to 247)
On completion of the entry procedure, press button to confirm the setting and press
button to return the main set-up menu.
Baud Rate
1
From the Set-up menu, use and
buttons to select the Baud Rate
option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k,
38.4k
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 17 -
Parity
1
From the Set-up menu, use and
buttons to select the Parity
option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Parity (EVEN / ODD/ NONE)
Default is NONE.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Stop bits
1
From the Set-up menu, use and
buttons to select the Stop Bit
option.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 18 -
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Stop Bit (2 or 1)
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use and
buttons to select the reset
option.
2
Press to enter the selection
routine. The MD will flash.
Press to confirm the setting and press to return to the main set up menu.
EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 19 -
Reverse connected current inputs correction set-up
1
use and buttons to
select page “SET sys cont”
2-1
Press to enter Phase A , the
default is Frd (forward)
2-2
use and buttons to
Phase B or C setting pages
How to operate if phase A is reversely connected
1
Go to phase A setting page
2
Press to enter the selection
routine. The Frd will flash.
Use button to change Frd to Rev.
Press to confirm the setting and press to return to the main set up menu.

This manual suits for next models

1

Other Eastron Measuring Instrument manuals

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM630-Modbus V2 User manual

Eastron

Eastron SDM630-Modbus V2 User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM630-Mbus V2 User manual

Eastron

Eastron SDM630-Mbus V2 User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630MCT-RC User manual

Eastron

Eastron SDM630MCT-RC User manual

Eastron SDM630-EV User manual

Eastron

Eastron SDM630-EV User manual

Eastron SMART X96-RC User manual

Eastron

Eastron SMART X96-RC User manual

Eastron SDM630M CT User manual

Eastron

Eastron SDM630M CT User manual

Eastron SDM230-LoRaWAN User manual

Eastron

Eastron SDM230-LoRaWAN User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM530-Modbus User manual

Eastron

Eastron SDM530-Modbus User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM630Pulse User manual

Eastron

Eastron SDM630Pulse User manual

Eastron SDM120 Modbus User manual

Eastron

Eastron SDM120 Modbus User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM230 Series User manual

Eastron

Eastron SDM230 Series User manual

Eastron SDM320-C User manual

Eastron

Eastron SDM320-C User manual

Eastron SDM630MCT-MOD-MID User manual

Eastron

Eastron SDM630MCT-MOD-MID User manual

Eastron SDM120-CT-MV User manual

Eastron

Eastron SDM120-CT-MV User manual

Eastron SDM220-Modbus User manual

Eastron

Eastron SDM220-Modbus User manual

Popular Measuring Instrument manuals by other brands

Bender ISOMETER isoHR1685DW-925 manual

Bender

Bender ISOMETER isoHR1685DW-925 manual

Endress+Hauser Deltatop DP71B technical information

Endress+Hauser

Endress+Hauser Deltatop DP71B technical information

KROHNE BM 26 BASIC Supplementary instructions

KROHNE

KROHNE BM 26 BASIC Supplementary instructions

Bosch FSA 500 Original instructions

Bosch

Bosch FSA 500 Original instructions

BD Sensors BD SIMEX PAC-73T user manual

BD Sensors

BD Sensors BD SIMEX PAC-73T user manual

Riftek RF656XY-35 user manual

Riftek

Riftek RF656XY-35 user manual

Technische Alternative CAN-EZ3 General information, Installation and connection, Relevant functions

Technische Alternative

Technische Alternative CAN-EZ3 General information, Installation and connection, Relevant functions

AERMEC AERWEB300 installation manual

AERMEC

AERMEC AERWEB300 installation manual

Conrad SB-090 Safety instruction

Conrad

Conrad SB-090 Safety instruction

Delmhorst Instrument Co RC-1E owner's manual

Delmhorst Instrument Co

Delmhorst Instrument Co RC-1E owner's manual

Hanna Instruments HI 250 instruction manual

Hanna Instruments

Hanna Instruments HI 250 instruction manual

Endress+Hauser Micropilot S FMR531 manual

Endress+Hauser

Endress+Hauser Micropilot S FMR531 manual

MFJ Enterprises MFJ-872 instruction manual

MFJ Enterprises

MFJ Enterprises MFJ-872 instruction manual

smart-me 212062 quick start guide

smart-me

smart-me 212062 quick start guide

Kroeplin D Series user manual

Kroeplin

Kroeplin D Series user manual

Nidec Kato Engineering KRM2000 user manual

Nidec

Nidec Kato Engineering KRM2000 user manual

HCI TPM-W204 user manual

HCI

HCI TPM-W204 user manual

Oakton pH 5+ instruction manual

Oakton

Oakton pH 5+ instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.