ENTRYPASS EP.MINI User manual

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Version: 1.01
Last Updated: 21-06-2016
EP.MINI WIRING GUIDE

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Notes:
See http://www.entrypass.net/ for updates, revisions, and download the latest
installation manual
There are currently 2 version of EntryPass Platform1 Access Control System available for
different card number system
1) EntryPass Platform1 Access Control System (6 Digit Card Number System) cater for 6
digit card number installation
2) EntryPass Platform1 Access Control System (10 Digit Card Number System) cater for 10
digit card number installation
For EntryPass Platform1 Access Control System to work correctly, both control panel and
software MUST be using the same card number system
This software installation manual might be updated without prior notice
Please refer to separate EntryPass Platform1 User Manual for detail operation help. The
Official EntryPass Platform1 User Manual can be downloaded from our website under
“Download” section

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Technical Support
If you cannot find the answer to your question in this manual or in the Help files, we recommend you
contact your system installer. Your installer is familiar with your system configuration and should be able
to answer any of your questions.
Should you need additional information, please call our Technical Support Help desk, Monday to Friday
9:00 AM to 6:00 PM (GMT +8:00)
Method Details
Phone + 60 (3) - 8068 1929
Fax + 60 (3) - 8068 1922
Internet www.entrypass.net
Email support@entrypass.net
BEFORE YOU BEGIN

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
CAUTION
Battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire. To prevent a risk of explosion do
not pry the battery out with a metal or conductive tool.
Preparing Your EntryPass Controllers
EntryPass controller contains numerous delicate electronic circuits and components which can become
damaged as a result of electrostatic discharge (ESD). Thus, prior to installation, please follow the instruction
below:
•Observe precautions while handling the circuit board assembly by using proper grounding straps and handling
precautions at all
•Visually ensure no onboard parts is broken, damage or contains burn mark
•Do not turn on the power supply until you completed all wiring and external add on devices installations
Instances of Non-Warranty
•Damage due to natural disaster, accident or human cause.
•Damage as a result of violating the conditions recommended in the user manual
•Damage due to improper installation
•Damage due to use of uncertified components
•Damage due to use exceeding the permitted parameters
Considerations Prior to Installation

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
MINI Reader
Keypad Display Unit
Encrypted Lock Control
(ELC)
MINI Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Encrypted Lock Control (ELC)
Description
Red : +12V DC
Black : GND / 0V
Orange : RCLK
Yellow : RDAT
Blue : RTX
Pink : Push Button
Red : +12V DC
Black : GND / 0V
Grey / Yellow : NO1
White / Blue : CM1
White : NC1
Brown : NO2
Grey : CM2
Green : NC2
Purple : +12V DC Lock
Purple : +12V DC Lock
MINI Reader Color Description
Red : +12V DC
Black : GND / 0V
Pink : Door Sensor
Black : GND / 0V
Blue : RTX
Brown : + 5VDC
White : Exit Reader D1
Green : Exit Reader DO
Orange: RCLK
Yellow : RDAT
Grey : RS485 C+
Purple : RS485 C-
Green : RS232 RX Separated
White : RS232 TX Separated
MINI Reader Color Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
White LCD Display
Enter Key
Numbered Keypad
Navigation Pad
LED Indicator
MINI Reader Keypad Display Unit

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Power Supply Unit Specification:
•Switching Power Supply
•12V DC
•3 Amp (Minimum)
ENTRYPASS
Power Supply Unit Specification

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
0 V +12 VDC
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
Red (+12VDC)
Black (Gnd)
Red (+12VDC)
Black (Gnd)
Blue (RTX) Blue (RTX)
Orange (RCLK) Orange (RCLK)
Yellow (RDAT) Yellow (RDAT)
The distance from MINI keypad reader to ELC should not more than 10 meter
Connecting MINI Reader to ELC

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
+-
White/Blue (CM1)
White (NC1)
0V
Emergency
Breakglass
Emergency
Keyswitch
Electro-Magnetic Lock
-
+
Purple (+12VDC)
Purple (+12VDC)
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
Connecting the Lock (NC), Breakglass and Keyswitch to ELC
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
+-
White/Blue (CM1)
Grey/Yellow (NO1)
0V
Electro-Magnetic Lock (Drop Bolt)
-
+
Purple (+12VDC)
Purple (+12VDC)
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
Connecting the Lock (NO), Breakglass and Keyswitch to ELC
Diode(1N4002) must be installed at the locking devices in order to protect against back EMF

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
The distance from door sensor to MINI and from push button to ELC should not more than 30 meter
Door Sensor Push Button
Pink (Door Sensor)
Black (Gnd)
Pink (Push Button)
Black (Gnd)
Connecting the Door Sensor and Push Button

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
To use MINI/N-MINI on exit reader side, you must enable the READER MODE function on the programming
mode
To configure MINI as a
READER Mode, press:
•F1
•123456
•01 Enter
•01 Enter
•05 Enter
•1 Enter
•ESC x3
To configure N-MINI as
aREADER Mode, press:
•F1
•123456
•01 Enter
•01 Enter
•04 Enter
•1 Enter
•ESC x3
0 V +12 VDC
Exit Reader
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
Green (D0)
White (D1)
Black (Gnd)
Red (+12VDC)
Black (Gnd)
Red (+12VDC)
Orange (RCLK)
Yellow (RDAT)
Connecting the Exit Reader –MINI/N-MINI Reader as an Exit
Reader

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
0 V +12 VDC
Green (D0)
White (D1)
Black (Gnd)
Red (+12VDC)
Green (D0)
White (D1)
Exit Reader
Black (Gnd)
Red (+12VDC)
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
The distance from MINI to exit reader should not more than 10 meter
Connecting the Exit reader –3rd Party Reader

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Unit Address
Software address
field
00
255.255.255.0
01
255.255.255.1
02
255.255.255.2
03
255.255.255.3
04
255.255.255.4
05
255.255.255.5
06
255.255.255.6
07
255.255.255.7
08
255.255.255.8
09
255.255.255.9
10
255.255.255.10
11
255.255.255.11
12
255.255.255.12
13
255.255.255.13
14
255.255.255.14
15
255.255.255.15
To configure MINI unit address
(default: 00), press:
•F1
•123456
•01 Enter
•01 Enter
•04 Enter
•Key in new unit address (00 –
15)
•ESC x3
The unit address that you configure on the MINI
controller will determine the controller address on the
EntryPass Platform1 Access Control System software
Configuring the MINI Unit Address

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
DB 9 Female Connecter
White to Pin 2
Green to Pin 3
Black to Pin 5
Green (RS 232 RX)
White (RS 232 TX)
Black (Gnd)
EntryPass Platform1
Server Access
Control System
Connecting to the PC via RS232 Mode
The distance from computer to MINI should not more than 10 meter

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Purple (C-)Purple (C-)
Grey (C+)Grey (C+) Grey (C+)
C-
C+
Purple (C-)
MINI 16
Unit Address: 15
MINI 2
Unit Address: 01
MINI 1
Unit Address: 00
PCC
(Pc Communicator)
RS 232: 10 meter
RS232
Power
Tx
Rx
EntryPass Platform1
Server Access
Control System
RS 485: I000 meter (Maximum)
To configure MINI unit address
(default: 00), press:
•F1
•123456
•01 Enter
•01 Enter
•04 Enter
•Key in new unit address (00 –
15)
•ESC x3
When the implementation consists of more than 1 MINI to be connected to the PC using the same
bus/comport, the unit address for each MINI must be unique. Only a total of 16 controllers can be
connected to each bus/comport.
Connecting to the PC via RS485 Mode

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
0 V +12 VDC
Red/Yellow (+12VDC)
Black (Gnd)
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
Connecting to Power Supply Unit

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
+-
White/Blue (CM1)
0V
Emergency
Breakglass
Emergency
Keyswitch
Electro-Magnetic Lock
-
+
Purple (+12VDC)
Door
Sensor
Push
Button
Black (Gnd)
Exit
Reader
Black (Gnd)
Red/Yellow (+12VDC)
+12 VDC
Switching Mode
Power Supply Unit
(12V DC, 3A Minimum)
EntryPass Platform1
Server Access
Control System
White (NC1)
Orange (RCLK)
Yellow (RDAT)
Blue (RTX)
Pink (Push Button)
Red (+12VDC)
Black (Gnd)
Orange (RCLK)
Yellow (RDAT)
Blue (RTX)
Red (+12VDC)
Green (D0)
White (D1)
Black (Gnd)
Pink (Door Sensor)
RS232
Power
Tx
Rx
Grey (C+)
Purple (C-)
PCC
(Pc Communicator)
C+
C-
Complete Overview

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Before you begin to connect to the EntryPass Platform1 Access Control System, please
make sure all the wiring connection is correct. On the MINI keypad, please make sure the
following setting has been done:
Format Memory
Unit Address
Advisable to
perform format
memory for the first
time you turn on
the power
To configure the MINI
unit address if there is
more than one MINI
controller connected
to the PC
communicator
Before Connecting to the EntryPass Platform1 Access
Control System
Other manuals for EP.MINI
1
Other ENTRYPASS Control System manuals