
1.2 Electrical installation
All wiring must conform to local and national codes. Multiple wiring
diagrams are shown in this section. Always refer to the diagrams that apply
to your configuration and disregard all other wiring diagrams.
WARNING
Electrical shock
Failure to install covers and ground leads could result in serious injury or
death.
Disconnect and lock out power before connecting the power supply.
Install all protective covers and ground leads after installation.
To meet the safety requirements of IEC 61010-1 (EC requirement) and
ensure safe operation of this equipment, connect the main electrical
power supply through a circuit breaker (minimum 10 A) which will
disconnect all current-carrying conductors during a fault situation.
This circuit breaker should also include a mechanically operated isolating
switch. If it does not, keep another external means of disconnecting the
power supply from the equipment located close by. Circuit breakers or
switches must comply with a recognized standard such as IEC 947.
To maintain proper earth grounding, ensure a positive connection exists
between the analyzer housing and earth. The connecting ground wire
must be 14 AWG minimum.
Line voltage, signal, and relay wiring should be rated for at least 221 °F
(105 °C).
1.2.1 Wire Rosemount 6888C Analyzer Probe only (no Rosemount 6888Xi
Electronics)
The Rosemount 6888 Analyzer Probe has built-in electronics that control the
heater temperature and amplify the raw O2 milli-volt signal to a linear
4-20 mA.
You can run the 4-20 mA signal lines can be run directly to the control room
and also power the analyzer electronics. There is no O2 display or keypad on
the probe, so you must set up the analyzer through HART® communications
via a Field Communicator or Asset Management Solutions (AMS).
Procedure
1. Remove the cover from the probe.
2. Connect the line (L1 wire) to the L1 terminal, the neutral (L2 wire) to
the L2/N terminal, and the ground wire to the ground lug.
The analyzer accepts line voltage at 120/240 VAC ±10%, 50/60 Hz.
No setup is required.
October 2022 Quick Start Guide
Quick Start Guide 11