  9. Eaton 600 A 35 kV Class Insulated Standoff Bushing User manual

Eaton 600 A 35 kV Class Insulated Standoff Bushing User manual

600 A 35 kV class PUSH-OP®
deadbreak connector
General
Eaton offers a complete threadless deadbreak,
clampstick operable connection system with
its Cooper Power™ series 600 A, 35 kV
class PUSH-OP®deadbreak connector for
terminating underground cables to transformers,
switches, switchgear, and other apparatus. It
is fully shielded, submersible, and meets the
requirements of IEEE Std 386™-2006 standard –
Separable Insulated Connector Systems.
The design employs a unique, 600 A rated, plated
copper probe and mating PUSH-OP bushing
utilizing a plated copper finger contact system.
The PUSH-OP connector's stainless steel latching,
linkage mechanism provides leverage for easy
disconnection of the terminator and easy handling
of heavy cable. The result is a one-person,
clampstick operable connection system that is
unequalled in ease of operation and time required
to perform sectionalizing operations.
A coppertop compression connector is provided
for terminating the conductor.
The 200 A three-phase rated loadbreak interface
provides a means for obtaining a live test, visible
ground and visible break using a clampstick. It also
provides a convenient location for Eaton's Cooper
Power series M.O.V.E. arrester or grounding
elbow. The grounding elbow may be continuously
connected to the PUSH-OP connector while
moving it to and from an apparatus bushing.
Eaton offers an optional capacitive test point similar
to test points on 200 A elbow connectors. This allows
use of Eaton's Cooper Power series test point faulted
circuit indicators.
The PUSH-OP connector also has a non-bolted
connection that eliminates threading and its
associated problems.
PUSH-OP connectors are designed for use on solid
dielectric cable (XLPE or EPR) with extruded semi-
conducting shields and concentric neutral, with or
without jacket. Installation on jacketed concentric
neutral cable may require additional sealing
material. Cold shrinkable adapters are available for
tape shield, linear corrugated and drain wire cable
adaption for use with deadbreak connectors.
Installation
The T-body housing with stainless steel shroud is
assembled onto prepared cable with a threaded
coppertop spade lug compression connector. The
loadbreak reducing tap plug is threaded into the
connector and onto a probe using an alignment
tool, installation torque tool, and T-wrench.
The assembled housing is then connected to
a de-energized 600 A PUSH-OP type bushing
interface and bracket using a clampstick without
any threading operation. (See Table 5 for
information on tools.) Refer to Service Information
S600-53-3 600 A 35 kV Class PUSH-OP Deadbreak
Connector Installation Instructions for details.
Deadbreak Connectors
Catalog Data
CA650052EN Effective October 2015
Supersedes May 2015
COOPER POWER
SERIES
DRAIN WIRE TAB
Drain wire tab provides a convenient point
to connect drain wire to ensure grounding
of the connector shield.
600 A PUSH-OP
BUSHING
LOCATING PINS
CABLE ADAPTER
Molded cable adapter, sized
to fit cable insulation diameters
from 0.875 inch to 2.210 inches
(22.2 to 56.1 mm), provides stress
relief for the terminated cable.
Figure 1. PUSH-OP connector cutaway illustrates design integrity.
ote:N Dimensions given are for reference only.
EPDM INSULATION
High-quality peroxide-cured
EPDM Insulation is mixed
and formulated in-house for
complete control of raw
rubber characteristics.
SHROUD
Stainless steel (Series
300) shroud provides a
hotstick eye and the
locating pins for
connection to a PUSH-OP
type bushing tap.
LOADBREAK REDUCING TAP PLUG is
