Elitech ECS-10HT1 User manual

ECS-10HT1 Temperature controller instruction
1.Product Overview
ECS-01HT1 Universal temperature controller can convert Fahrenheit, Celsius display display,
switching cooling / heating mode. The allocation of cabinet temperature sensor and defrosting control
sensor. Optional defrost relay output and copy card function.
2.operation and display panel
3.Specifications and dimensions
Installation dimension : 71mm×29mm Controller size : 78.5mm×34.5mm×74mm
4.Technical parameters
1)Measuring range : -50~99℃/℉(only refers to the sensor calibration value is set to 0)
2)Temperature resolution : 9.9~-9.9 , 0.1℃/℉, the others,1℃/2℉
3)Measurement accuracy : -40℃~50℃, ±1℃, 50℃~70℃, ±2℃, the others : ±3℃
or -40℉~99℉, ±2℉, the others : ±6℉
4)Temperature controlling range : -50~99℃/℉
5)Power supply : 220±10%(VAC) , 50/60Hz
6)power consumption : <3W
7)Rated current of the relays :
Refrigeration : 30A/220VAC , it can directly drive 1.5 HP (220VAC) compressor , single phase
17A/220VAC , it can directly drive 1.0HP (220VAC) compressor , single phase
Defrost: 10A/220VAC( suggest connect the max 1.4 KW electric heating wire)
8) Front panel water proof : IP65
9)The back shell water proof : None
10) Operation condition : 0℃~55℃
11) Storage condition : -25℃~75℃,
12) Relative humidity : 20%~85% (relative humidity )
5.Indicator light status description
Indicator light
Symbol
Status
Meaning
Setting
set
On
Parameter settings
Off
working order
Compressor
On
Cooling / heating
Off
Cooling / heating stoped
Flashing
Cooling / heating delay

Defrost
On
Defrost work
Off
Defrost stop
Temperature unit
℃
On
Temperature unit is ℃
Temperature unit
℉
On
Temperature unit is ℉
Check the temperature setting
On
See the set point
6.Parameter Table
Menu
Functions
Setting range
Default
Level
St
Temperature setting value
Maximum ~Minimum Set Point
3
Pr0
Hy
Hysteretic value
0.1~10℃
1~25℉
2
Pr1
LS
Minimum set point
-50℃~St
-50℉~St
-50
Pr2
US
Maximum set point
St~99℃
St~99℉
99
Pr2
ot
Cabinet sensor calibration
-9.9~9.9℃
-20~20℉
0
Pr1
P2
Evaporator sensor selection
y:Enable
n:Forbidden
y
Pr1
oE
Evaporator sensor calibration
-9.9~9.9℃
-20~20℉
0
Pr2
od
Outputs activation delay at start
up
0~99min
0
Pr2
AC
Anti-short cycle delay
0~50min
1
Pr1
Cy
Compressor running time in the
mode of “Run/stop in a
proportional time”
0~99min
15
Pr2
Cn
Compressor stop time in the
mode of “Run/stop in a
proportional time”
0~99min
30
Pr2
CH
Cooling /Heating
CL:Cooling
Ht:Heating
CL
Pr2
CF
℃/℉
C:℃
F:℉
C
Pr2
Ld
Default Display
P1:Display the cabinet sensor
P2:Display the evaporator sensor
SP:Display the temperature
setpoint
P1
Pr2

