
Type S402Y
4
applicable codes) to prevent service 
conditions from exceeding those limits.
Additionally, physical damage to the 
regulator could result in personal 
injury or property damage due to 
escaping gas. 
To avoid such injury and damage, install 
the regulator in a safe location. 
 1. Only personnel qualied through training and    
 experience should install, operate, and maintain a 
 regulator. Before installing a Type S402Y 
 regulator, check for damage which have might 
 ocurred in shipment. Also check for dirt or foreign 
 materials which may have accumulated in the 
 regulator body or in the pipeline.
 2. The Type S402Y may be installed in any position 
       (vertical or horizontal).  Apply a good grade of   
 pipe compound to the male threads (being 
       sure not to apply pipe compound to ow path  
 of the pipe) of the pipe and install the regulator 
       so the ows is in the direction of the arrow cast  
 on the body. Use approved piping procedures 
 when installing the regulator. The spring case can 
 be rotated to any position relative to the body.
!
WARNING
A regulator may vent some gas to 
the atmosphere. In hazardous or 
ammable gas service, vented gas 
may accumulate, and cause personal 
injury, death, or property damage due 
to re or explosion.  Vent a regulator 
in hazardous gas service to a remote, 
safe location away from air intakes or 
any hazardous location. The vent line 
or stack opening must be protected 
against condensation or clogging.
Under enclosed conditions or indoors, 
escaping gas may accumulate and be 
an explosion hazard. In these cases, 
the Type S402Y vent should be piped 
away from the regulator to a safe 
location outdoors.
 3. On outdoors installations, regulators installed with 
 vents in positions other than vertically down 
 require additional vent protection from the 
 elements. Such protection may be with separate 
 hood, shields, or the Fisher®Y602 Series vents. 
 4. Regulator operation within the ratings does not 
 preclude the possibility of damage from the debris 
 in the lines or from external sources. A regulator 
 should be inspected for damage periodically and 
 after any overpressure condition.
 5. With proper installation completed, slowly open 
 the upstream and downstream shutoff valves. 
 Check all connections for leaks. Check the 
 downstream equipment for proper operation.
 6. If outlet pressure adjustment is necessary, monitor 
 downstream pressure with a gauge during the 
 adjustment procedure. To increase the outlet 
 pressure, the adjusting screw (key 12, Figure 1) 
 must be turned clockwise. This requires removal of 
 the closing cap (key 11, Figure 1). To reduce the 
 outlet pressure setting, turn the adjusting screw 
 counter-clockwise. Do not adjust the spring to 
 procedure an outlet pressure setting above the limit 
 stamped on the regulator.
Overpressure Protection
The wide-open Cg for relief sizing along with the 
capacity information should be used in choosing 
appropriate overpressure protection devices to 
ensure that none of the limits in the Specications 
section, Table 1, or Table 2 are exceeded.
Overpressuring any portion of a regulator or 
associated equipment may cause leakage, 
parts damage, or personal injury due to bursting 
of pressure-containing parts or explosion of 
accumulated gas. Regulator operation within ratings 
does not prevent the possibility of damage from 
external sources or from debris in the pipeline. A 
regulator should be inspected for damage after any 
overpressure condition. 
Startup
!
WARNING
In order to avoid an overpressure 
condition and possible equipment 
damage, pressure gauges should 
always be used to monitor pressures 
during startup.