200 A, single-phase loadbreak and three-
phase. Fault close rated.
CAPACITIVE TEST POINT
Capacitive test point (Optional)
allows use of Cooper Type
S.T.A.R. (TPR) Series Fault
Indicators.
CLAMPSTICK
EYE
COMPRESSION
CONNECTOR 15/16 inch 9NS 2B
threaded coppertop compression
connector is sized to ensure a
cool running connector with maxi-
mum current transfer.
COPPER PROBE ASSEMBLY
Field replaceable tin-plated
copper probe and STUD-T
assembly ensures reliable
electrical connection.
Installation of connector
assembly to PUSH-OP
bushing requires no threading.
SEMI-CONDUCTING INSERT
Molded semi-conducting insert
provides corona-free electrostatic
shielding of the compression connector.
SEMI-CONDUCTING SHIELD
Precision molded peroxide-cured semi-
conducting shield provides ground
shield continuity and meets the
requirements of IEEE Std 592™
standard.
T-BODY
Molded T-body adapts to all
cable sizes and provides a
deadfront shielded connection.
Figure 2. PUSH-OP connector stacking dimensions.
ote:N Dimensions given are for reference only.
A
D
S3S2
C
S5
B
35 kV
A 18.1" (460 mm)
B 0.25" (6 mm)
C 0.25" (7 mm)
D 12.1" (307 mm)
S2 0.50" (13 mm)
S3 12.5" (317 mm)
S5 2.9" (72.14 mm)
Production tests
Tests conducted in accordance with IEEE Std 386™-2006 standard:
• ac 60 Hz 1 Minute Withstand
• 50 kV
• Minimum Partial Discharge Extinction Voltage
• 26 kV
Tests conducted in accordance with Eaton requirements:
• Physical Inspection
• Periodic Dissection
• Periodic Fluoroscopic Analysis
Table 1. Voltage Ratings and Characteristics
Description kV
Standard Voltage Class 35
Maximum Rating Phase-to-Phase (Bushing Insert Only) 36.6
Maximum Rating Phase-to-Ground 21.1
AC 60 Hz 1 Minute Withstand 50
DC 15 Minute Withstand 103
BIL and Full Wave Crest 150
Minimum Partial Discharge Extinction Voltage 26
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
2
Catalog Data CA650052EN
Effective October 2015
600 A 35 kV class PUSH-OP deadbreak connector
www.eaton.com/cooperpowerseries
Optional features
Insulated protective cap
200 A insulated protective cap fits over loadbreak reducing tap plug
for deadfront shielding.
Capacitive test point
Capacitive test point, on molded T-body, with snap-on cap, provides a
place to mount STVT, STLO and STHI test point faulted circuit indica-
tors.
To order replacement compression connectors and cable adapters
for a PUSH-OP connector, see Catalog CA650006EN, “Deadbreak
Accessories, Tools and Replacement Parts”.
Ordering information
Each PUSH-OP Connector kit contains:
• Molded Rubber T-body with stainless steel shroud
• Loadbreak Reducing Tap Plug
• Cable Adapter
• Probe
• Compression Connector
• Silicone Lubricant
• Installation Instruction Sheet
• Copper Alloy Stud
Catalog number selection
Use the following procedure to develop the correct part number for
the desired PUSH-OP kit, based on cable size, conductor size and
desired options.
Step 1 – Determine the cable’s diameter over the electrical
insulation as shown in Figure 3 (including tolerances). Then identify a
cable range from Table 3 that brackets the minimum and maximum
insulation diameters. Select the correct CABLE RANGE CODE.
Step 2 – Identify the conductor size and type in Table 4 and select
the CONDUCTOR CODE from the far right column.
Step 3 – For a PUSH-OP kit with a capacitive test point and
protective cap, order:
For a PUSH-OP kit without a capacitive test point or protective cap,
order:
EXAMPLE: To select a PUSH-OP kit without a capacitive test point,
with a protective cap for a 250 kcmil compressed cable with a
nominal insulation diameter of 1.16".
Step 1 – Nominal diameter over the insulation is 1.16" ± .030"
minimum diameter = 1.16 - .030 = 1.13"
