EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
SDM630MCT Series
DIN Rail Energy Meter for Single and Three Phase Electrical Systems
Measures kWh Kvarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, THD,etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
1/5A CT connection
Better than Class 0.5S
USER MANUAL 2019
2019 V1.1
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 1 -
Introduction
This document provides operating, maintenance and installation instructions. The unit measures
and displays the characteristics of single phase two wires (1p2w), Single phase(split-phase) three
wire(1p3w), three phase three wires(3p3w,) and three phase four wires(3p4w) supplies, including
voltage, frequency, current, power ,active and reactive energy, imported or exported. Energy is
measured in terms of kWh, kVArh. Maximum demand current can be measured over preset
periods of up to 60minutes. In order to measure energy, the unit requires voltage and current
inputs in addition to the supply required to power the product. The requisite current input(s) are
obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of
operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is
password protected.
This unit can be powered from a separate auxiliary (AC or DC) supply. Alternatively it can be
powered from the monitored supply, where appropriate.
Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Supply system selection 1p2w, 1p3w,3p3w,3p4w
Demand Interval time
Reset for demand measurements
Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
Current Transformer Primary Current
The unit can be configured to operate with CT ratio between primary current and secondary
current. The secondary CT has two options: 1A/5A
RS485 Serial –Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 2 -
Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
for active energy is 3200imp/kWh(Terminals 11&12). The pulse width for pulse 1(Terminals 9&10)
can be set from the set-up menu.
Description of under-range and over range display
1, Display Description of Under-range and Over-range parameters:
On the voltage, current and power, etc. displays, when the parameters mesured are under-range,
the display will show “0”. when the parameters are over-range, two interfaces will be shown by
turns. One is the current measured value and the other is with “-“ symbol.
For example:
If the voltage is overrange, the display of voltage will show below two interfaces in rotation:
Interface 1
Interface 2
2, Explanation of the threshold of Underrange and Overrange:
Threshold of Under-range:
A, Voltage: < 30V (for L-N / L-L);
B, Current: < 0.004A (for L-N / L-L);
C, Power: < 1W(VAr)(VA) (for L-N / L-L);
Threshold of Over-range:
A, Voltage: > 305V (for L-N);Voltage: > 530V (for L-L);
B, Current: > 6A (for L-N / L-L);
C, Power: > 1830W(VAr)(VA) (for L-N);Power: > 3180W(VAr)(VA) (for L-L);
Note: The threshold value of under-range and over-range is the secondary value of the meter. CT
and PT ratio are not included.
For example:
if the CT ratio is 10, it is under-range when the current is less than 0.04A (=0.004*10); It is
over-range when the current is over 60A (=6*10).
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 3 -
Start Up Screens
1
The first screen lights up
all display
segments and can be used as a display
check.
2
The second screen indicates the
firmware installed in the unit and its
build number.
3
The interface performs a self-test and
indicates
the result if the test passes.
*After a short delay, the screen will display active energy measurements.
Measurements
The buttons operate as follows:
1
Selects the Voltage and Current display screens
In Set-
up Mode, this is the “Left” or “Back”
button.
2
Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
3
Select the Power display screens
In Set-up Mode, this is the “Down” button
4
Select the Energy display screens
In Set-
up mode, this is the “Enter” or “Right”
button
Voltage and Current
Each successive pressing of the button selects a new range:
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 4 -
1
Phase to neutral voltages
2
Phase to neutral voltages
3
Current on each phase
4
Neutral current
5-1
Phase to neutral voltage THD%(3p4w)
5-2
Phase to neutral voltage THD%(3p3w)
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 5 -
6
Current THD% for each phase
Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
1
Frequency and Power Factor (total)
2
Power Factor of each phase
3
Maximum Current Demand
4
Maximum Power Demand
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 6 -
Power
Each successive pressing of the button select a new range:
1
Instantaneous Active Power in kW
2
Instantaneous Reactive Power in kVAr
3
Instantaneous Volt-amps in KVA
4
Total kW, kVArh, kVA
Energy Measurements
Each successive pressing of the button selects a new range:
1, Only SDM630MCT display
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 7 -
1
Total active energy in kWh
2
Total reactive energy in kVArh
3
Imported active energy in kWh
4
Exported active energy in kWh
5
Imported reactive energy in kVArh
6
Exported reactive energy in kVArh
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 8 -
2, Only SDM630MCT-2T display
1
Total active energy in kWh
2
T1 Total active energy in kWh
3
T2 Total active energy in kWh
4
Total reactive energy in kVArh
5
T1 Total reactive energy in kVArh
6
T2 Total reactive energy in kVArh
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 9 -
3, Only SDM630MCT-MT display
1
Total active energy in kWh
2
T1 Total active energy in kWh
3
T2 Total active energy in kWh
4
T3 Total active energy in kWh
5
T4 Total active energy in kWh
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 10
6
Total reactive energy in kVArh
7
T1 Total reactive energy in kVArh
8
T2 Total reactive energy in kVArh
