Elitech ECS-961neo User manual

ECS-961neo Temperature controller
2、User interface
3.Technical date sheet
4、Indicator light
5.Parameters
1、Description
ECS-961neo has user menu and administrator menu. User menu is used to adjust the temperature.The administrator menu will be only
acve with the correct password, it can help the user avoid to operang the controller mistake.
ECS-961neo has 1 sensor for the room and with 17A(max) relay to control the compressor; it has a very big display screen with the
compressor and defrost indicator light which help the user check the statues of the refrigeraon units easily.
Install size: 71mm×29mm controller size: 78.5mm×34.5mm×41mm
◆ Display range: -50
℃
~99
℃
(when the correcon =0)
◆ Resoluon: 0.1 or 1
℃
◆ Accuracy: (-40
℃
~50
℃
): ±1
℃
; (51
℃
~70
℃
): ±2
℃
; others: ±3
℃
◆ Measuring range: -50
℃
~99
℃
◆ Power: 220VAC±10%(50/60Hz); Consumpon: <3W
◆ Analogue inputs: 1 NTC sensor
◆ Output:
Refrigeraon: 17A/240VAC(No type),can directly drive single-phase 1.0HP(220VAC) load
Or 10A/240VAC(No type)
◆ Water proof of front face: IP65
◆ Working temperature: 0
℃
~55
℃
◆ Storage: -25
℃
~75
℃
◆ Relave humidity: 20%~85%(no frost)
Light
Symbol
state
Meaning
Set light set
Permanently on
Parameter seng
off
Status of temperature measuringand controlling
Compressor light
Permanently on
Compressor acve
off
Compressor turn off
Flashing
A delay
Defrost light
Permanently on
Defrost acve
off
Defrost turn off
Menu
Descripon
Range
Defaults
M.U
User menu
SEt
Temperature control set point
LSE
~
HSE
4.0
℃
℃
Administrator menu
PA1
Password
00
~
250
-
/
diF
Compressor relay acvaon differenal
0.1
℃~
30.0
℃
2.0
℃
HSE
Max value of the set point
SEt
~
99.0
90.0
℃
LSE
Min Value of the set point
-50.0
~
SEt
-50.0
℃
Ont
Ont: controller on me for fault probe;
OFt: controller offme for fault probe;
Ont=0, O= any: compressor off;
Ont≠0, OFt=0: compressor remains on;
Ont≠0, OFt≠0:compressor in duty cycle;
0~2500min
OFt 0~2501 min
dOF
Compressor relay acvaon delay
0
~
250
0
min
OdO
Delay in acvaon output aer the instruments is switch on
0
~
250
0
min
dit
Defrost cycle
1
~
250
6
hour
dCt
Selecon of count mode for the defrost interval :
0= compressor runningme
1=natural me
2=compressor closingme
0/1/2 1 /
dOH
Delay for start of first defrost aer request.
1~59
1
min
dEt
Defrost me; dEt=0 means that defrost is forbidden
0
~
250
30
min
dPO
Determines whether the instrument must enter defrost mode at start-up
n/y
n
/
LOC
Basic commands modificaon lock. y =yes; n =no.
n/y
n
/
PA1
Password seng
0
~
250
5
/
ndt
Decimal point display
n/y
y
/
CA1
Calibraon1. Value to be added to the value read by probe 1
-12.0
~
12.0
0
℃
ddL
Display mode duringdefrost:
0=display real temperature of room;
1=display the temperature when start to defrost ,defrost closingand room
temperature ≤the sengtemperature,then will display the real temperature;
2=display “dEF” defrost closingand room temperature ≤the seng
temperature ,then will display the real temperature;
0/1/2 1 /
Menu
Descripon
Range
Defaults
M.U
Note:if the product default parameter value is adjusted, this manual will no longer be marked.
6、KEYS
6.1 KEYS
Name Funcon Acon Led
Set
Set enter Press and release Set light on
Enter into the administrator menu Pressingat least 5s Set light on
Opens Programmingmenu Confirm commands
Press
Set light on
▲
Scroll menu items Increases values
press
Set light on
Upload the date to hot key
Pressing3s
Success“uP”
、
fail “Er”
▼
Scroll menu items Increases values
press
Set light on
Download the date from hot key
Pressing3s
Success“do”
、
fail “Er”
Quit from user menu
press
Set light off
Acvates the manual defrost funcon pressing3s light on or off
▲+▼
The values of user menu parameters recovery
Pressing10s
“rSt”
HC Cooling /heang 0 /
0:cooling
1:heang