maximum diameter = 1.16 + .030 = 1.19"
From Table 3 identify the cable range 1.13" - 1.19" and select the “H”
Cable Range Code.
Step 2 – The conductor size is a 250 kcmil compressed. From Table
4, under the column “Concentric or Compressed”, identify 250 kcmil
and select the “17” conductor code.
Step 3 – Order catalog number:
POP635H17C
Current ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
* If available system fault current exceeds 10 kA, current limiting fusing must be used upstream.
Otherwise fault close and short time ratings of the 200 A interface will be exceeded.
** Switching rated limited to Single-phase 21.1 kV.
Table 2. Current Ratings and Characteristics
Description Amperes
600 A Interface
Continuous 600 A rms
24 Hour Overload 1,000 A rms
Short Time 40,000 A rms symmetrical for 0.17 s
27,000 A rms symmetrical for 4.0 s
200 A Interface*
Continuous 200 A rms
Switching** 10 operations at 200 A rms at 21.1 kV
Fault Closure 10,000 A rms symmetrical at 36.6 kV for 0.17 s after 10
switching operations
Short Time 10,000 A rms symmetrical for 0.17 s
3,500 A rms symmetrical for 3.0 s
Figure 3. Illustration showing typical construction of medium voltage underground
cable.
OUTER JACKET
CONDUCTOR
INSULATION CONDUCTOR
SHIELD
METAL NEUTRAL
OR SHIELD
INSULATION
SHIELD DIAMETER OVER
INSULATION
POP635 TC
CABLE RANGE
CODE
CONDUCTOR
CODE
POP635 CABLE RANGE
CODE
CONDUCTOR
CODE
Table 3. Cable Diameter Range
Inches mm
Cable
Range
Code Inches mm
Cable
Range
Code
0.875-0.985 22.2-25.0 D1.355-1.520 34.4-38.6 M
0.930-1.040 23.6-26.4 E1.485-1.595 37.7-40.5 N
0.980-1.115 24.9-28.3 F1.530-1.640 38.9-41.7 P
1.040-1.175 26.4-29.8 G1.575-1.685 40.0-42.8 Q
1.095-1.240 27.8-31.5 H1.665-1.785 42.3-45.3 R
1.160-1.305 29.5-33.1 J1.755-1.875 44.6-47.9 S
1.220-1.375 31.0-34.9 K1.845-1.965 46.9-50.0 T
1.285-1.395 32.5-35.4 L1.960-2.210 49.8-56.1 U
3
Catalog Data CA650052EN
Effective October 2015
600 A 35 kV class PUSH-OP deadbreak connector
www.eaton.com/cooperpowerseries
Table 5. Replacement Parts and Tools
Description Catalog Number
T-body without Test Point with shroud PDT635
T-body with Test Point with shroud PDT635T
Loadbreak Reducing Tap Plug (includes Built-In Alignment Tool) LRTP635
Probe and STUD-T Assembly 2638894B01B
200 A, 35 kV Class Insulated Protective Cap LPC235
Installation Torque Wrench TQHD635
5/16 inch T-Wrench TWRENCH
See Catalog CA650006EN for replacement compression connectors, cable adapters and additional
information on tools.
Figure 4. Catalog Number TWRENCH
The T-Wrench is used to install the loadbreak reducing tap plug
into the compression connector and T-body.
Figure 5. Catalog Number TQHD635
The Torque Tool is required to assemble a 35 kV Class PUSH-OP
deadbreak connector. It is precision calibrated and hotstick
operable.
Table 4. Conductor Size and Type
Concentric or Compressed Compact or Solid CONDUCTOR
CODEAWG or kcmil mm2AWG or kcmil mm2
No Connector 00
3–2–10
2 – 1 _ 11
1 – 1/0 – 12
1/0 50 2/0 70 13
2/0 70 3/0 – 14
3/0 – 4/0 95 15
4/0 95 250 120 16
250 120 300 – 17
300 150 350 – 18
350 – 400 185 19
400 185 450 – 20
450 – 500a240 21
500 240 600 300 22
600 300 700 – 23
650b– 750c–24
750d400 900 – 25
900 – 1000 500 26
1000 500 – – 27
1250 630 – – 28
a. Also accepts 550 kcmil compact conductor.
b. Also accepts 700 kcmil compressed conductor.
c. Also accepts 800 kcmil compact conductor.
d. Also accepts 700 kcmil concentric conductor.
600 A 35 kV class PUSH-OP deadbreak connectorCatalog Data CA650052EN
Effective October 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. CA650052EN
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series product
information call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.