dE
Defrost termination temperature
-50~90℃
-50~90℉
2
Pr1
id
Defrost cycle
0~99hour
8
Pr1
Md
The maximum time of defrost
1~99min
20
Pr1
dF
Defrost status display
rt : Display cabinet temperature
It : Display start-defrost cabinet
temperature
St : Display temperature setting
value
dF : Display “dF”
it
Pr2
AU
Cabinet temperature upper limit
alarm value
(AL+1)~99℃
(AL+1)~99℉
99
Pr1
AL
Cabinet temperature lower limit
alarm value
-50℃~(AU-1)
-50℉~(AU-1)
-50
Pr1
Ad
Temperature alarm delay
0~99min
15
Pr2
dA
Exclusion of temperature alarm
at startup
0~99min
90
Pr2
7. FRONT PANEL COMMANDS
Key
Function
Button action
Indicator light
SET
To display target set point
Press and release
immediately
light
Set point value
Push the key for more
than 2 seconds
Set recording light
Save the set point and exit the
setting mode
Press the response
Set Light is off
In programming mode it selects a
parameter
Press the response
Set recording light
SET+▼
To enter in programming mode
Pressing the keys for 3s
Set recording light
SET+▲
To return to room temperature
display
Press the response
Set Light is off
▲
In programming mode it browses
the parameter codes or increases
the displayed value
Press the response
Set recording light
Upload the data to copy card
Pressing the keys for 1s
Success of “uP” 、
Failure of "Er”
▼
In programming mode it browses the
parameter codes or decreases the
displayed value
Press the response
Set recording light

Download the copy card
pressing the keys for 1s
Success of “do” 、
Failure of “Er”
To display the Evaporator
temperature
Press the response
Start manual defrost
pressing the keys for 2s
light
HOW TO SEE THE SET POINT :
1) Push and immediately release the SET key, the set point will be showed and the “ ”LED
starts lighting ;
2) Push and immediately release the SET key or wait about 15s to return to normal visualisation.
HOW TO CHANGE THE SET POINT :
1) Push the SET key for more than 2 seconds to change the set point value ;
2) The value of the set point will be displayed and the “set ”LED starts lighting ;
3) To change the Set value press the ▲or ▼ within 15s ;
4) To memorise the new set point value push the SET key again or wait 15s.
HOW TO CHANGE A PARAMETER VALUE :
To change the parameter’s value operate as follows:(first level Pr1)
1)Enter the Programming mode by pressing the SET+ ▼keys for 3s , the “set”LED starts to light ;
2)Select the required parameter. Press the SET key to display its value ;
3)Use▲or ▼to change its value ;
4)Press SET to store the new value and move to the following parameter ;
5)To exit : Press SET+▲or wait 15s without pressing a key .
HIDDEN MENU(the second level Pr2)
(The hidden menu includes all the parameters of the instrument (Pr1 and Pr2))
1) Enter the Programming mode by pressing the SET+▼keys for 3s the”set “LED starts to light ;
2) Then push again the SET+▼ keys for more than 7s. The L2 label will be displayed immediately
followed from the Hy parameter ;
3) Select the required parameter ;
4) Press the SET key to display its value ;
5) Use ▲or ▼to change its value ;
6) Press SET to store the new value and move to the following parameter ;
7) To exit: Press SET+▲or wait 15s without pressing a key.
NOTE: If none parameter is present in L1, after 3s the “nP” message is displayed. Keep the keys pushed
till the L2 message is displayed.
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND
VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL”
(user level) by pressing SET+ ▼.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
TO LOCK/ UNLOCK THE KEYBOARD

