Type PST Model-9 Automatic Source Transfer Switchgear with iST Control
Product information
Introduction
Service Information MN285002EN provides installation
instructions, operation information, maintenance
procedures, and testing information for Eaton's Cooper
Power™ series Type PST Model-9 Underground Distribution
Automatic Source Transfer Switchgear with iST Control.
Before installing and operating this control, carefully read
and understand the contents of this manual.
For additional information, refer to the following applicable
service information bulletins:
S275-10-1 Type CI Three-Phase Fault Interrupters
Installation and Operation Instructions
MN285006EN Type VFI, Fluid Insulated, Vacuum Fault
Interrupter; Installation, Operation, and Maintenance
Instructions
Read this manual first
Read and understand the contents of this manual and follow
all locally approved procedures and safety practices before
installing or operating this equipment.
Additional information
These instructions cannot cover all details or variations
in the equipment, procedures, or process described, nor
provide directions for meeting every possible contingency
during installation, operation, or maintenance. For additional
information, please contact your Eaton representative.
Acceptance and initial inspection
The PST switchgear is completely assembled, tested, and
inspected at the factory. The switchgear is filled to the
correct level with insulating fluid. It is in good condition
when accepted by the freight carrier for shipment.
1. Upon receipt, inspect the unit thoroughly for damage
and loss of parts or fluid incurred during shipment.
If damage or loss is discovered, file a claim with the
carrier immediately.
2. Check for fluid leakage.
Handling and storage
The switchgear should remain on its shipping pallet until it is
installed. When handling the switchgear, always use a fork
truck that has adequate lifting capacity and forks that extend
the entire length of the pallet. Improper handling can cause
damage to the switchgear.
If the switchgear is to be stored for any appreciable time
before installation, provide a clean, dry storage area.
Be careful during handling and storage to minimize the
possibility of mechanical damage. Do not stack other
material on the switchgear.
Standards
PST Model-9 Underground Distribution Switchgear products
are designed and tested in accordance with standards: IEEE
Std C57.12.28™-2005 and IEEE Std 386™-2006.
Quality standards
ISO 9001 Certified Quality Management System.
PST Model-9 overall description
Type PST Model-9 Automatic Source Transfer Switchgear
provides both loss-of-source health and overcurrent
protection for critical loads for 15, 25, and 35 kV
underground systems.
PST Model-9 units are self-contained, steel constructed
underground distribution enclosures containing mineral oil
or Envirotemp™ 200™ as a dielectric insulating medium.
They are shipped fully assembled and filled with insulating
fluid. PST Model-9 switchgear is designed for outdoor
mounting on a concrete pad. Power is fed to, and from, the
switchgear from underground through openings in the pad.
Deadfront construction minimizes the high voltage safety
hazards for both the operator and the general public.
Loss-of-source health protection functionality is provided
by an iST control system and two three-phase Type CI
motor-operated, source-side vacuum interrupter switches
(Figure 1).
Eaton's Cooper Power series iST control monitors the
preferred and alternate line voltages and provides the timing
and control logic required to perform the automatic load
transfer in the event of a source health loss. The control
commands the operations of the two Type CI vacuum
interrupter switches during auto transfer. Manually operated
levers enable manual trip and close of source-side CI
interrupter switches during power outages. Operational
power (120 Vac) for the transfer control and vacuum
switches is derived from system line levels via internally
mounted potential transformers; no external source of
power is required.
Eaton's Cooper Power series VFI Interrupters and iST control
provide independent overcurrent protection of the two
PST taps. Both taps are independently served by separate
controls commanding the operations of a dedicated VFI
vacuum fault interrupter on each tap (Figure 1).
1
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN285002EN April 2019