Elcomponent AEM35 User manual

AEM35 User Manual
Installation and user instructions
Three-phase energy analyser for indirect connection (5A or 0.333V) with Modbus or pulse interface
The analyser measures active and reactive energy,
summing or separating imported energy from
exported energy. It displays the main electrical
parameters, including THD, calculated neutral
current and running hours. Current measurements
by external current transformers and voltage
measurements either direct or by potential
transformers. Equipped with a pulse output and
optionally with RS485 Modbus port. It measures
four DIN modules, with removable LCD display unit
allowing the same unit to be used either DIN-rail or
panel mounted and to be used as a transducer
without the display.
Features
Power
Self-power supply from 40 to 480VAC (45-65Hz).
Consumption
≤2VA/1W
Nominal current (In)
Transformer primary current corresponding to 5A secondary
output (AEM35) or 0.333 V secondary output (AEM35V)
Maximum current (continuing)
1.2 In
Start-up current
0.01 A
Nominal voltage
230 V LN, 400 V LL ac
Voltage range
160 to 240 V LN ac, 277 to 415 V LL ac
Frequency
45-65Hz
Accuracy class
Active energy: Class 1 (EN62053-21)
Reactive energy: Class 2 (EN62053-23)
Environmental specifications
Working temperature
From –25 to +55 °C/from –13 to +131 °F
Storage temperature
From –30 to +70 °C/from –22 to +158 °F
Output Specifications
Pulse output
Programmable from 0.01 to 9.99 kWh per pulses
Pulse duration
TOFF ≥120ms, according to EN62052-31
TON selectable (30 ms or 100 ms) according to EN62053-31
Modbus RS485 port output
Modbus RTU protocol
NOTE: to set output parameters, see Parameters menu (Fig. 27).

AEM35 User Manual
LED specifications
Pulse weight
Proportionate to the result of CT/Primary current and VT ratios:
Weight (kWh/pulse)
CT * VT
(AEM35)
Primary current * VT
(AEM35V)
0.001
< 7
< 35.0
0.01
≥ 7.0 < 70
≥ 35.0 and <350.0
0.1
≥ 70 < 700
350.0 and <3500.0
1
≥ 700.0
≥ 3500.0
Max Frequency
16Hz
Colour
Red
General features
Terminals
2.4 x 3.5 mm, Min./Max. screws tightening torque: 0.4 Nm / 0.8 Nm
Protection degree
Front: IP40, terminals: IP20
Dimensions
See Fig. 28.
Cleaning
Use a slightly dampened cloth to clean the instrument display; do not use abrasives or solvents.
Service and warranty
In the event of malfunction, fault or for information on the warranty, contact ELCOMPONENT Ltd.
General warnings
DANGER! Live parts. Heart attack, burns and other injuries. Disconnect the power supply and load
before installing the analyser. The energy analyser should only be installed by qualified/authorised
personnel.
Intended use: measurement of electrical parameters, indoor use. Use it in installations with
overvoltage cat. III or lower.
These instructions are an integral part of the product. They should be consulted for all situations tied
to installation and use. They should be kept within easy reach of operators, in a clean place and in
good conditions.
Pay attention when removing the
instrument from the DIN rail in order to
avoid breakage of the support.
Excessive rotation of the instrument to
remove it, might break the support as
shown in the figure. We suggest extracting
downwards.

AEM35 User Manual
Product (Fig.1)
Area
Description
A
Green LED:
• steady: the instrument is power
supplied
• blinking: the instrument is power
supplied and is communicating by
serial port.
B
Current, voltage, output and
communication connection
terminals
C
Command keys
D
Red LED:
• blinking: pulses proportional to
energy being measured
(pulse weight: see Features).
E
LCD display (no backlight)
Note: In separate package, cap seals for terminals
Display (Fig.2)
Area
Description
A
Unit of measure area
B
Signal area:
In case of wrong phase sequence
Phase to phase voltage L1-2, L2-3, L3-1
System values

AEM35 User Manual
Procedure for adapting the mounting (Fig. 3)
It is possible to convert the type of instrument installation, from DIN to Panel (72x72) or vice versa,
thanks to the special removable front panel. The instrument without the front panel will have the
function of a transducer.
The table below advises the conversion process:
Step
Action
1
Unclip, using a screwdriver of appropriate size, the spring tabs (total of two) A pushing them
from the slots B.
2
Pull out the display unit
3
Insert the display unit into the side desired, according to the type of montage:
C- DIN rail
D- panel 72x72
Note: the package includes two mounting brackets for panel mounting of the instrument
ARON connection diagrams, AEM35 only.
Diagram
Description
SyS selection (Fig. 26)
Fig. 4
3-ph, 3-wire, unbalanced load, 2-CT connections. F=315 mA
3P
Fig. 5
3-ph, 3-wire, unbalanced load, 3-VT/PT and 2-CT connections
3P

