Lithium (LiFePo4)
Battery Owners Manual
Battery Packs Covered
12V96Ah 24V72Ah 36V72Ah 48V72Ah
12V144Ah 24V144Ah 36V105Ah 48V105Ah
12V216Ah 24V300Ah 48V160Ah
12V288Ah 48V320Ah
12V600Ah
WARNING!
•Always wear sa ety glasses when working with any type o battery
•Do not short circuit the battery terminals
•Do not connect the battery terminals with reverse polarity
•Do not charge more than 1C or 175A max (C=amp hours o the battery pack)
•Do not continuously discharge more than 1C or 175A max (C=amp hours o the battery pack)
•Do not momentarily discharge more than 600A or 3 seconds
•Do not momentarily discharge more than 300A or 30 seconds
•Do not open the battery pack or any reason, there is a risk o electric shock.
•Do not connect batteries in series to obtain a higher voltage pack.
•Do not connect more than 3 batteries in parallel
•Only parallel connect battery packs o identical voltage, capacity, and age
torage
Charge at least every six months
I storing unused or extended periods, disconnect loads and store at 50% state o charge
I storing unused or extended periods, store at room temperature
Installation
Make sure the battery pack voltage is correct or the application.
Do not connect with reverse polarity.
Always secure battery pack in place with mounting strap or battery hold down kit
Use only M8 or 5/16 ring terminals
Torque terminal bolts to 150-155 in/ t - Do not over tighten
I an inverter or DC-DC voltage converter will be used, connect battery terminals prior to
connecting an inverter or converter. Terminal arc damage is not covered under warranty.