9
T3 Total reactive energy in kVArh
10
T4 Total reactive energy in kVArh
Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 11
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing.
If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Set-up Entry Methods
Some menu items, such as password and CT, require a four-digit number entry while others, such
as supply system, require selection from a number of menu options.
Menu Option Selection
1) Use the and buttons to select the required item from the menu. Selection
does not roll over between bottom and top of list
2) Press to confirm your selection
3) If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
5) Having completed a parameter setting, press to return to a higher menu level. You
will be able to use the and buttons for further menu selection.
6) On completion of all setting-up, press repeatedly until the measurement screen is
restored.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 12
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3) After setting the last digit, press to exit the number setting routine.
Change password
1
Use the and to
choose the change password option
2-1
Press the to e
nter the change
password routine. The new password
screen will appear with the first digit
flashing.
2-2
Use and
to set the
first digit and press t
o confirm
your selection. The next digit will flash.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 13
2-3
Repeat the procedure for the remaining
three digits.
2-4
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed
DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
maximum demand measurement. The options are: off, 5, 8, 10, 15,20, 30, 60 minutes
1
From the set-up menu, use and
buttons to select the DIT
option. The screen will show the
currently selected integration time.
2-1
Press
to enter the selection
routine. The current time interval will
flash.
2-2
Use and
buttons to
select the time required.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 14
2-3
Press to confirm the selection.
SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
Backlit set-up
The meter provides a function to set the blue backlit lasting time.
1
The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s set as 5, the backlit
will be off in 5minutes from the last time
operation on the meter.
Notes: If it’s set as 0,
the backlit will
always be on.
2
Press
to enter the selection
routine. The current time interval will
flash
The options can be:
0/5/10/30/60/120minutes
Use and buttons to select the time required. Then press to
confirm the set-up,
Supply System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use
and
buttons to select the System
option. The screen will show the
currently selected power supply.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 15
2
Press
to enter the selection
routine. The current selection will flash.
3-1
Use and
buttons to
select the required system option:
1P2(W), 1P3(W),3P3(W) ,3P4(W).
3-2
Press to confirm the selection.
SET indicator will appear.
Press to exit the system selection routine and return to the menu. SET will disappear
and you will be returned to the main Set-up Menu
CT
The CT option sets the secondary current (CT2 1A or 5A) of the current transformer (CT) that
wires to the meter.
1
From the Set-up menu, use and
buttons to select the CT option.
2
Secondary CT setting
Press
to enter the CT
secondary
current selection
routine.:5A/1A
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 16
3
Set CT 1 value
Press
to enter the CT Ratio
setting screen. The range is from 0001 to
9999.
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
1
From the Set-up menu, use a
nd
buttons to select the PT option.
The screen will show the voltage PT
secondary
voltage value. The default
value is 400V
2
Secondary PT setting
Press
to enter the PT
secondary voltage selection routine. The
range is from 100 to 500V
3
Set PT 1 value
Press to enter the PT ratio
screen.
The range is from 0001 to 9999
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVArh
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 17
1
From the Set-up menu, use and
buttons to select the Pulse
output option.
2
Press
to enter the selection
routine. The unit symbol will flash.
3
Use and
buttons to
choose kWh or kVArh.
On completion of the entry procedure, press
to confirm the setting and press
to return to the main set up menu.
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100/1000kWh.
(It shows 1 impulse = 10kWh/kVArh)
1
From the Set-up menu, use
and
buttons to select the
Pulse Rate option.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 18
2
Press to
enter the selection
routine. The current setting will flash.
0.01/0.1/1/10/100/1000kWh/kVA
rh per
pulse
Use and buttons to choose pulse rate. On Com
pletion of the entry
procedure, press to confirm the setting and press to return to the main set
up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be 200, 100 or 60ms.
(It shows pulse width of 200ms)
1-1
From the Set-up menu, use
and
buttons to select the Pulse
width option.
1-2
Press
to enter the selection
routine. The current setting will flash.
Use and
buttons to
choose pulse width.
On completion of the entry procedure, press
to confirm the setting and press
to return to the main set up menu.
EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 19
Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
RS485 Address
(The range is from 001 to 247)
1
From the Set-up menu, use
and
buttons to select the
Address ID
2-1
Press
button to enter the
selection routine. The current setting will
be flashing.
2-2
Use and buttons to
choose Modbus Address(001 to 247)
On completion of the entry procedure, press button to confirm the setting and press
button to return the main set-up menu.
Baud Rate