7.Output instruction
8.special display code
9.Wiring diagram (Refer to the actual product. )
10. Safety rules
ECS-961neo Temperature controller
E1
Probe failure
Er
Copy card failure
EP Copy card date can’t match controller data
rSt
Parameters already recovery
do
Upload succeed
up
Download succeed
LOC
Room temperature set locked
6.2 Key operaon
Set the temperature
a) Press and release “Set” to enter into the user menu, “set ” light on and display “SEt”.(Note:if LOC=n , it will display “LOC” and the
value can’t be modified)
b) Press “Set” key will display the value of “SEt” .
c) Press ▲/▼ key to adjust the value of “SEt”.
d) Press key or waing 30s to save the set point value and return to display status.
Enter password
a) Pressing “Set”key 5s, will display PA1.(Enter the correct password to enter into the administrator menu. If Password seng (PA1≠0),
will display PA1. If Password seng(PA1=0), will enter into the administrator menu directly )
b) Press “Set” key will display “00”, then press “▲”/“▼” to enter the password.
c) Aer finishing to entering the password, press “Set” key will display PA1, if the password is correct ,then will enter into the
administrator menu. Press ▲or ▼ to choose the parameters: diF->HSE->......->CA1->ddL; or the controller will quit from the seng
status.
Universal password: 125
Parameter value set
a) Choosing the parameter code and press “Set” key.
b) Press ▲/▼ to adjust the value.
c) Press “Set” key to return the parameter display status.
d) Press or waing 30s to save the set point and return to the temperature display status.
Parameter value recovery
a) When the controller in the temperature display status , pressing both ▲+▼ 10s, will display rSt code . it means that the controller
already recovery.
b) When using the CPK-4 hot key to program the controller, it will auto double backup parameters.
c) The first is use to drive the controller and the second will use to recovery the controller.
d) Connect CPk-4 again and download the data if you want to modify the second backup parameter.
Manual Defrost funcon: pressing key 3s defrost will on or off.
Copy card
Upload (from the controller to copy card)
a) Program the controller first by hands;
b) Connect the copy card and pressing ▲ key unl display “ uP” code;
c) Aer 5S , pull up the copy card;
Download (from the copy card to the controller)
a) Aer connecng the copy card, pressing ▼ key unl display “ do” code;
b) Aer 5s, pull up the copy card;
Note: If it displays“Er”, it indicates the failure of programming. At this me, you need to check whether the copy card is reliably inserted,
if yes, repeat the above steps again.
If it displays“EP”, it indicates inconsistent data between copy card and controller, programming fails. At this me, need to change to the
right copy card and repeat the steps above; or upload the data of copy card again, and repeat the steps above.
And during this me , should provide a stable power and copy card is well connecon .
Cooling/heang:
Normal status:
HC = 0 , cooling:
When the cabinet temperature is higher than the set temperature (SEt) + hysteresis (diF), and finish the compressor start Min. interval,
the compressors will start ;
When the cabinet temperature is lower than the set temperature (SEt), the compressor will close.
HC = 1, heang :
When the cabinet temperature is lower than the set temperature (SEt) , and finish the compressor start Min. interval, the heang will start ;
When the cabinet temperature is higher than the set temperature (SEt)+ hysteresis (diF), the heang will close.
Note: if the compressor is the first me power on, compressor delay me will according( OdO) or the compressor delay me will be
according (doF).
Probe failure: Compressor will running according the set me cycle.
If Ont=0 and OFt=0, compressor will be always close.
If Ont=0 and OFt≠0, compressor will be always close.
If OFt=0 and Ont≠0, compressor will be always running.
Defrost:
1)dEt=0, defrost is forbidden.
2)dEt≠0, defrost will be acvaon according any below condions:
a) If dPO=y, defrost will start aer running out the me of defrost delay(dOH).
b) Aer running out the me of “dit”, will start the defrost funcon.
Note: defrost cycle (dit) and (dOH) will according dCt( 0,1,2).
c) Pressing 3S, start to defrost.
3) In the state of defrost (Any of the following condion could close defrost):
① Will close the defrost when run out the me of dEt.
② Will close the defrost funcon if pressing key 3S.
4) Compressor start to work aer the defrost.
Note: the status of display during the defrost :
ddL=0: display the real temperature.
ddL=1: display the temperature when start to defrost, defrost closing and room temperature ≤the seng temperature, then will display
the real temperature.
ddL=2: display “dEF”, defrost closing and room temperature ≤the seng temperature, then will display the real temperature.
★Danger:
1) Strictly disnguish the power wire, relay output, sensor down-lead and data line, and the relay could not be overloaded.
2) Prohibit connecng the wire terminals without electricity cut-off.
★Warning:
Prohibit using this unit under the environment of over damp, high temp, strong electromagnesm interference or strong corrosion.
★Noce:
1) The power supply should conform to the voltage value indicated in the instrucon, and make sure a steady power supply.
2) To avoid the possible interference, the sensor down-lead/data line and power wire should be kept in a proper distance.
17(5)A
NL
Power
Hot Key
N
1 2 3 4 5
Other Elitech Controllers manuals
Popular Controllers manuals by other brands

Honeywell
Honeywell T775L Series installation instructions

IP Power
IP Power 9258 Quick start user manual

McIntosh
McIntosh MPC1500 owner's manual

motortronics
motortronics VCM series quick start guide

KRIWAN
KRIWAN INT280-60 quick start guide

Gira
Gira Powernet Single Switching Actuator installation instructions