Instruction Manual
D103391X012
4310 Wireless Position Monitor
December 2011
4
Table 1. Specifications (continued)
Electrical Classification
Only applicable to the 4310 with battery sourced
power module; External power option approvals will
be included when available
CSA (C/US)— Intrinsically Safe
ATEX— Intrinsically Safe
IECEx— Intrinsically Safe
INMETRO— Intrinsically Safe
NEPSI— Intrinsically Safe
Refer to Special Instruction for “Safe Use” and
Installations in Hazardous locations, starting on
page 11, for additional information
Electrical Housing
Only applicable to the 4310 with battery sourced
power module; External power option approvals will
be included when available
4X & IP66
IEC 61010 Compliance
Meets Pollution Degree 2
Adjustments
Zero and Maximum Span through local interface.
Weight
0.5 Kg (1.1 lbs)
Power Module(2)
Standard
Lithium, non‐rechargeable
Power Module Limits
Standard —10 years @ update rate of 16 seconds or
longer with 3 additional devices communicating
through it
Extended‐Life —10 years @ update rate of 4 seconds
or longer with 3 additional devices communicating
through it
Shelf life —10 years (radio off)
External Power (Optional)
12 - 28 volts DC
130 mA maximum input current
Polarity Insensitive
Wire Size— 14-20 gauge
Update Rates
For position feedback, temperature, and power
module voltage—selectable from 1 second to 1 hour,
1s, 2s, 4s, 8s, 16s, 32s, 1 to 60 minutes
Factory default is 1 minute
Note: Sample rate for position feedback is normally
the same as the update rate. When using Report by
Exception reporting refer to Advanced Wireless
Reporting, on page 27, for additional information.
Construction Material
Housing: Engineered resin
1. The pressure/temperature limits in this manual and any applicable standard or code limitation for valve should not be exceeded.
2. Due to the combustible nature of the lithium content, the power module has special installation, operation, storage, and/or shipping requirements. Observe all warnings included with the power
module before installing, operating, storing, or shipping. Contact your Emerson Process Management sales office if additional information is needed.
Table 2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria(1)
Enclosure
Electrostatic discharge (ESD) IEC 61000‐4‐2 6 kV contact
8 kV air B
Radiated EM field IEC 61000‐4‐3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 10V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 3V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field IEC 61000‐4‐8 30 A/m at 50 Hz & 60 Hz
100 A/m @ 50 Hz A
Burst IEC 61000‐4‐4 2 kV (5/50 ns, 5 kHz) B
Surge IEC 61000‐4‐5 1 kV line to line / 2 kV line to ground B
Conducted RF IEC 61000‐4‐6 3 V (150 kHz to 80 MHz) A
Performance criteria: +/- 2% of effect
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.