Keep pressed ▲+▼ for more than 3s,the “oF” message will be displayed and the keyboard will be
locked.
Keep pressed ▲+▼ for more than 3s ,the “on” message will be displayed and the keyboard will be
unlocked.
MANUAL DEFROST
Press to view the current evaporator sensor measured temperature value.
Push the key for more than 2 seconds and a manual defrost will start.
8.Output
1 Cooling/Heating :
Cooling :
Normal status : When the cabinet temperature is higher than the set point + hysteresis (Hy),and finish
the Anti-short cycle delay time(AC), cooling will start ;
When the cabinet temperature is lower than the set point, cooling will stop.
For the first time the power on ,and the time up to (od) value , if the cabinet temperature is higher than
the set point + hysteresis (Hy) , cooling will start.
Heating:
Normal status : When the cabinet temperature is lower than the set point , and finish the Anti-short cycle
delay time(AC), heating will start ;
When the cabinet temperature is higher than the set point + hysteresis (Hy), heating will stop.
For the first time the power on ,and the time up to (od) value , if the cabinet temperature is lower than
the set point , heating will start.
If the cabinet sensor is fault , the compressor will run and stop according to the set time.( running
time Cy and stop time Cn).
2 Defrost:
1) If the defrost cycle (id=0) , the defrost will be forbidden .
2) id≠0:
①The Evaporator sensor start to work (P2=y), the evaporator’s sensor temperature is higher than
the defrost termination temperature(dE) , it can’t open the defrost function .
②The Evaporator sensor start to work (P2=y) and the evaporator’s sensor temperature is lower
than the defrost termination temperature(dE) or (P2=n) , the defrost function will start when fit one of the
next conditions :
a) The controller will start defrost according to the set defrost cycle.
b) Press for 2s,start defrost.
3) Under the defrost state(Any of the following conditions can be closed defrosting):
①The evaporator sensor start to work (P2=y) ,Evaporator sensor temperature >Defrost
termination temperature(d7),defrost is closed
②Maximum time of defrost(Md)runs out,defrost is closed;
③Press for 2s,stop defrost;
3 FaultAlarm :
Mess.
Cause
Outputs
P1
Cabinet temperature sensor fault
Compressor output according to “Cy” e “Cn”
P2
Evaporator sensor fault
Defrost relay will working fellow the preset of “id”

Mess.
Cause
Outputs
and “Md”
HA
Cabinet high temperature alarm
Outputs unchanged
LA
Cabinet low temperature alarm
Outputs unchanged
nP
Evaporator sensor is
forbidden ,display screen show
the evaporator’s temperature
Er
Hot key program failure
1) When the temperature sensor is fault , it is display P1 or P2, it will recover when the problem is
solved.
2) Cabinet over temperature alarm :
When the cabinet temperature is beyond the (AU) set point , Ad and (dA) all finished , it will display
HA, when the temperature is lower than the (AU) , the alarm will stop.
When the cabinet temperature is below the(AL) set point , Ad and (dA) all finished , it will display LA,
when the temperature is higher than the (AL) , the alarm will stop.
9.Hot key
1) Upload
①Program one controller with the front keypad.
②Insert the “Hot key” and push ▲key; the "uP" message appears.
③Turn OFF the instrument remove the “Hot Key”, then turn the controller ON again.
2) Download
①Insert the “Hot key”, push the ▼key, the controller will display “do”.
②Turn OFF the instrument remove the “Hot Key”, then turn he controller ON again.
NOTE: The “Er” message is displayed for failed programming.
In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the
operation.
★Pelase make sure that the power is stable during this time.
10.Wiring diagram

11.Safety rules
★Danger :
1) Strictly distinguish the power wire, relay output, sensor down-lead and data line, and the relay
could not be overloaded.
2) Prohibit connecting the wire terminals without electricity cut-off.
★Warning :
Prohibit using this unit under the environment of over damp, high temp., strong electromagnetism
interference or strong corrosion.
★Notice:
1) The power supply should conform to the voltage value indicated in the instruction, and make sure a
steady power supply.
2) To avoid the possible interference, the sensor down-lead/data line and power wire should be kept in

a proper distance.
3) When evaporator sensor is installed, the sensor should be well connected with the copper tube
which is 5cm away from evaporator inlet.
Table of contents
Other Elitech Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Trane
Trane VariTrac Installation

Critical Environment Technologies
Critical Environment Technologies PDC Series Installation and operation manual

TRI02SYS
TRI02SYS 02LINE 10020076 Installation and operating manual

Seeley
Seeley Braemar XE71-42G owner's manual

Myron L
Myron L ULTRAPEN PTBT2 manual

Raychem
Raychem HTC-915 manual