manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eastron
  6. •
  7. Measuring Instrument
  8. •
  9. Eastron SDM630MCT V2 User manual

Eastron SDM630MCT V2 User manual

Other manuals for SDM630MCT V2

2

Other Eastron Measuring Instrument manuals

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM230 Series User manual

Eastron

Eastron SDM230 Series User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM72DM User manual

Eastron

Eastron SDM72DM User manual

Eastron SDM320-C User manual

Eastron

Eastron SDM320-C User manual

Eastron SDM630MV-2L User manual

Eastron

Eastron SDM630MV-2L User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM630MCT-RC User manual

Eastron

Eastron SDM630MCT-RC User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM630MCT-MBUS V2 User manual

Eastron

Eastron SDM630MCT-MBUS V2 User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SMART X96 Series User manual

Eastron

Eastron SMART X96 Series User manual

Eastron SDM630MCT-2L User manual

Eastron

Eastron SDM630MCT-2L User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SMART X96-RC User manual

Eastron

Eastron SMART X96-RC User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM220-MBUS User manual

Eastron

Eastron SDM220-MBUS User manual

Eastron SDM230-LoRaWAN User manual

Eastron

Eastron SDM230-LoRaWAN User manual

Eastron SDM630MCT-ML User manual

Eastron

Eastron SDM630MCT-ML User manual

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.eastron-germany.de info@bg-etech.de
SDM630MCT V2
DIN Rail Energy Meter for Single and Three Phase Electrical Systems
⚫Measures kWh Kvarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, THD,etc.
⚫Bi-directional measurement IMP & EXP
⚫Two pulse outputs
⚫RS485 Modbus
⚫Din rail mounting 35mm
⚫1/5A CT connection
⚫Better than Class 1 / B accuracy
USER MANUAL
2016 V4.8
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 1 -
Introduction
This document provides operating, maintenance and installation instructions. The unit measures
and displays the characteristics of single phase two wires (1p2w), three phase three wires(3p3w,)
and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active
and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60minutes. In order to
measure energy, the unit requires voltage and current inputs in addition to the supply required to
power the product. The requisite current input(s) are obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of
operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is
password protected.
This unit can be powered from a separate auxiliary (AC or DC) supply. Alternatively it can be
powered from the monitored supply, where appropriate.
Unit Characteristics
The Unit can measure and display:
⚫Line voltage and THD% (total harmonic distortion) of all phases
⚫Line Frequency
⚫Currents, Current demands and current THD% of all phases
⚫Power, maximum power demand and power factor
⚫Active energy imported and exported
⚫Reactive energy imported and exported
The unit has password-protected set-up screens for:
⚫Changing password
⚫Supply system selection 1p2w, 3p3w,3p4w
⚫Demand Interval time
⚫Reset for demand measurements
⚫Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
Current Transformer Primary Current
The unit can be configured to operate with CT ratio between primary current and secondary
current. The secondary CT has two options: 1A/5A
RS485 Serial –Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 2 -
Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
for active energy is 3200imp/kWh (Terminals 11&12). The pulse width for pulse 1 (Terminals
9&10) can be set from the set-up menu.
Start Up Screens
1
The first screen lights up all display
segments and can be used as a display
check.
2
The second screen indicates the
firmware installed in the unit and its
build number.
3
The interface performs a self-test and
indicates
the result if the test passes.
*After a short delay, the screen will display active energy measurements.
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 3 -
Measurements
The buttons operate as follows:
1
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back”
button.
2
Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
3
Select the Power display screens
In Set-up Mode, this is the “Down” button
4
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right”
button
Voltage and Current
Each successive pressing of the button selects a new range:
1-1
Phase to neutral voltages(3p4w)
1-2
Phase to neutral voltages(3p3w)
2
Current on each phase
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 4 -
3-1
Phase to neutral voltage THD%(3p4w)
3-2
Phase to neutral voltage THD%(3p3w)
4
Current THD% for each phase
Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
1
Frequency and Power Factor (total)
2
Power Factor of each phase
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 5 -
3
Maximum Power Demand
4
Maximum Current Demand
Power
Each successive pressing of the button select a new range:
1
Instantaneous Active Power in kW
2
Instantaneous Reactive Power in kVAr
3
Instantaneous Volt-amps in KVA
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 6 -
4
Total kW, kVArh, kVA
Energy Measurements
Each successive pressing of the button selects a new range:
1-1
Imported active energy in kWh
1-2
Exported active energy in kWh
2-1
Imported reactive energy in kVArh
2-2
Exported reactive energy in kVArh
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 7 -
3-1
Total active energy in kWh
3-2
Total reactive energy in kVArh
Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing.
If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 8 -
Set-up Entry Methods
Some menu items, such as password and CT, require a four-digit number entry while others, such
as supply system, require selection from a number of menu options.
Menu Option Selection
1) Use the and buttons to select the required item from the menu. Selection
does not roll over between bottom and top of list
2) Press to confirm your selection
3) If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
The SET indicator will appear.
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the and buttons for
further menu selection.
6) On completion of all setting-up, press repeatedly until the measurement screen is
restored.
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3) After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
B+G e-tech and EASTRON SDM630MCT V2 User Manual
B+G e-tech GmbH www.stromzähler.eu info@bg-etech.de
- 9 -
Change password
1
Use the and to
choose the change password option
2-1
Press the to enter the change
password routine. The new password
screen will appear with the first digit
flashing
2-2
Use and to set the
first digit and press to confirm
your selection. The next digit will flash.
2-3
Repeat the procedure for the remaining
three digits
2-4
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed