
7
It is recommended that the task of dimensioning the duct system is given to a professional
engineer.
The ducts must be large enough, min. Ø 100 mm, to allow a sufficiently low air speed. In
particular the outside feed and the waste air ducts need to be wide. The size of the outside
air duct, waste air duct and the outside grille must be Ø 160 mm. Do not fit an insect net
behind the grille.
Use only type approved materials, as galvanised spiral-weld or plastic pipe, for the duct
system. Valves which are suitable for mechanical ventilation must be used. Valves with a
diameter of 100 mm or larger are to be used for supply and exhaust air.
The outside air should be taken, if possible from the north side of the building or from a
shady place where temperature variations are moderately small.
The waste air should be led out about 90 cm above the roof saddle. Use insulated factory
made fittings. A cover must be installed on the end of the waste air duct to prevent rain
water from entering the duct system.
To enable duct cleaning, a sufficient number of control hatches should be placed in the
duct system. The control hatch locations could be marked for example on the roof trusses
to make finding them easier.
The exhaust air valves are placed in the following premises: Toilet, kitchen, washroom,
bathroom, clothing storage room, cleaning cupboard and utility room.
The supply air valves are placed in the following premises: bedroom, living room,
separate dining recess, hobby room, dressing room and sauna. We recommend that a
supply air valve is installed in the innermost corner of the sauna. The air flow from the
valve should be directed above the stove.
The air from a room with supply air is supposed to flow through chinks of the doors or “free
flow” door grilles to areas with exhaust air. Normally a 20 mm chink of the door is enough
besides in the sauna where a 100 mm chink is needed. Additional supply air can be
ducted directly to wood-burning fireplaces (in the sauna) from the outside. The duct must
be closable.
Garages or workshops must not be connected into the ventilation equipment of the house;
they should have their own extractor system or independent heat recovery unit.
The cooker extractor hood should not be connected into the house ventilation system.
(Excess steam and grease will cause blockage of the heat exchanger).
A fan assisted drying cabinet can be connected indirectly to the exhaust valve (drying
cabinet - valve attachment) which allows air from both the room and the cabinet to exhaust
from the same valve. The volume through the exhaust air valve has to be at least 12 l/s.
Silencers. A hard silencer 09 is recommended for the exhaust duct, silencer 09 or 06 is
recommended for the supply air duct.
PLANNING OF THE DUCT SYSTEM