Encelium KX7S User manual

KX7S Touchscreen INSTALLATION INSTRUCTIONS
PRODUCT SAFETY
When using electrical equipment, basic safety precautions should always be followed, including the following:
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Do not use the unit near water.
Do not allow objects to fall or liquids to be spilled
into the enclosure through openings.
Equipment should be mounted in locations and at
heights where it will not readily be subjected to
tampering by unauthorized personnel.
The use of accessory equipment is not recommended
by Encelium as it may cause an unsafe condition.
Do not use this equipment for other than the
intended use.
SAVE THESE INSTRUCTIONS.
READ THESE INSTRUCTIONS BEFORE USING THIS PRODUCT.
GETTING STARTED
Overview
The Encelium KX7S Touchscreen is a 177 mm (7 inches) flush-mount LCD touchscreen display that provides the ability to
recall multiple lighting scenes for a given zone. It's ideal for large multi-purpose spaces where lighting requirements vary
throughout the day, such as an auditorium or conference room.

2KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
SYSTEM OVERVIEW
Wired System Overview
With Encelium X, you can control DALI devices exclusively or a mixture of GreenBus and DALI.
GreenBus
Controller Wired Manager — GreenBus
Sensor SSU
Controller
Sensor
KX7S Touchscreen
XP-6S
Ethernet
GreenBus
Dimming
PoE
Wire Key
DALI
Wired Manager — DALI SSU
Ethernet
DALI
PoE
Wire Key
Sensor Sensor
KX7S Touchscreen

3
KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
Wireless System Overview
This illustration shows how each component is easily integrated into the Encelium X Lighting Control System.
Wireless Manager SSU
Sensor
sor
W
Sensor
KX7S Touchscreen
Integrated
Controller
XP-6S
Ethernet
PoE
Wire Key

4KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
MOUNTING OPTIONS
KX7S Touchscreen
The KX7S Touchscreen is designed for flush-mount, in-wall installations. It requires an available mounting depth of
52.5 mm (2 inches) from the surface of the wall. The recommended mounting height for the KX7S Touchscreen is
between 1.4 and 1.5 m (4.5 and 5 ft) from the bottom of the faceplate. The installation requires 52.5 mm
(2 inches) mounting depth from the surface of the wall.
KX7 front
(bezel removed)
Bezel
195 mm
(7.7 inch)
142 mm
(5.6 inch)
Wall Stud
Wall
Opening
Ethernet Cable
(from PoE Switch)
Mouting Height
1.4 — 1.5 m
(4.5 — 5 ft )
from bottom
of faceplate
Note: There is little margin for error when fitting the KX7S Touchscreen into the wall opening. Make sure to use the included
cardboard cut-out template to create the correct size opening in the wall. Additionally, carefully double-check that all
measurements taken using the cardboard cut-out template are accurate.

5
KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
XP-6S Advanced Control Processor
The XP-6S Advanced Control Processor can be either rack-mounted (mounting bracket included) or free standing in the
IT closet.
INSTALLATION
KX7S Touchscreen
The KX7S Touchscreen is rated for dry, indoor locations only.
Front View Rear View
CONTROL ETHERNETRS-232

6KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
The KX7S Touchscreen has the following built-in components: ambient and proximity sensors, USB port, and reset button.
Reset Button
Ambient and Proximity Sensors
USB Port
Two mounting wings are located on the top and bottom of the KX7S Touchscreen, which can be used to secure the KX7S
Touchscreen to drywall in retrofit installations. Place KX7S Touchscreen in the opening in the wall and tighten the mounting
wing screws located on the front of the KX7S Touchscreen (bezel removed). Attach the bezel, once the touch screen is
securely in place.
Mounting Wing Screws
(2X)
Mounting Wings (2X)

