4.9 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with oor n.
3. Press the “SET” key to display its value ( and LED starts blinking).
4. Use oor nto change its value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
4.10 HOW TO LOCK THE KEYBOARD
1. Keep the oand nkeys pressed together for more than 3 s the oand nkeys.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is only
possible the viewing of the set point or the MAX o Min temperature stored and to switch
ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the oand nkeys pressed together for more than 3s.
4.11 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is
switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a
monitoring system is connected, it does not record the instrument data and alarms.
N.B. During the OFF status the Light and AUX buttons are active.
4.12 TO SEE THE PROBE VALUES
1. Enter in “Pr2” level.
2. Select “Prd” parameter with oor n.
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value.
4. Use oand nkeys to display the other probe values.
5. Press “SET” to move to the following parameter.
5. PARAMETER LIST
REGULATION
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set
point.
LS Minimum set point limit: (-50,0°C
SET; -58°F÷SET) Sets the minimum acceptable value for the set
point.
US Maximum set point limit: (SET
110°C; SET÷230°F) Set the maximum acceptable value for set point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the
instrument and inhibits any output activation for the period of time set in the parameter. (Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used,
for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case
of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of
faulty thermostat probe. With COF=0 compressor is always active.
CH Type of action : CL (COOL); Ht (HEAT)
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is
changed the SET point and the values of some parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
de = 0,1°C
in = 1 °C
Lod Local display : select which probe is displayed by the instrument:
P1 = Thermostat probe
P2 = Not used
P3 = auxiliary probe
1r2 = Not used
Red Remote display : select which probe is displayed by the remote display (XW-REP)
P1 = Thermostat probe
P2 = Not used
P3 = auxiliary probe
1r2 = Not used
DEFROST
EdF Defrost mode:
in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor
is running (even non consecutively).
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
cycles.
MdF (Maximum) duration of defrost: (0÷255 min) it sets the maximum length for defrost.
dFd Display during defrost:
rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
dEF = “dEF” label;
dEG = “dEG” label;
dAd Defrost display time out: (0
255 min) Sets the maximum time between the end of defrost and the
restarting of the real room temperature display.
dPO First defrost after start-up:
y = Immediately;
n= after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost will be
delayed for this time.
ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
ALC= rE, 0
50°C or 90°F
ALC= Ab, ALL
110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALL Low temperature alarm setting:
ALC = rE , 0
50 °C or 90°F
ALC = Ab , - 50°C or -58°F
ALU
when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature
alarm set point, always positive.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the
corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the
temperature alarm condition after the instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0
255 min) Time interval between the detection of the temperature
alarm condition at the end of defrost and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0
255 min) Time delay to signal the temperature
alarm condition after closing the door.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its
alarm signalling: the flashing message “dA” is displayed.
nPS Pressure switch number: (0
15) Number of activation of the pressure switch, during the “did” interval,
before signalling the alarm event (I2F= PAL).
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0
12.0°C/ -21
21°F) allows to adjust possible offset of the
thermostat probe.
O3 Auxiliary probe calibration: (-12.0
12.0°C/ -21
21°F) allows to adjust possible offsets of the evaporator
probe.
P2P Evaporator probe presence:
n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.
P3P Auxiliary probe presence: n= not present; y= present.
HES Temperature increase during the Energy Saving cycle : (-30,0°C
30,0°C / -22÷86°F) sets the
increasing value of the set point during the Energy Saving cycle.
DIGITAL INPUTS
odc Compressor and fan status when open door:
no = normal;
Fan = normal;
CPr = Compressor OFF;
F_C = Compressor OFF.
I1P Door switch input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;
dFr = Start defrost;
AUS = not used;
Es = Energy Saving;
onF = remote On/OFF.
did Time interval/delay for digital input alarm:(0
255 min.) Time interval to calculate the number of the
pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines
the time delay between the detection and the successive signalling of the alarm.
SAA Set Point for anti-condensing heater: (-50,0÷110,0°C; -58÷230°F) defines the room temperature
setpoint to switch on the anti-condensing heater.
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the Dixell parameter map.
Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2 and the auxiliary
probe Pb3.
Pr2 Access to the protected parameter list (read only).
6. DIGITAL INPUTS
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the
second is programmable in seven different configurations by the “I2F” parameter.
6.1 DOOR SWITCH INPUT
It signals the door status and the corresponding relay output status through the “odc” parameter:
no = normal;
Fan = normal;
CPr = Compressor OFF;
F_C = Compressor OFF.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the
display shows the message “dA”. The alarm stops as soon as the external digital input is disabled again. During
this time and then for the delay “dot” after closing the door, the high and low temperature alarms are disabled.
6.2 CONFIGURABLE INPUT - GENERIC ALARM (EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm
message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.