manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Industrial Electrical
  8. •
  9. Emerson Liebert NXL User manual

Emerson Liebert NXL User manual

1
Liebert®NXL Battery Interface Box™
Product Specification/Installation Sheet
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert
NXL™ Battery Interface Board Box. Read this manual thoroughly before working with the DC system.
Retain this manual for use by installing personnel.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules.
These limits provide reasonable protection against harmful interference in a commercial environment. This
unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with
this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a
residential area may cause harmful interference that the user must correct at his own expense.
Placement and Cable Entry
The Liebert Battery Interface Box should be installed near the DC disconnect. The location should allow
access to the box and allow the front door to be opened for service. Access to the Battery Interface Board
(BIB), fuse disconnects and terminal blocks are behind the front door. See Figure 1 for cable entry layout.
!WARNING
Risk of electrical shock. Can cause personal injury or death.
The DC terminal voltage connected to this equipment will exceed 400VDC and is potentially
lethal. Be constantly aware that the DC system contains high DC as well as AC voltages.
Check for voltage with AC and DC voltmeters before making contact.
Special safety precautions are required for procedures involving handling, installing and
maintaining the DC system. Only properly trained and qualified personnel wearing
appropriate personal protective equipment should be involved in installing the Liebert NXL
Battery Interface Board Box or preparing the system for installation.
Special care must be taken when working with the batteries associated with this equipment.
Observe all DC safety precautions before working on or near the DC system.
The following precautions must be observed when working on this equipment:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting DC terminals.
• Determine whether the DC source is grounded. If it is grounded, remove source of ground.
Contact with any part of a grounded DC source can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and maintenance.
2
Control Connection
Each Liebert NXL Battery Interface Board Box contains a Battery Interface Board (BIB). All DC systems
must have their Battery Interface boards controls connected in series. The CAN controls cables must be two,
twisted pair, shielded 18AWG (Belden 9156 or equivalent).
NOTICE
Risk of improper installation. Can cause equipment damage.
During system commissioning, Emerson Services will set the jumpers on the External
Interface Board in the Liebert NXL UPS and the BIB. If another DC source is added to the
system after commissioning, it is imperative that Liebert Services reset the jumpers on the
EIB board and the BIB board.
Figure 1 Dimensions and layout
NOTE
Care must be taken to route control cables away from high-voltage cables and busbars.Use
recommended knockouts for installing all cables and use provided tie point to secure, see
Figure 2.
Table 1 Battery Interface Box specifications
Parameter Values
DC Sense Volts, VDC 384-576
DC Sense Current, IDC 0.0002A
CAN Volts, VDC 24V
CAN Maximum Current, IDC 2A
UVR Volts, VDC 48V
Dry Contacts Volts, VDC (Auxiliary Contacts) 24V
Dry Contacts VoltsCurrent, IDC (Breaker Aux) 10mA
Mounting Hardware (supplied by others) Must suppor 30lb. (13.6kg)
UVR Max Cont Current, IDC 100mA
NOTE:
1. All dimensions are in inches (mm).
2.Mounting hardware must support the full
weight of units and be appropriate
for the material the box will be attached to.
Dia. .78 (20)
Knockout
4 Places
Mounting Slot Dia.
.25 (6.4); 2 Each
Hole Cutout Dia.
.63 (15.9); 2 Each
A
FRONT
BOTTOM
TOP
LEFT SIDE
0
4.3
(109)
8.3
(211)
10.8
(274)
12.6 (320)
0
12.6
(320)
0
1.8 (46)
1.8
(46)
1.8 (46)
010.8 (274)
0
RIGHT SIDE
03.6 (92)
FRONT (MOUNTING)
DETAIL A
0
.7 (19) 11 (280)
0
6.3
(160)
536210GX - Submittal
3
Figure 2 Control wiring routing
External Battery Room Temperature Sensor—Optional
Connecting an optional sensor to the BIB to monitor the ambient room temperature will enable the Liebert
NXL to perform temperature-compensation charging. The optional temperature sensor should be mounted in
the area that will have the highest battery ambient temperature. If multiple Battery Interface Boxes are used
with an optional temperature sensor, the UPS will report the highest temperature.
DC Sense Connections—Optional
Connecting the optional DC sense voltage wires will allow the Liebert NXL to display the DC source on the
UPS HMI. This connection cannot be used with split-battery bus systems, flywheel systems or any DC system
that does not have a valid DC voltage when the DC breaker is open.
If the DC sense wires are connected to the BIB, the DC source cabinet may require field-installed fuse
protection; refer to national and local codes to verify. The DC sense wires must run from the most-positive DC
voltage to the most-negative DC voltage
DC Breaker Undervoltage Release (UVR) Contacts
If the DC breaker is used as a Module Battery Disconnect breaker (UPS will have control of the breaker),
then the 48V UVR contacts must be run to the BIB.
If the DC breaker is used as a Battery Isolation Switch, then the 48V UVR contacts will not be run to the
BIB.
CAN Communication Connections
Belkin 9156 (or equivalent) cable must be used to run the CAN Communication Connections. If multiple
External Battery Interface Boxes are used, the CAN cables will connect in a daisy chain from the UPS EIB to
BIB #1 to BIB #2 to BIB #N.
Knockout for
CAN Wiring
Knockout
for Optiona
l
DC Sense
Leads
Optional DC
Sense Leads
Knockout for
BreakerAux
Contacts Leads
Knockout for Optional
Motor Operator
Sense Wiring
CAN Leads
Optional
Temp Sensor
Breaker
C
ontacts
Leads
Knockout for
Optional Temp
Sense Wiring
Optional Motor
Operator Sense Leads
TOP VIEW
BOTTOM VIEW
FRONT VIEW
4
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All
names referred to are trademarks or registered trademarks of
their respective owners.
SL-25515_REV5_07-11
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
Figure 3 Motor operator
+-
MBD
+-
TB1150 (T Conn)
Battery Interface
Board (BIB)
TB1151 (T Conn)
4
3
2
5
1
P1153
Optional Battery
Voltage Sense
(540VDC)
+
-
To
UPS
MBD Form C
From
Battery String
Thermistor
(Option)
Notes:
Unless noted otherwise, wiring symbols used are :
Control wiring by others
Copper busbar / cable landing for power cables
Power wiring by others
Twisted pair control wiring
EG
1
3
1
2
5
4
2
P1152
1
3
2
1
BIB w/
Enclosure
MBD w/ Enclosure
++
--
+
-
-
+
EG
2
TB2
TB1
HV TB
Red
Black
White
Yellow
Brown
Input Voltage
208V
460V/ 480V
575V/ 600V
H1
FDISC 2
T1
F1
H2
X1
X2
From UPS Input
(F53, F54, line-side of CB1)
Use FNQ-R-15 fuses
FDISC 1
Control - Off
Control - On
120/230VAC
120/230VAC
TB2
Motor Operator Parts
Motor Op.
120/230VAC
(Option )
Green
Critical
Alarm
Cont.
CAN L (In)
CAN H (In)
TB1154 (T Conn)
241
Input from TB1154A
(UPS EIB)
+24V (In)
3
Gnd (In)
1
TB1158 (T Conn)
764523
Maint.
Alarm
Cont.
Input from Alber Monitor (Option )
8
Remote
Reset
Control
Contact
UVR Coil
(48VDC)
NO
NC
Com
Com
NC
NO
Neg
Pos

