REPLACING THE BATTERY
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
When replacing batteries, replace with the same type and size battery.
To replace the battery:
1. Turn off all connected loads, then turn off the UPS and unplug the input
power cord. (Batteries are NOT hot-swappable.)
2. Carefully lay the UPS on its left side, as shown in the diagram.
3. Use a #1 Phillips head screwdriver to remove the four screws from the
right-side cover, then pull up the right-side cover and remove it.
4. Remove the black wire from the negative (-) terminal and the red wire from
the positive (+) terminal.
5. Gently remove the battery from the UPS.
Attention: Risk of Electric Shock.
6. Verify that the replacement battery matches the dimensions and battery
specifications.
7. Connect the battery leads to the new battery. Be sure to reconnect the red
wire to the positive (+) terminal and the black wire to the negative (-)
terminal.
Note: Small sparks may occur at the battery connectors during
reconnection. Take care not to short-circuit the positive and negative
battery terminals while replacing the battery.
8. Place the battery in the UPS.
9. Ensure correct alignment of front panel, then reattach the right-side cover.
Evenly tighten the four screws from Step 3. (Do NOT overtighten screws.)
Dispose of the old battery properly at an appropriate recycling facility.
TROUBLESHOOTING
If the UPS detects a fault, consult the table below for possible causes and solutions. For further assistance, please contact your local Emerson Network Power representative.
SPECIFICATIONS
!
CAUTION
Do not dispose of batteries in a fire. The batteries may explode.
!
CAUTION
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
This product is designed for IT power systems with 230V.
Fault Possible Causes Solutions
Mains is normal, but LED 1 is not illuminated.
The UPS may not be turned on.
The power cord may not be connected properly.
The upstream mains circuit breaker may be tripped.
• Press the On/Off button to turn on the UPS.
• Connect the power cord securely into a wall socket.
• Reset the circuit breaker.
LED 1 flashes (green) every 3 seconds, but there is
no output power. Battery voltage may be too low. • Recharge the UPS for 8 hours.
Alarm buzzer beeps continuously although mains is
normal. The UPS may be overloaded (check LED 2). • Disconnect some equipment from the UPS.
UPS does not provide expected backup time. The UPS battery reached end of life. • Replace the internal battery.
The UPS is on and connected to mains, but fails to
operate properly. Mains power may be outside the unit’s operating range. • If mains is normal, try reconnecting mains and
restarting the UPS.
Model Number PSP500MT3-230U PSP650MT3-230U
Capacity (VA/W) 500/300 650/390
Net Weight, kg (lb.) 3.9 (8.6)
Shipping Weight, kg (lb.) 4.8 (10.6)
Dimensions - W x D x H, mm (in.) 87 x 215 x 251 (3.4 x 8.5 x 9.9)
Mains Voltage 160-287VAC
Frequency 50/60Hz ±5Hz
Output Voltage (Mains Normal) Typical 160-287VAC
Output Voltage (Battery Operation) 230VAC ±5%
On-Battery Wave Form Stepped sinewave
VRLA Battery Type - VDC x Ah x Quantity 12V x 7.2Ah x 1 12V x 7.2Ah x 1
Typical Recharge Time 6-8 hours to 90%
Battery Run Time See Load Autonomy table at right Load Autonomy - Liebert PSP 230V 500VA-650VA
Audible and Visual Audible alarm / LED Load (watts) 500VA 650VA
Backup Sockets IEC 320 C13 (3) 50 55 56
Surge Sockets IEC 320 C13 (1) 100 18 19
Operating Temperature, °C (°F) 0 to 40 (32 to 104) 150 12 12
Storage Temperature, °C (°F) -15 to 40 (5 to 104) 200 8 8
Operating / Storage Relative Humidity 0%-90%, non-condensing 250 5 5
EMI Classification Class B 300 N/A 4
Agency 350 N/A 3
Safety IEC/EN/AS 62040-1-1 Note: All run times are in minutes, assume fully charged
batteries and are typical at 25°C (77°F) with resistive loads.
EMC
EN 62040-2:2005 Class B
IEC 61000-4-2 Electrostatic discharge
IEC 61000-4-3 Radiated E-RFI fields
IEC 61000-4-4 Fast E transients
IEC 61000-4-5 Surges/Lightning
IEC 61000-4-6 Conducted RFI
Transportation ISTA Procedure 1A Certification
Note: The Liebert PSP is compliant with the Restriction of Hazardous Substances Directive (ROHS),
prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.
Step 1
Steps 2 and 3
ATTENTION:
Risk of
Electric Shock