AEM35 User Manual
Connection diagrams, all models.
Diagram
Description
SyS selection (Fig. 26)
Fig. 6
3-ph, 4-wire, unbalanced load, 3-CT connection. F=315 mA
3P.n
Fig. 7
3-ph, 4-wire, unbalanced load, 3-CT and 3-VT/PT connections
3P.n
Fig. 8
3-ph, 3-wire, unbalanced load, 3-CT connection. F=315 mA
3P
Fig. 9
3-ph, 3-wire, unbalanced load, 3-CT and 2-VT/PT connections
3P
Fig. 10
3-ph, 3 or 4-wire, balanced load, 1-CT connection. F=315 mA
3P.1
Fig. 11
3-ph, 3-wire, balanced load, 1-CT and 2-VT/PT connection
3P.1
Fig. 12
2-ph, 3-wire, 2-CT connection. F=315 mA
2P
Fig. 13
2-ph, 3-wire, 2-CT and 2-VT/PT connections
2P
Fig. 14
1-ph, 2-wire, 1-CT connection. F=315 mA
1P
Fig. 15
1-ph, 2-wire, 1-CT and 1-VT/PT connection
1P

AEM35 User Manual
Connection diagrams, all models.
Diagram
Description
Fig. 16
Opto-mosfet static output
Fig. 17
RS485 Modbus with Master
Note: additional instruments with RS485 are connected in parallel. The serial output
must only be terminated on the last network device connecting terminals B+ and T. For
connections longer than 1000 m or networks with more than 160 instruments, use a
signal repeater.
Fig. 18
REMEMBER: in case of use of Current Sensors with the secondary output of 0,333V use
AEM35V models only connected as shown in figure 18.
Fig. 19
REMEMBER: in case of use of Rogowski Current Sensors, use AEM35V models only
connected as shown in figure.

AEM35 User Manual
Menu map (Fig. 23)
Area
Function
A
Measurement menu. Measurements displayed by default when turned on. Pages are
characterised by the reference unit of measure.
B
Parameter menu. Parameter settings pages. Require login password.
C
Information menu. The pages display information and set parameters without having to
enter a password.

AEM35 User Manual
Commands (Fig. from 20 to 22)
Navigation
Parameter settings
Operation
Command
Operation
Command
View the next measurement page
Fig. 20
Enter parameter setting
Fig. 21
Open the information menu
Fig. 21
Change between increase mode
(C icon displayed) and decrease
mode (-C icon displayed)
Fig. 21
View the next information page
Fig. 21
Exit the information menu
Fig. 20
Increase value/view next option (C)
Fig. 20
Open the parameter menu
Fig. 22
Decrease value/view previous
option (-C)
Fig. 20
Exit the parameter menu (info
menu shown)
Fig. 22
(page End)
Confirm a value
Fig. 22
NOTE: after 120s of inactivity, the measurement
page will be displayed.
Note: hold the key for up to 2,5s
Setting a parameter (Fig. 24)
Procedure example:
How to set Ut rat.=11 (passing the value 13).
NOTE: the first displayed value is the current one.
Settings are applied when the value is confirmed.
The value is being edited if C or -C appears.
After 120s of inactivity on a value being set, the
title page is displayed (P int in the figure) and C/-
C disappears.
After further 120s, the measurement page is
displayed.

