Eastron SDM530-MT User manual

Eastron SDM530-MT User Manual
- 1 -
SDM530-MT
Three Phase Multi-function DIN rail meter
Measures kWh Kvarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
4 tariffs,10 time segments
Better than Class 1 / B accuracy
USER MANUAL
2015 V1.5
Eastron SDM530-MT User Manual
- 2 -
Introduction
The SDM530-MT measures and displays the characteristics of three phase four wires (3p4w)
supplies, including voltage, frequency, current, power, active and reactive energy, imported or
exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be
measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires
voltage and current inputs in addition to the supply required to power the product.
SDM530MT-MT supports max. 100A direct connection, saves the cost and avoid the trouble to
connect external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces
provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
Unit Characteristics
The Unit can measure and display:
Line voltage
Line Frequency
Currents, Current demands
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Demand Interval Time(DIT)
Reset for demand measurements
Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
RS485 Serial–Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.
Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
of pulse output 2 for active energy is 400imp/kWh, its width is fixed at 100ms.
The default constant of configurable pulse output 1 is 400imp/kWh default pulse width
is100ms.The configurable pulse output 1 can be set from the set-up menu.
Eastron SDM530-MT User Manual
- 3 -
Start-up Screens
1
The first screen lights up all display
segments and can be used as a display
check
2
The second screen indicates the
firmware installed in the unit and its
build number.
3
The interface performs a self-test and
indicates the result if the test passes.
After 5 seconds delay, the screen will display active energy measurements.
Measurements
The buttons operate as follows:
1
Select the Voltage and Current display screens
In Set-up Mode, this is the “Up” or “back”button
2
Select the Power, Frequency and Power factor
display screens
In Set-up Mode, this is the “Down” button
3
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right”
button
Eastron SDM530-MT User Manual
- 4 -
Voltage and Current and Max Demand
Each successive pressing of the button selects a new range:
1-1
Phase to neutral voltages
1-2
Phase to neutral voltages
2-1
Current on each phase
2-2
Neutral current
3
Maximum Current Demand
Eastron SDM530-MT User Manual
- 5 -
Power and Frequency and Power factor
Each successive pressing of the button selects a new range:
1-1
Instantaneous Active Power in kW
When it’s exported, there will be a mark
of minus “-”.
1-2
Instantaneous Reactive Power in kVAr
When it’s exported, there will be a mark
of minus “-”.
1-3
Instantaneous Volt-amps in KVA
When it’s exported, there will be a mark
of minus “-”.
1-4
Total kW, kVArh, kVA
When it’s exported, there will be a mark
of minus “-”.
2
Frequency and Power Factor (total)
Eastron SDM530-MT User Manual
- 6 -
3
Power Factor of each phase
4
Maximum Power Demand
Energy Measurements
Each successive short pressing (lasting less than 3s) of the button selects a new
range:
1-1
Total active energy in kWh
Total kWh=imported +exported (kWh)
1-2
Total Imported active energy in kWh
1-3
Total Exported active energy in kWh
Eastron SDM530-MT User Manual
- 7 -
2-1
Tariff 1 Active energy
2-2
Tariff 2 Active energy
2-3
Tariff 3 Active energy
2-4
Tariff 4 Active energy
3-1
Total reactive energy in kVArh
Total kVArh=imported +exported (kVArh)
3-2
Imported reactive energy in kVArh
Eastron SDM530-MT User Manual
- 8 -
3-3
Exported reactive energy in kVArh
4-1
Tariff 1 Reactive energy
4-2
Tariff 2 Reactive energy
4-3
Tariff 3 Reactive energy
4-4
Tariff 4 Reactive energy
5-1
Date
Example:1st,Jan,2000
Eastron SDM530-MT User Manual
- 9 -
5-2
Time
Hour: minute: second
00:02:16
Set-up
To enter set-up mode, long pressing the button for 2 seconds, until the password
screen appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Menu Option Selection
1) Use the and buttons to select the required item from the menu
2) Press to confirm your selection
3) If an item flashes, then it can be adjusted by the and buttons. If not,
there maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
The SET indicator will appear.
Eastron SDM530-MT User Manual
- 10 -
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the and
buttons for further menu selection.
6) On completion of all set-up, press repeatedly until the measurement screen is
restored.
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit
has been set.
3) After setting the last digit, press to exit the number setting routine. The SET
indicator will be removed.
Change password
1
Use the and to
choose the change password option
2-1
Press the to enter the
change password routine. The new
password screen will appear with the
first digit flashing
Eastron SDM530-MT User Manual
- 11 -
2-2
Use and to set
the first digit and press to
confirm your selection. The next digit will
flash.
2-3
Repeat the procedure for the remaining
three digits
2-4
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will
be removed
DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
maximum demand measurement. The options are: 1, 5, 8,10, 15, 30,60 minutes
1
From the set-up menu,
use and buttons
to select the DIT option. The screen will
show the currently selected integration
time.
Default is 60
2-1
Press to enter the selection
routine.
The current time interval will flash
Eastron SDM530-MT User Manual
- 12 -
2-2
Use and
buttons to select the time required.
2-3
Press to confirm the
selection. SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
Backlit set-up
1
The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s setted as 5,the
