Specification are subject to change without notice. Copyright 2007 Eaton Power Quality Pty Ltd
Technical Specification –SPDV60-300 Tvss Doc# 510083
Page 1 of 2
Web: http://www.powerware.com.au Phone: 1300 UPS UPS
SPDV60-300 SURGE DIVERTER
(Single mode, 220-250V (380-440V), 60/30kA)
INSTALLATION INSTRUCTIONS
FEATURES
• 1 mode plug-in protection (L-N)
• Compact solution for primary protection
• DIN43880 base, 35 mm DIN-rail mountable
• MOV is thermally protected
• Includes dry-contact alarm
Applications
• Mains point-of-entry /Main SWB
• Telecommunication Systems / Rectifiers
• Process and Control Systems / Factories & Units
• Computer Systems / Medical Systems
• All sensitive Electronic Equipment
FUNCTIONAL DESCRIPTION
The SPDV60-300 is designed to protect single and 3-
phase power systems against damage from surges
and spikes caused by lightning and other electrical
sources. The unit is intended for point-of-entry or
sub-board protection and is connected in parallel with
the power system via HRC fuses. The unit features a
plug-in module that may be replaced without rewiring
in the event of a fault. Check that the model you have
purchased is rated correctly for your power system.
.
This model (SPDV60-300) is designed for single
and 3-phase power systems, with a grounded
neutral, in the range of 220-250V(380-440V). If
your power system is “delta” (i.e. ungrounded),
or a different voltage, this model is NOT suitable.
Please contact your supplier for a suitable model to
suit your application.
OPERATION
The operational status of the unit is shown by a flag
indicator on the front of the module. In normal
operation, the flag is green. If the unit becaomes
damaged, the flag changes to red, indicating that
replacement is necessary. A ‘dry-contact’ alarm
output is fitted to the base unit and will change over if
the module is faulty or not in place.
WARRANTY
Eaton Power Quality warrants this unit against faulty
parts and workmanship for a period of 12 months
from the date of purchase. If this product fails to
operate correctly, please contact your Eaton
representative. This warranty doesn’t cover neglect
or intentional misuse. As this product is intended for
use in electrically harsh environments no claim is
made of suitability for purpose. This unit is designed
to reduce the likelihood of damage, not prevent it.
Please also note that an excessive surge, such as
from a direct lightning strike to the site or a power
system fault, may cause damage to the unit and
render it inoperable. A unit that has been damaged in
this way is not warrantable.
For installation details,
see over page.
SPECIFICATIONS
Manufacturers name and model Eaton Powerware
SPDV60-300
Method of mounting Fixed. DIN Rail mount
Input voltage 220-250VAC (380-440V)
40-70Hz
Maximum continuous operating
voltage - MCOV 300VAC
Service type TN-C and TN C-S (3-phase
with grounded neutral)
Test classification Class II
Supply current <10mA
Initial clamp voltage 470V
Maximum rated surge current -
Ismax 8/20us 60kA
Nominal surge current - In
8/20us 30kA
Residual voltage (Vpl) @
3kA, 8/20uS 1.0kV
Residual voltage (Vpl) @ Ismax
30kA, 8/20uS 1.4kV
Energy absorbtion (2ms) 2130j
Nominal surge lifetime (In) 30kA (8/20uS), 20 times
Internal protection MOV thermal disconnect
device
External disconnector
requirements Gg/Gl HRC fuses, 1 per
unit/phase, 160A maximum.
Terminations Power terminals 25mm2,
Alarm terminals 1.5mm2
Alarms/indicators Flag indicator, dry contact
alarm relay –
250VAC/24VDC, 2A
Location Category Indoor
Enclosure rating IP20
Applicable standards. IEC61643-1, IEC610006,
ANSI/IEEE C62.41,
AS1768-1991, AS3100
Dimensions DIN43880, 1 units (17mm)
Weight 100g
Environment -10 to 60C, 0-90%RH
Warranty 12 months, workmanship
and materials