AEM35 User Manual
Measurement menu (Fig. 25)
The picture shows some available measure pages as example.
General measurement
Measure
Application (see also
parameter menu “APPLiC”)
Total kWh; kW sys
A
B
C
D
E
F
Total kvarh; kvar sys
Note*: in application F kvarh is calculated by both positive and negative
kvar integration
B
C
D
E
F*
PF sys; Hz
B
C
D
E
F
PF per phase, A, V LL, V LN, THD VLL, THD VLN, THD A, An, Working
hours.
Note: to see the THD measure the THD function must be enabled
C
D
E
F
Exported kWh (kWh-), working hours of exported kWh (h-)
E
Available variables only via RS485
V LN sys, V LL sys, VA sys, VA L1, VA L2, VA L3, var L1, var L2, var L3, W L1, W L2, W L3.
Wrong wiring detection function (supporting the voltages/currents connections to the metering
device).
Information menu (Fig. 26)
Available information pages for ALL MODELS
Page
Code
Description
Disp. values in the example (fig.26)
01
y. xxx r.XX
Year of production and firmware release
Y 2017 (Year); r.A0 (revision)
02
Led
kWh per pulse
kWh 0.001 (kWh per pulse); LED
03
SyS
Type of system and type of connection
SYS 3P.n (system, see also fig 6, 7);
4W (4 Wires connection)
05
Ut rAt.
Voltage transformer ratio
10
06
PuLSE
Pulse output: kWh per pulse
0.10
07
Add
Serial communication address
2
08
PArity
Parity
No
09
bAud
Baud rate
115 kbps
10
bStop
Bit stop
1
11
SN
Secondary Address
1234567
Available information pages AEM35 ONLY
Page
Code
Description
Disp. values in the example (fig.26)
04
Ct rAT.
Current transformer ratio
1.0
Available information pages for AEM35V ONLY
Page
Code
Description
Disp. values in the example (fig.26)
SEnSOR
Type of current sensor (Ct or RoG)
Ct
04
Ct Prin
Current sensor nominal primary current
90
Measurement faults
If the measured signal exceeds the admitted analyser limits, a specific message appears:
• EEE blinking: the measured value is out of limits
• EEE on: the measurement depends on a value that is out of limits
NOTE: active and reactive energy measurements are displayed but do not change.

AEM35 User Manual
Parameter menus (Fig. 27)
Available menus for ALL MODELS
Page
Description
Values
PASS
Enter current password
Current password.
CnGPASS
Change password
Three digits (000–999)
APPLiC.
Selects the pertinent application
A/ B/ C/ D/ E/ F
SYS
System type
3Pn: 3-phase unbalanced with neutral;
3P: 3-phase unbalanced without neutral;
3P1: 3-phase balanced with or without
neutral;
2P: 2-phase;
1P: single phase
Ut rAt.
Voltage transformer ratio (VT)
1.0–999
PuLSE
Selects the pulse weight
kWh per pulse, 0.01–9.99
ton
Pulse duration (ON time in msec)
30-100
P.tESt
Sets the simulated power value (kW), for
the pulse output test.
Note: with APPLiC C, E, E, F only.
1-999 kW. (The pulses frequency is
according to the “PuLSE” weight selection)
tESt
Activates the pulse output test when ON
(the function is active until you remain
within the menu).
Note: with APPLiC C, D, E, F only.
Add
Serial address
1–247
bAud
Baud rate (kbps)
9,6/ 19,2/ 38,4/ 57,6/ 115,2
PAritY
Parity
No or Even
bStoP
Stop bit
1-2
tHd
THD enabling
On: enabled / Off: disabled
EnE rES
Reset of all the meters
No: cancels reset / Yes: enable reset
End
It allows exiting the programming mode
-
Available menu for AV5, AV6 ONLY
Page
Description
Values
Ct rAt.
Current transformer ratio (CT)
NOTE*: The maximum VT by CT ratio: 1187
1.0–999*
Available menu for MV5, MV6 ONLY
Page
Description
Values
“roG” values
SEnSOr
Selects the used current sensor
Ct: current
transformer/roG:
Rogowski sensor
Ct Prin
Current sensor nominal primary current
NOTE*: the max value of the multiplication
of primary current x VT ratio is 220000
10–9990*
1,00k, 2,00k, 4,00k
Blocking access to the parameter menu
It is possible to block the access to programming by means of a specific trimmer
positioned on the rear of the removable display unit. Turn the trimmer clockwise up to
its run end with the help of a suitable screwdriver.

AEM35 User Manual

AEM35 User Manual
• EN 61010-1
• 2014/30/EU • EN 62053-21
• EN62052-11
Table of contents
Other Elcomponent Measuring Instrument manuals

Elcomponent
Elcomponent SPCPro2 User manual

Elcomponent
Elcomponent SPCMini User manual

Elcomponent
Elcomponent SPCMini User manual

Elcomponent
Elcomponent EnergyPro EP600i User manual

Elcomponent
Elcomponent AEM33 485 DIN User manual

Elcomponent
Elcomponent PQPro User manual

Elcomponent
Elcomponent AEM33 V 485 DIN User manual

Elcomponent
Elcomponent EnergyPro EP600 User manual

Elcomponent
Elcomponent AEM32 DIN User manual

Elcomponent
Elcomponent AEM32 User manual