Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
18
Additional Device Status - DVC5000 Device Revision 3, Firmware 5, 6
Command 48 returns 7 bytes of data, with the following status information:
Byte Bit Name of Status Bit Meaning
0
7 Reserved
6No Free Time 1,2 Active if the microprocessor detects a fault in the servo execution
period.
5RAM Failure 1,2 Active if there is a failure associated with the internal RAM
memory.
4Drive Current Failure 1,2 Active when the drive current to the I/P converter is not flowing as
expected.
3Critical NVM Failure 1,2 Active if there is a failure of nonvolatile memory used for
configuration data critical for instrument operation.
2Temperature Sensor Failure 1,2 Active when the instrument temperature sensor fails or the sensor
reading is outside of the range of 60° to 100°C (76° to 212°F).
1Pressure Sensor Failure 2
Active if any of the 3 pressure sensor readings are outside the range
of 24.0% to 125.0% of the calibrated pressure for more than 60
seconds.
0Travel Sensor Failure 1,2 Active if the sensed travel is outside the range of 25.0% to 125.0%
of calibrated travel.
1
7Auto Cal in Progress Alert 2Active when auto calibration is in progress.
6Dynamic Bypass Enabled 2Active if Dynamic Bypass is enabled.
5Calibration In Progress Alert 2Active when calibration is in progress.
4Diagnostics in Progress Alert 2Active when a diagnostic test is in progress.
3High Performance in Effect Active when the instrument is using the High Performance Tuning
Parameters.
2Custom Characterization Custom Characterization in Effect active if the user-defined
Custom Characterization is enabled.
1Input Characterization Input Characterization in Effect active if any of the user-defined
Characterizations other than “Linear” is enabled.
0PWB Set to “Multi-Drop” 2Active is PWB switch is set to “Multi”
2
7 Reserved
6NonCritical NVM Alert 2Active if there is a failure of nonvolatile memory used for data not
critical for instrument operation.
5Cycle Counter High Alert 2Active if the Cycle Counter exceeds the Cycle Count Alert Point.
4Travel Accumulator High
Alert 2Active if the Travel Accumulator exceeds the Travel Accumulator
Alert Point.
3Instrument Time is Invalid
Alert 2Active if the instrument has been powered down since the last time
the instrument clock was set.
2 Reserved
1Offline / Failed Alert 2Active if a shutdown alert has put the DVC5000 in a failed state.
0Auxiliary Input Alert 2Active when the AUX input is configured as an alarm switch and the
alarm is active
"Reserved" bits are always set to 0.
1. Sets “Field Device Malfunction”.
2. Sets “More Status Available”.
(continued)