Other manuals for SDM630MCT Series

1

This manual suits for next models

2

Other Eastron Measuring Instrument manuals

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630MCT-MBUS V2 User manual

Eastron

Eastron SDM630MCT-MBUS V2 User manual

Eastron SDM630MCT-2L User manual

Eastron

Eastron SDM630MCT-2L User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM72DM User manual

Eastron

Eastron SDM72DM User manual

Eastron SDM630-MT V2 User manual

Eastron

Eastron SDM630-MT V2 User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM630-Mbus V2 User manual

Eastron

Eastron SDM630-Mbus V2 User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM630D User manual

Eastron

Eastron SDM630D User manual

Eastron SDM630MCT-RC User manual

Eastron

Eastron SDM630MCT-RC User manual

Eastron SDM220-MBUS User manual

Eastron

Eastron SDM220-MBUS User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630 User manual

Eastron

Eastron SDM630 User manual

Eastron SDM230 Series User manual

Eastron

Eastron SDM230 Series User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SMART X96 Series User manual

Eastron

Eastron SMART X96 Series User manual

Popular Measuring Instrument manuals by other brands

Agilent Technologies 4338B Service manual

Agilent Technologies

Agilent Technologies 4338B Service manual

Polimaster PM1603A operating manual

Polimaster

Polimaster PM1603A operating manual

DynaQuip WaterCop Classic Owner's manual & installation guide

DynaQuip

DynaQuip WaterCop Classic Owner's manual & installation guide

NOVANEX BLUE Line ESR quick start guide

NOVANEX

NOVANEX BLUE Line ESR quick start guide

Akron Style operating instructions

Akron

Akron Style operating instructions

Keysight N2894-60002 user guide

Keysight

Keysight N2894-60002 user guide

Hydrotechnik MultiSystem 4070 operating instructions

Hydrotechnik

Hydrotechnik MultiSystem 4070 operating instructions

NKT Photonics SuperK COMPACT Product guide

NKT Photonics

NKT Photonics SuperK COMPACT Product guide

Teledyne SP Devices ADQ7 quick start guide

Teledyne SP Devices

Teledyne SP Devices ADQ7 quick start guide

Testboy 70 operating instructions

Testboy

Testboy 70 operating instructions

KMC Controls TRUEFIT MEP-4552 installation guide

KMC Controls

KMC Controls TRUEFIT MEP-4552 installation guide

OPW 200TG Installation and maintenance instructions

OPW

OPW 200TG Installation and maintenance instructions

AGFA 4406/027 installation manual

AGFA

AGFA 4406/027 installation manual

ATAGO PAL-50S instruction manual

ATAGO

ATAGO PAL-50S instruction manual

LDG MC-7600 quick start guide

LDG

LDG MC-7600 quick start guide

Applent Instruments AT2818 user guide

Applent Instruments

Applent Instruments AT2818 user guide

Landis+Gyr E650 Series user manual

Landis+Gyr

Landis+Gyr E650 Series user manual

Klein 3313 Assembly instruction

Klein

Klein 3313 Assembly instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.