Eaton Powerware BladeUPS Quick guide

Racks and Power Distribution
Racks and Power Distribution
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
12kW ZC1224010100000 1 Powerware BladeUPS 6U
12 kW 400V w/60A 5W
in/ RPM ONLY w/WEB/
SNMP/4.8 min battery
For additional
battery 103005747-6591 1 Battery increase to 12 minutes 3U
runtime 2 Battery increase to 20 minutes 6U
3 Battery increase to 27 minutes 9U
4 Battery increase to 34 minutes12U
* Each UPS requires same number of external batteries
TWO (2) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
PW107BA0UC08 2 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 1 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052737 1 42U Enclosure (Rack) Split Rear & -
Casters & Sides
1052754 1 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 75U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
ONE (1) RACK @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, (2 x L21-30R),
(6 x C19), BladeUPS Plug, 10 ft
PW107BA0UC08 2 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052737 1 42U Enclosure (Rack) Split Rear & -
Casters & Sides
Total U space remaining for IT equipment 33U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Racks and Power Distribution
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
12kW N+1 ZC122P060100000 2 Powerware BladeUPS 12U
12 kW 400V w/parallel cord,
13 min battery @ 12 kW
103005913 1 Powerware 42U enclosure 6U
with BladeBar and
Bottom WW
116750221-001 1 ConnectUPS-X WEB/SNMP -
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1 24U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591 2 Battery increase to 30 minutes 6U
battery runtime* 4 Battery increase to 44 minutes12U
6 Battery increase to 59 minutes18U
8 Battery increase to 76 minutes24U
* Each UPS requires same number of external batteries
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
24kW N+1 ZC122P060100000 3 Powerware BladeUPS 18U
12 kW 400V w/parallel
cord, 9 min battery @ 24 kW
103005913 1 Powerware 42U enclosure 6U
with BladeBar and
Bottom WW
116750221-001 1 ConnectUPS-X WEB/SNMP -
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1 18U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591 3 Battery increase to 21 minutes 9U
battery runtime* 6 Battery increase to 32 minutes18U
9 Battery increase to 43 minutes27U
12 Battery increase to 54 minutes 36U
* Each UPS requires same number of external batteries
TWO (2) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
PW107BA0UC08 2 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 2 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 1 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 81U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
ONE (1) RACK @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 2 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 1 42U Enclosure (Rack) Split Rear & -
Casters no Sides
Total U space remaining for IT equipment 39U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FOUR (4) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 1 Powerware Rack Power Module (RPM), 3U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 4 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 4 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 3 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 162U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
TWO (2) RACKS @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 4 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 2 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 1 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 78U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Powerware®BladeUPS™
Configuration Guide
Quick configurations for 12 kW single UPS solutions up to 60 kW N+1
redundant systems.
Step 1 Select UPS based on power configuration.
Step 2 Select desired rack and power configuration.
Step 3 Select appropriate startup and service support.
Note: Typical rack configurations. Other configurations available.