Other manuals for 600 A 35 kV Class Insulated Standoff Bushing

4

This manual suits for next models

1

Other Eaton Cables And Connectors manuals

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton Crouse-Hinds GRUE Series Setup guide

Eaton

Eaton Crouse-Hinds GRUE Series Setup guide

Eaton 600 A 15 kV class T-OP II Programming manual

Eaton

Eaton 600 A 15 kV class T-OP II Programming manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton 600 A 35 kV Class Insulated Standoff Bushing User manual

Eaton

Eaton 600 A 35 kV Class Insulated Standoff Bushing User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton 200 A 15 kV class User manual

Eaton

Eaton 200 A 15 kV class User manual

Eaton Crouse-Hinds Ark-Gard ENR Series Setup guide

Eaton

Eaton Crouse-Hinds Ark-Gard ENR Series Setup guide

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton RMQ-Titan C22-PV Series User manual

Eaton

Eaton RMQ-Titan C22-PV Series User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton EU4A-RJ45-CAB2 Manual

Eaton

Eaton EU4A-RJ45-CAB2 Manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton Moeller SmartWire-Darwin Series User manual

Eaton

Eaton Moeller SmartWire-Darwin Series User manual

Eaton Network Adapter FCC 15 User manual

Eaton

Eaton Network Adapter FCC 15 User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton DX-CBL-PC-1M5 Manual

Eaton

Eaton DX-CBL-PC-1M5 Manual

Eaton 200 A 25 kV class User manual

Eaton

Eaton 200 A 25 kV class User manual

Eaton Crouse-Hinds ARKTITE CPP Series Setup guide

Eaton

Eaton Crouse-Hinds ARKTITE CPP Series Setup guide

Eaton EZ II Series User manual

Eaton

Eaton EZ II Series User manual

Popular Cables And Connectors manuals by other brands

Monoprice HD-140E3-3D-V2 manual

Monoprice

Monoprice HD-140E3-3D-V2 manual

PCB Piezotronics IMI SENSORS 009M205/100 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS 009M205/100 Installation and operating manual

Bayco 800 Series instruction manual

Bayco

Bayco 800 Series instruction manual

NEUTRIK opticalCON QUAD Handling instructions

NEUTRIK

NEUTRIK opticalCON QUAD Handling instructions

Balluff BKS-S32M-00 Assembling Instruction

Balluff

Balluff BKS-S32M-00 Assembling Instruction

Lenze L-force EYF 0021 A F03 Series Mounting instructions

Lenze

Lenze L-force EYF 0021 A F03 Series Mounting instructions

REMA DIN 80 technical information

REMA

REMA DIN 80 technical information

ADC Standard FTP Switchboard Cable Specification sheet

ADC

ADC Standard FTP Switchboard Cable Specification sheet

Philips SWV2693W Specifications

Philips

Philips SWV2693W Specifications

CommScope SYSTIMAX VisiPatch CPC5562 instruction sheet

CommScope

CommScope SYSTIMAX VisiPatch CPC5562 instruction sheet

CYP CLUX-12E Operation manual

CYP

CYP CLUX-12E Operation manual

Chicago Electric 93633 operating instructions

Chicago Electric

Chicago Electric 93633 operating instructions

Telegärtner RJ45 Stecker Assembly instruction

Telegärtner

Telegärtner RJ45 Stecker Assembly instruction

HCS J6E-00863 installation manual

HCS

HCS J6E-00863 installation manual

Philips SWA2523T Specifications

Philips

Philips SWA2523T Specifications

Bals INNOLINQ QUICK-CONNECT installation manual

Bals

Bals INNOLINQ QUICK-CONNECT installation manual

Dorma PT 60 Installation instruction

Dorma

Dorma PT 60 Installation instruction

Connect Tech COM Express CCG022 user guide

Connect Tech

Connect Tech COM Express CCG022 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.