Register 6 indicates if the measured value is below standby level, above active level
or in between both levels:
■If the measured light level is below the Standby level, Input Register 6 indicates
“Standby”.
■If the measured ambient light level is above the Active level, Input Register 6
indicates “Active”.
■If the measured ambient light level is between the active and stand-by level, Input
Register 6 indicates “Low intensity”. When this feature is used, it is advisable to
adjust the active and standby levels in Holding Registers 34 and 35 according to
the actual ambient light conditions around the sensor.
VERIFICATION OF INSTALLATION INSTRUCTIONS
After switching on the power supply one of the LEDs lights up according to the
status of the measured variable. If this is not the case, check the connections.
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type Description Data Values
1Temperature signed int. Actual temperature level -300—700 500 = 50,0 °C
2Relative humidity unsigned int. Actual relative humidity level 0—1.000 1.000 = 100,0 % rH
3Dew point signed int. Calculated dew point -700—700 200 = 20,0 °C
4CO2unsigned int. Actual CO2level 0—2.000 2.000 = 2.000 ppm
5Ambient light intensity unsigned int. Measured light intensity 0—32.000 1.000 = 1.000 lx
6 Active / standby unsigned int.
Active or Standby indication according the Active /
Standby light level dened via holding registers 34
and 35. If the measured light level is between the
two levels, the indication is “0” (Low intensity)
0—2
0 =
1 =
2 =
Low light intensity
Active
Standby
7—10 Reserved, return “0”
11 Output value 1 unsigned int. Analog output value - T, rH or CO20—1.000 0 =
1.000 =
0 %
100 %
12—13 Reserved, return “0”.
14 Temperature alert ag unsigned int.
Flag indicates that measured temperature is outside
set alert values. Set to ‘1’ when the measured value
is outside the temperature alert values dened by
holding registers 20 and 21
0—1 0 =
1 =
Measured temperature is OK
Measured temperature is too high/ low
15 Relative humidity alert ag unsigned int.
Flag indicates that measured relative humidity
is outside set alert values. Set to ‘1’ when the
measured value is outside the relative humidity alert
values dened by holding registers 22 and 23
0—1 0 =
1 =
Measured rH is OK
Measured rH is too high/ low
16 CO2 alert ag unsigned int.
Flag indicates that measured CO2level is outside set
alert values. Set to ‘1’ when the measured value is
outside the CO2 range limit values dened by holding
registers 24 and 25
0—1 0 =
1 =
Measured CO2is OK
Measured CO2is too high/ low
17 Temperature range limit ag unsigned int.
Flag indicates that measured temperature is outside
set range limit values. Set to ‘1’ when the measured
value is outside the temperature range limit values
dened by holding registers 14 and 15
0—1 0 =
1 =
Temperature range is OK
Temperature range is too high/ low
18 Relative humidity range
limit ag unsigned int.
Flag indicates that measured relative humidity is
outside set range limit values. Set to ‘1’ when the
measured value is outside the relative humidity limit
range values dened by holding registers 16 and 17
0—1 0 =
1 =
rH range is OK
rH range is too high/ low
19 CO2 range limit ag unsigned int.
Flag indicates that measured CO2level is outside
set range limit values. Set to ‘1’ when the measured
value is outside the CO2 values dened by holding
registers 18 and 19
0—1 0 =
1 =
CO2range is OK
CO2range is too high/ low
20 Humidity / temperature
sensor fault unsigned int. Flag indicates if the communication with the
temperature and humidity sensor is lost 0—1 0 =
1 =
No
Yes
21 CO2Sensor fault unsigned int. Flag that shows if the communication with the CO2
sensor is lost 0—1 0 =
1 =
No
Yes
22 Ambient light sensor fault unsigned int. Flag that shows if the communication with the
ambient light sensor is lost 0—1 0 =
1 =
No
Yes