backlit will be off in 5minutes from the
last time operation on the meter.
2
Press to enter the selection
routine. The current time interval will
flash.
The options can be:0/10/30/60/120
“0”means always on
Default lasting time is 60minutes
Use and buttons to select the time required. Press to
confirm the set-up,
Pulse output
This option allows you to configure the pulse output 1. The output can be set to provide a pulse
for a defined amount of energy active or reactive.
Use this section to set up the pulse output for:
Total kWh/ Total kVArh
Active kWh/Reactive kWh
Active kVArh/Reactive kVArh
Eastron SDM530-MT User Manual
- 13 -
1
From the Set-up menu, use
and buttons to select the
Pulse output option.
2-1
Press to enter the selection
routine. The unit symbol will flash.
2-2
Use and buttons
to choose kWh or kVArh.
Default is kwh
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
DFt/0.1/1/10/100kWh/kVArh.
(It shows 1 impulse = 0.01kWh/kVArh)
1
From the Set-up menu, use
and buttons to select the
Pulse Rate option.
Eastron SDM530-MT User Manual
- 14 -
2
Press to enter the selection
routine. The current setting will flash.
Default is DFt (2.5kWh/kVArh).
Use and buttons to choose pulse rate. On completion of the entry
procedure, press to confirm the setting and press to return to the
main set up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as
200, 100(default) or 60ms.
(It shows pulse width of 100ms)
1-1
From the Set-up menu, use
and buttons to select the
Pulse width option.
1-2
Press to enter the selection
routine. The current setting will flash.
Default is 100
Use and buttons to choose pulse width. On completion of the entry
procedure, press to confirm the setting and press to return to the
main set up menu.
Eastron SDM530-MT User Manual
- 15 -
Scroll display
1-1
From the Set-up menu, use
and buttons to select the
Scroll display option.
1-2
Press to enter the selection
routine. The current setting will flash.
The options can be:1 to255 Seconds
Default is 255s
Use and buttons to choose interval of scroll display. On completion of
the entry procedure, press to confirm the setting and press to return
to the main set up menu. To activate the scroll display mode, press the lasting for
2seconds on the main interface. To close it, press button lasting for 2seconds
accordingly. The default status of scroll display is closed.
Communication
There is a RS485 port can be used for communication using Modbus RTU protocol.
RS485 Address
(The range is from 001 to 247)
1
From the Set-up menu, use
and buttons to select the
Address ID
Eastron SDM530-MT User Manual
- 16 -
2-1
Press button to enter the
selection routine. The current setting will
be flashing.
2-2
Use and
buttons to choose Modbus Address(001
to 247) Default is 001
On completion of the entry procedure, press button to confirm the setting and
press button to return the main set-up menu.
Baud Rate
1
From the Set-up menu, use
and buttons to select the
Baud Rate option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and
buttons to choose Baud rate 1.2K.2.4k.
4.8k, 9.6k (default.)
Eastron SDM530-MT User Manual
- 17 -
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Parity
1
From the Set-up menu, use
and buttons to select the
Parity option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons
to choose Parity (EVEN / ODD / NONE)
Default is NONE
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Stop bits
1
From the Set-up menu, use
and buttons to select the
Stop Bit option.
Eastron SDM530-MT User Manual
- 18 -
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons
to choose Stop Bit (2 or 1)
Default is 1.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use
and buttons to select the
reset option.
2
Press to enter the selection
routine. The MD will flash.
Press to confirm the setting and press to return to the main set up
menu.
Eastron SDM530-MT User Manual
- 19 -
Specifications
Measured Parameters
The unit can monitor and display the following parameters of four phase four wires(3p4w) supply.
Voltage and Current
Phase to neutral voltages 176 to 274V a.c.
Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 85000 W
Reactive Power 0 to 85000 VAr
Volt-amps 0 to 85000 VA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset
Energy Measurements
Imported active energy 0 to 999999.99 kWh
Exported active energy 0 to 999999.99 kWh
Imported reactive energy 0 to 999999.99 kVArh
Exported reactive energy 0 to 999999.99 kVArh
Total active energy 0 to 999999.99 kWh
Total reactive energy 0 to 999999.99 kVArh
Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±1% of range maximum
Interfaces for External Monitoring
Three interfaces are provided:
an RS485 communication channel that can be programmed via protocol remotely.
an Pulse output(Pulse 1) indicating real-time measured energy.(configurable)
an Pulse output(Pulse 2)
The Modbus configuration (Baud rate etc.) and the pulse output assignments (kW/kVArh,
import/export etc.) are configured through the Set-up screens.
Pulse Output
Eastron SDM530-MT User Manual
- 20 -
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total /
import/export kWh or kVarh.
The pulse constant can be set to generate 1 pulse per:
DFt=2.5 Wh/VArh
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10=10Wh/kVArh
100 = 100 kWh/kVArh
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with active kWh. The constant is 400imp/kWh.
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the
Set-up menu:
Baud rate 1200, 2400, 4800, 9600
Parity none (default)/odd/even
Stop bits 1 or 2
RS485 network address nnn –3-digit number, 001 to 247
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is
verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor < 0·005)
Magnetic field of external origin Terrestrial flux
Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Dimensions