Racks and Power Distribution
Racks and Power Distribution
Racks and Power Distribution
Eaton, Powerware, and BladeUPS are trade names, trademarks, and/or
service marks of Eaton Corporation and its subsidiaries or affiliates.
© 2008 Eaton Corporation, All Rights Reserved.
1018037 Rev C
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
36kW N+1 ZC122P060100000 4 Powerware BladeUPS 24U
12 kW 400V w/parallel cord,
7.7 min battery @ 36 kW
103005913 1 Powerware 42U enclosure 6U
with BladeBar and
Bottom WW
116750221-001 1 ConnectUPS-X WEB/SNMP -
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1 12U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591 4 Battery increase to 18 minutes 12U
battery runtime* 8 Battery increase to 28 minutes24U
12 Battery increase to 37 minutes 36U
16 Battery increase to 47 minutes 48U
* Each UPS requires same number of external batteries
SIX (6) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 2 Powerware Rack Power Module 0U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 6 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 6 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 5 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 243U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
THREE (3) RACKS @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 2 Powerware Rack Power Module 6U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032420CD100000 1 Powerware Rack Power Module (RPM), 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 15 ft
PW107BA0UC08 6 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 3 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 2 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 117U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
48kW N+1 ZC122P060100000 5 Powerware BladeUPS 30U
12 kW 400V w/parallel cord,
6.9 min battery @ 48 kW
103005913 1 Powerware 42U enclosure 6U
with BladeBar and
Bottom WW
116750221-001 1 ConnectUPS-X WEB/SNMP -
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1 6U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591 5 Battery increase to 17 minutes 15U
battery runtime* 10 Battery increase to 26 minutes 30U
15 Battery increase to 34 minutes 45U
20 Battery increase to 44 minutes 60U
* Each UPS requires same number of external batteries
UPS PRODUCTS AND ACCESSORIES
Power Rack Space
Configuration Parts Qty Description Required
60kW N+1 ZC122P060100000 6 Powerware BladeUPS 36U
12 kW 400V w/parallel cord,
6.9 min battery @ 48 kW
103005913 1 Powerware 42U enclosure 6U
with BladeBar and
Bottom WW
116750221-001 1 ConnectUPS-X WEB/SNMP -
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1 0U
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591 6 Battery increase to 15 minutes 18U
battery runtime* 12 Battery increase to 22 minutes 36U
18 Battery increase to 29 minutes 54U
24 Battery increase to 37 minutes 72U
* Each UPS requires same number of external batteries
EIGHT (8) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 3 Powerware Rack Power Module (RPM), 9U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 8 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 8 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 7 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 324U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FOUR (4) RACKS @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out BladeUPS Plug, 10 ft
Y032440CD100000 3 Powerware Rack Power Module 9U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 8 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 4 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 3 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 156U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FIVE (5) RACKS @ 12 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 2 Powerware Rack Power Module 6U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 3 Powerware Rack Power Module (RPM), 9U
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 10 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19)
1052736 5 42U Enclosure (Rack) Split Rear & -
Casters no Sides
1052754 4 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 195U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
**TEN (10) RACKS @ 6 KW PER RACK
Rack Space
Parts Qty Description Required
Y032420CD100000 1 Powerware Rack Power Module 3U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
Y032440CD100000 4 Powerware Rack Power Module 12U
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
PW107BA0UC08 10 Vertical (0U) ePDU 7 kW, 16A 230V 0U
(24 x C13) / (8 x C19) -
1052736 10 42U Enclosure (Rack) Split Rear &
Casters no Sides
1052754 9 Powerware Baying Kit, -
to attach two racks together
Total U space remaining for IT equipment 405U
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
** When supporting more than eight racks it is recommended to place UPS in center of configuration
to make power distribution wiring easier.
BELGIUM
Tel: +32 (0) 2 348 4410
CZECH
Tel: +420 272 760 365
DENMARK
Tel: +45 3686 7910
FINLAND
Tel: +358 9 452 661
FRANCE
Tel: +33 1 60 12 74 00
GERMANY
Tel: +49 7841 6040
ITALY
Tel: +39 02 95542 309
NORWAY
Tel: +47 23 03 65 50
POLAND
Tel: +48 22 331 85 24
RUSSIA
Tel: +7 495 981 37 70
SLOVAKIA
Tel: +421 2 4463 7046
SPAIN
Tel: +34 475 32 03
SWEDEN
Tel: +46 8 598 940 00
THE NETHERLANDS
Tel: 0800–8774636
UAE
Tel: +971 4 881 19 33
Fax: +971 4 881 1939
UNITED KINGDOM
Tel: +44 1753-608 700
acukpowerware@eaton.
com
Other manuals for Powerware BladeUPS
2
Other Eaton UPS manuals

Eaton
Eaton 5E User manual

Eaton
Eaton Powerware 9395 User manual

Eaton
Eaton 3S User manual

Eaton
Eaton Eaton series User manual

Eaton
Eaton 93PM IBC-L User manual

Eaton
Eaton EX RT 5 User manual

Eaton
Eaton EX RT 5 User manual

Eaton
Eaton 9E-IN 1K User manual

Eaton
Eaton 93PM IBC-LW User manual

Eaton
Eaton ON-LINE Series User manual

Eaton
Eaton 5E700UD-KR Assembly instructions

Eaton
Eaton Power Xpert 9395P-600/600 User manual

Eaton
Eaton 9 55 Series User manual

Eaton
Eaton MBP6Ki User manual

Eaton
Eaton 9315 User manual

Eaton
Eaton Ellipse ECO 500 User manual

Eaton
Eaton Powerware 9140 User manual

Eaton
Eaton 9SX 15K Series User manual

Eaton
Eaton Powerware 9395 User manual

Eaton
Eaton 9PX 1:1 Quick start guide