activate and deactivate as described in Table 1. Note that microwave detection is indicated only after a
successful PIR detection. Wait 3-5 seconds between walk tests. Adjust microwave sensitivity by turning the
MW trimmer clockwise to increase sensitivity or counter-
clockwise to decrease sensitivity. Do not set microwave
sensitivity higher than required. This test should be performed
weekly.
Setting the LED indicators: To enable/disable the LED
indicators refer to Table 2 for the appropriate DIP-switch
setting. If the LEDs are disabled, the memory function is not
affected and the red LED still flashes after an alarm.
Remote LED disable: Using header JP1, it is possible to remotely disable and enable the LED indicators
using an external switch. To do so, set Switch 4 to OFF, open JP1 to disable the LEDs and short JP1 to
enable the LEDs.
Memory function: The Memory function indicates that an alarm occurred while the system was armed.
When using this feature, connect switched 12V to terminal 3 (0V = System Disarmed, 12V = System Armed).
To indicate an alarm, the red LED
flashes after disarming the system. To
reset the memory function, briefly arm
and then disarm the system. In Memory
mode, the LEDs are always disabled
while the system is armed.
Note: If terminal 3 (ARM) is not
connected, set switch 3 to ON.
Technical Specifications
Operating Voltage: 9 - 16VDC
Current Consumption: Standby 26mA@12V
Max. (Alarm) 43mA@16V
Coverage: 12m x 12m
Pulse Count: 1 or 2 Selectable
Pyroelectric Sensor: Dual Element
Microwave Antenna: Planar Patch
Microwave Frequency: 10.525, 10.687 or 10.590GHz
Alarm Output: N.C.
Switching Voltage: 30VDC not to exceed 10W
Switching Current: 0.3A not to exceed 10W
Alarm Duration: 2 seconds
Tamper Switch: N.C.
Contact Rating 30VDC, 50mA max.
Operating Temperature: -10°to 60°C
Temperature Compensation: Thermistor
Reverse Polarity Protection: Diode
Fire Protection: ABS Plastic Housing
LED Indicators: Selectable
Dimensions: 127 x 71 x 56mm
Switch ON OFF
1 60Hz Fluorescent Light
Noise Filter
50Hz Fluorescent Light
Noise Filter
2 1 Pulse 2 Pulse
3 Memory Disabled Memory Enabled
4 LEDs Enabled LEDs Disabled
Table 2: DIP-Switch Configuration
Figure 3: Lens Pattern
Note: The diagram shows the maximum coverage pattern
for the detector set at a vertical adjustment of 0°.
ZI0185B (6/04)
Electronics Line 3000 Ltd.: 2 Granit Street, Kiryat Arieh, POB 3253, Petah Tikvah 49130 Israel. Tel: (972-3) 918-1333, Fax: (972-3) 922-0831
USA: 5637 Arapahoe Avenue, Boulder, Colorado 80303. Tel: (800) 683-6835, Fax: (303) 938-8062
UK: Unit 7, Leviss Trading Estate, Station Road, Stechford, Birmingham B33 9AE. Tel: (44-121) 789-8111, Fax: (44-121) 789-8055
France: ZI-61, rue du Marché Rollay, 94500 Champigny-Sur-Marne. Tel: (33-1) 45.16.19.20, Fax: (33-1) 45.16.19.29
All data is subject to change without prior notice. In no event shall Electronics Line 3000 Ltd. (EL3K) be liable for an amount in excess of EL3K.’s
original selling price of this product, for any loss or damage whether direct, indirect, incidental, consequential or otherwise arising out of any failure
of the product. Hereby, Electronics Line 3000 Ltd. declares that this detector is in compliance with the essential requirements and other relevant
rovisions of Directive 1999/5/EC.
LED Indication
Yellow Microwave detection
Green PIR detection
Red Alarm detection
Flashing
Green/Yellow
Microwave Supervision
Failure (replace unit)
Table 1: LED indication