
CT SET-UP
To enter programming mode press and
simultaneously for 5 seconds. The CT primary value may then
be set from the following nominal values (Secondary must by
set for special Voltage Output CTs):
5, 10, 15, 20, 30, 40, 50, 60, 80, 100, 150, 200, 250, 300, 400,
500, 600, 800, 1000, 1200, 1250, 1500, 1600, 2000, 2400, 3000,
2500, 4000, 4500, 5000, 5500, 6000, 6500, 7000, 7500, 8000,
8500, 9000, 9500, 10000, 10500, 11000, 11500, 12000, 12500,
13000, 13500, 14000, 14500, 15000, 15500, 16000, 16500,
17000, 17500, 18000, 18500, 19000, 19500, 2000, 205000,
21000, 21500, 22500, 23000, 23500, 24000, 24500, 25000
Press the p or q key until the desired current is displayed. If
the desired CT value is not present in the above list, the ratio
may be ‘fine adjusted’ as follows: Press and hold the t and p
buttons simultaneously for 2 seconds to enter ‘Fine Adjust
Mode’. This is indicated by a decimal point displayed
immediately to the right of the defined parameter viz: “Ct.” this
enables the CT primary value to be changed in 10A steps until
the desired ratio is displayed. Press the t key to store the
value and advance the page.
VT SET-UP
The default voltage setting is 400V and this value should not be
altered.
PULSE SET-UP
The pulse rate value (PLr) may be set between 0.1 and 100
pulses per unit. Press the p or q key until the desired pulse is
displayed. Note that the unit of energy (Wh/kWh/MWh) will
automatically change to reflect the primary values of CT & VT
previously set. The pulse value is set for both outputs during
the process. Press the t key to store the value and advance
the page.
The pulse duration value (PLt) may be set in increments
between 100mS & 20 seconds as required.
The Pulse Output Test (Pto) allows the meter pulse output and
connected data collection hardware to be tested, regardless of
whether an actual load is present. Press the p button to start
the test. The display will show “Ptr” and both outputs will pulse
simultaneously. This is verified by the front panel l.e.d.s. Press
the p and q together to stop the test and reset the test
counter.
HOURS RUN SET-UP
The hours run preset level may be set between 1% and 100% of
the full scale current. Press the p or q key until the desired
value is displayed. Press the t key to store the value and
advance the page.
RS485 SET-UP
This allows the baud rate and MODBUS address to be set. Use the
p and q buttons to set the desired baud rate. Press the t key to
store the value and advance the page.
Use the p and q buttons to set the unit address. Press the t key
to store the value and save and exit from the set-up menu. The
display will show ‘storing’ to confirm this action.
Connection: 3 Phase 3 or 4 wire Unbalanced, 3 Phase Balanced,
Single Phase Load.
Inputs: Voltage: 400/230V 3 Phase 3/4 wire
Current: 0.33Vac – External CTs. Fully isolated.
Pulse Output: Opto isolated volt free contact
Rating: 100mA ac/dc, 100V ac/dc max
Value: 1 pulse per kWh
1 pulse per 10 kWh
1 pulse per 100 kWh
1 pulse per 1000 kWh
Duration: 100ms
Isolation: 2.5kV for 1 minute
Power Supply: 230V 50/60Hz +/- 15%
Overload: Voltage x 4 for 1 hour
Current x 40 for 0.5 seconds max
Consumption: 2VA
Weight: 325g
IP Rating: Instrument = IP20 Front panel = IP40
Temp Range: -10o - +65o
Dims: 106w x 58d x 90h mm (6 DIN)
Accuracy: kWh: Class 1 EN62053-21 7 BS8431 (2%-120%
Nominal Load)
Environment: Operate -10oC > T < 65oC. RH < 75% Non-
Condensing
Storage- 25oC > T < 75oC
IP54 (IP65 with optional kit)
NOTE: Do not expose the instrument display to direct
sunlight.
Unit 5 Southmill Trading Centre, Southmill Road, Bishop’s Stortford,
Herts. CM23 3DY.
01279 503173 sales@elcomponent.co.uk
www.elcomponent.co.uk
16.04.15 – Issue 5
5 TECHNICAL CHARACTERISTICS