Other Eastron Measuring Instrument manuals

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM630MCT-ML User manual

Eastron

Eastron SDM630MCT-ML User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM120-CT-MV User manual

Eastron

Eastron SDM120-CT-MV User manual

Eastron SDM630MCT-RJV-333mV User manual

Eastron

Eastron SDM630MCT-RJV-333mV User manual

Eastron SDM120C User manual

Eastron

Eastron SDM120C User manual

Eastron SDM120CTM User manual

Eastron

Eastron SDM120CTM User manual

Eastron SMART X96 Series User manual

Eastron

Eastron SMART X96 Series User manual

Eastron SDM72DM User manual

Eastron

Eastron SDM72DM User manual

Eastron SDM630-2T User manual

Eastron

Eastron SDM630-2T User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM530Y User manual

Eastron

Eastron SDM530Y User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM220-MBUS User manual

Eastron

Eastron SDM220-MBUS User manual

Eastron SDM630MV-2L User manual

Eastron

Eastron SDM630MV-2L User manual

Eastron SDM630-Modbus V2 User manual

Eastron

Eastron SDM630-Modbus V2 User manual

Eastron SDM630-Modbus V2 User manual

Eastron

Eastron SDM630-Modbus V2 User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Popular Measuring Instrument manuals by other brands

Unit UTS3000B/A Series user manual

Unit

Unit UTS3000B/A Series user manual

Sensor Therm METIS H3 series user manual

Sensor Therm

Sensor Therm METIS H3 series user manual

Macnaught M1 SERIES instruction manual

Macnaught

Macnaught M1 SERIES instruction manual

parktool TS-2Di instructions

parktool

parktool TS-2Di instructions

red lion PAX LITE PAXLCR Series manual

red lion

red lion PAX LITE PAXLCR Series manual

Delta DPM-C320 Operation manual

Delta

Delta DPM-C320 Operation manual

Microtech 14109805 Series manual

Microtech

Microtech 14109805 Series manual

PerkinElmer Lambda 365 installation instructions

PerkinElmer

PerkinElmer Lambda 365 installation instructions

CANchecked MFD15 quick start guide

CANchecked

CANchecked MFD15 quick start guide

red lion PAX2S000 installation guide

red lion

red lion PAX2S000 installation guide

Delta OHM HD51.3D4R operating manual

Delta OHM

Delta OHM HD51.3D4R operating manual

Isotech Fast-Cal Series User maintenance manual/handbook

Isotech

Isotech Fast-Cal Series User maintenance manual/handbook

i-PRO WJ-NU301K Series installation guide

i-PRO

i-PRO WJ-NU301K Series installation guide

HANYOUNG NUX MP3 instruction manual

HANYOUNG NUX

HANYOUNG NUX MP3 instruction manual

LineEye LE-8500X-RT instruction manual

LineEye

LineEye LE-8500X-RT instruction manual

FRO­NIUS 63A-1 operating instructions

FRO­NIUS

FRO­NIUS 63A-1 operating instructions

A-MSystems 2100 instruction manual

A-MSystems

A-MSystems 2100 instruction manual

Quantel ULTRA quick start guide

Quantel

Quantel ULTRA quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.