For more information visit: www.Eaton.com Page 4 Page 1 For more information visit: www.Eaton.com
SP2 Surge Protective Device
Installation & Operation
Instruction Manual
IB158003EN
Rev. 2
.0 Introduction
This manual escribes how to install a Surge
Protective Device (SPD) in parallel (shunt) across the
AC supply of the following types of electrical
systems:
• Single-Phase
• Split Phase
• Three-Phase Wye
• Three-Phase Delta
The SPD is esigne to be installe on service
entrance, branch panels, an /or in ivi ual
equipment isconnects, an functions to protect
sensitive electronic equipment from amaging
voltage transients. The connecting wires o not
carry supply current. Instea , they carry only
short- uration currents that are associate with a
transient event.
These instructions o not cover all etails,
variations, or combinations of the equipment, its
storage, elivery, installation, checkout, safe
operation, or maintenance. If you require further
information regar ing a particular application or
installation that is not covere in this manual,
please contact Eaton’s Power Quality Technical Sup-
port at 1-800-809-2772, option 4, option 2.
. Safety Precautions
A license /qualifie electrician must complete all
instructions escribe in this manual in accor ance
with the U.S. National Electrical Co e, state an
local co es, or other applicable country co es. All
electrical co es superse e these instructions.
Improper installation can cause eath, injury
an /or equipment amage. Follow all warnings
an cautions. Completely rea an un erstan the
information in this instruction manual before
attempting to install or operate this equipment.
Improper wiring coul cause eath, injury, an /or
equipment amage. Only license /qualifie
electricians who are traine in the installation an
service of electrical evices are to install an service
this equipment.
Use appropriate safety precautions an
equipment for arc flash protection.
During normal operation, hazar ous voltages are
present insi e the SPD.
When servicing the SPD, follow all safe work
practices to avoi electrical shock.
Do not perform a high-pot test with the SPD
connecte to the electrical system. Failure to
isconnect the SPD uring a high-pot test will result
in amage to the SPD.
Do not install with lea length less than six (6)
inches.
.2 Catalog Numbering System
Series Voltage Co e
SP2- 120 = 120V single-phase
240 = 240V single-phase
240S = 240V split-phase
240D = 240 elta
480D = 480 elta
208Y = 120/208 wye
480Y = 277/480 wye
600Y = 347/600 wye
4.0 Specifications
5.0 Warranty
Eaton warrants these pro ucts for a perio of 2
years from the ate of elivery to the purchaser to
be free from efects in both workmanship an
materials. Eaton assumes no risk or liability for
results of the use of the pro ucts purchase from it,
inclu ing but without limiting the generality of the
foregoing: (1) The use in combination with any
electrical or electronic components, circuits,
systems, assemblies, or any other materials or
substances; (2) Unsuitability of any pro uct for use
in any circuit or assembly. Purchaser’s rights un er
the warranty shall consist solely of requiring Eaton
to repair, or at Eaton’s sole iscretion, replace, free
of charge, F.O.B. factory, an efective items
receive at sai factory within sai term etermine
by Eaton to be efective. The giving of or failure to
give any a vice or recommen ations by Eaton shall
not constitute any warranty by or impose any
liability upon Eaton.
The foregoing constitutes the sole an exclusive
liability of Eaton AND IS IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESSED, IMPLIED OR
STATUTORY AS TO THE MERCHANTABILITY,
FITNESS FOR PURPOSE SOLD, DESCRIPTION,
QUALITY, PRODUCTIVENESS OR ANY OTHER
MATTER. In no event shall Eaton be liable for
special or consequential amages or for elay in
performance of the warranty. This warranty oes
not apply if the pro uct has been misuse , abuse ,
altere , tampere with, or use in applications other
than specifie on the nameplate. At the en of the
warranty perio , Eaton shall be un er no further
warranty obligation expresse or implie . The
pro uct covere by this warranty certificate can
only be repaire or replace by the factory. For help
on troubleshooting the SPD, or for warranty
information, call 1-800- 809-2772, Option 4,
sub-option 2. Repair or replacement units will be
returne collect. If Eaton fin s the return to be a
manufacturer’s efect, the pro uct will be returne
prepai .
Eaton
1000 Cherrington Parkway
Moon Township, PA 15108-44312, USA
www.eaton.com/sp
For Technical Support, please call 1-800-809-2772
© Eaton Corporation
All Right Reserve
Description Ratings
Surge current capacity per phase (Imax) 45kA
Nominal Discharge Current (In) 10kA
Short circuit current rating (SCCR) 200kA
SPD type Type 1 (can also be use in Type 2 applications)
System voltages available (VAC)
Single-Phase 120/240
Split-phase 240
Three-phase wye 208, 480, 600
Three-phase elta 240, 480
Protection modes
Single-phase L-N
Split-phase L-N
Three-phase wye L-G, L-L
Three-phase elta L-G, L-L
Maximum continuous operating voltage (MCOV)
SP2-120 150V
SP2-240 320V
SP2-240S 150V
SP2-208Y 150V
SP2-480Y 320V
SP2-600Y 420V
SP2-240D 320V
SP2-480D 550V
Input power frequency 50/60Hz
Enclosure rating NEMA 4X
Operating temperature -40°C through 65°C (-40°F through 149°F)
Operating humi ity 5% through 95%, noncon ensing
Operating altitu e Up to 12,000 ft (3658m)
Agency certification an approvals UL1449 3r E ition Type 1 Liste evice
Warranty 2 years