7
KX7S Touchscreen Installation Instructions
KX7S Touchscreen INSTALLATION INSTRUCTIONS
XP-6S Advanced Control Processor
The XP-6S front and back panels.
Front View (Cover Off)Rear View
++++++
USB
PROG PORT
POWER
POWER
SIGNAL IN
HIGH OUT
RELAYS
123
TRIGGERS
123
SENSE
123
COMM
NET LINK
RESET
STATUS
PORT 1 PORT 2 PORT 3 PORT 4 PORT5 PORT 6
IR OUTPUT ADJUST
Model XP-6s
Advanced Control Processor
HIGH OUT
POWER
POWER IRRELAYS
TRIGGERS
SENSE RS-232 (1)
ETHERNET EXPANSION
RS-232 (2)RS-232 (3)
12 VDC 1A
123E
N
D
3-24 VDC
123E
N
D
12V 100mA MAX 3A 30VDC MAX
123
AB AB AB
GND
INPUT
12 VDC
165234
IR SERIAL SENSE
MULTI-PURPOSEI/O PORTS
To access the XP-6S front panel, pull the cover forward to remove.
+
+
+
+
+
+
A single XP-6S Advanced Control Processor can be used to control up to 100 KX7S Touchscreens in a single site.
The KX7S is powered via PoE.
XP-6S
KX7S
CONTROL ETHERNETRS-232
HIGH OUT
POWER
POWER IRRELAYS
TRIGGERS
SENSE RS-232 (1)
ETHERNET EXPANSION
RS-232 (2)RS-232 (3)
12 VDC 1A
123E
N
D
3-24 VDC
123E
N
D
12V 100mA MAX 3A 30VDC MAX
123
AB AB AB
GND
INPUT
12 VDC
165234
IR SERIAL SENSE
MULTI-PURPOSEI/O PORTS
Ethernet to Network SwitchEthernet with PoE to Network Switch

encelium.com
Copyright © 2022 Digital Lumens, Incorporated. All rights reserved. Digital Lumens, the Digital
Lumens logo, We Generate Facility Wellness, SiteWorx, LightRules, Lightelligence, Encelium,
the Encelium logo, Polaris, GreenBus and any other trademark, service mark, or tradename
(collectively “the Marks”) are either trademarks or registered trademarks of Digital Lumens,
Inc. in the United States and/or other countries, or remain the property of their respective
owners that have granted Digital Lumens, Inc. the right and license to use such Marks and/or
are used herein as nominative fair use. Due to continuous improvements and innovations,
specifications may change without notice.
DOC-000447-00 Rev C 02-22
KX7S Touchscreen INSTALLATION INSTRUCTIONS
ELECTRICAL CONNECTIONS
KX7S Touchscreen and XP-6S Advanced Control Processor Wiring
GreenBus
XP-6S
KX7S
PSU
External Power Supply
100 — 240 VAC, 50/60 Hz, 1A
To Additional ECUs
(As Needed)
Power Supply
100 — 240 VAC,
50/60 Hz, 1.8A
SSU
External PoE Switch
120 VAC, 60 Hz, 10 W
(Non-Emergency Circuit)
120 VAC, 60 Hz, 300 W
Emergency Circuit (Preferred)
Non-Emergency Circuit (Acceptable)
Ethernet Cable with PoE
91.4 m (300 ft) maximum (Typical)
Ethernet Cable
91.4 m (300 ft) maximum
(Typical)
Wired Manager —
GreenBus
To secure LAN Port for
PC Lighting Control
(Requires Static IP Address)
Note: A PoE network switch is required to power the KX7S
Note: The maximum run from the network switch
to any end device is 91.4 m (300 ft). The PoE Injector
does not extend the length limitation.
Note: The XP-6S Remote Control
Processor requires 120V power
to the power supply.
HIGHOUT
DALI
XP-6S
KX7S
PSU
External Power Supply
100 — 240 VAC, 50/60 Hz, 1A
To Additional ECUs
(As Needed)
SSU
External PoE Switch
230 VAC, 50 Hz, 10 W
(Non-Emergency Circuit)
230 VAC, 50 Hz, 300 W
Emergency Circuit (Preferred)
Non-Emergency Circuit (Acceptable)
Ethernet Cable with PoE
91.4 m (300 ft) maximum (Typical)
Ethernet Cable
91.4 m (300 ft) maximum
(Typical)
Note: A PoE network switch is required to power the KX7S
Note: The maximum run from the network switch
to any end device is 91.4 m (300 ft). The PoE Injector
does not extend the length limitation.
Note: The XP-6S Remote Control
Processor requires 120V power
to the power supply.
HIGHOUT
Power Supply
100 to 240 VAC,
50/60 Hz, 1.3A
Wired Manager — DALI
To secure LAN Port
for PC Lighting
Control (Requires
Static IP Address)
TROUBLESHOOTING
There are no user-serviceable parts inside. For detailed information about how to set-up, install, use, and maintain Encelium
hardware and software, please visit: help.encelium.com
Table of contents