Other manuals for Liebert NXL

4

Other Emerson Industrial Electrical manuals

Emerson SOLA HD SLCASK-CVR User manual

Emerson

Emerson SOLA HD SLCASK-CVR User manual

Emerson AVTRON LOADBANK LPH400 User manual

Emerson

Emerson AVTRON LOADBANK LPH400 User manual

Emerson Numatics G2-2 ControlNet Series Instruction manual

Emerson

Emerson Numatics G2-2 ControlNet Series Instruction manual

Emerson AT Series User manual

Emerson

Emerson AT Series User manual

Emerson Leroy-Somer TAL 049 Instruction Manual

Emerson

Emerson Leroy-Somer TAL 049 Instruction Manual

Emerson PACSystems RX3i IC695CPE400 User manual

Emerson

Emerson PACSystems RX3i IC695CPE400 User manual

Emerson SolaHD User manual

Emerson

Emerson SolaHD User manual

Popular Industrial Electrical manuals by other brands

Riken Keiki RM-5000 Series operating manual

Riken Keiki

Riken Keiki RM-5000 Series operating manual

Murata GRM0225C1E9R8DA03 Series Reference sheet

Murata

Murata GRM0225C1E9R8DA03 Series Reference sheet

Ingersoll-Rand FA5A Supplemental service and maintenance instructions

Ingersoll-Rand

Ingersoll-Rand FA5A Supplemental service and maintenance instructions

Murata GRM32EC81E226KE15 Series Reference sheet

Murata

Murata GRM32EC81E226KE15 Series Reference sheet

Murata GRM31C5C1E104JA01 Series Reference sheet

Murata

Murata GRM31C5C1E104JA01 Series Reference sheet

Murata GRM188R71E223KA01 Series Reference sheet

Murata

Murata GRM188R71E223KA01 Series Reference sheet

Murata GRM0335C1H8R7CA01 Series Reference sheet

Murata

Murata GRM0335C1H8R7CA01 Series Reference sheet

Murata GJM0335C1HR40WB01 Series Reference sheet

Murata

Murata GJM0335C1HR40WB01 Series Reference sheet

Murata GRM033R61E392MA12 Series Reference sheet

Murata

Murata GRM033R61E392MA12 Series Reference sheet

Murata GRM216R71H822KA01 Series Reference sheet

Murata

Murata GRM216R71H822KA01 Series Reference sheet

Massoth DiMAX eMOTION manual

Massoth

Massoth DiMAX eMOTION manual

Murata GRM0335C1E8R2CA01 Series Reference sheet

Murata

Murata GRM0335C1E8R2CA01 Series Reference sheet

Murata GRM3195C1H472JA01 Series Reference sheet

Murata

Murata GRM3195C1H472JA01 Series Reference sheet

Promax Prolite-41 Quick reference guide

Promax

Promax Prolite-41 Quick reference guide

Pepperl+Fuchs LS680-DA manual

Pepperl+Fuchs

Pepperl+Fuchs LS680-DA manual

Murata GRM033R61A104ME84 Series Reference sheet

Murata

Murata GRM033R61A104ME84 Series Reference sheet

Afag CS 8 Series manual

Afag

Afag CS 8 Series manual

nvent Raychem JBU-100-E Installation instruction

nvent

nvent Raychem JBU-100-E Installation instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.