? Error code A. and 3flash alternately?
! The vane switch has not switched on 15s after
the fan has been switched on.
• Vane, fan or grille are dirty. Clean, see page18
(Maintenance).
• Fuse F1 defective (8 A, slow-acting, H). Check
the function of the fan and replace fuseF1 if
necessary.
! Motor defective.
• Remove the device and return it to the supplier.
? Error code A. and 3flash alternately and the
light is red?
! The fault could not be rectified. The programmed
number of start-up attempts having failed, the
ACU initiates a fault lock-out.
• Reset using the RESET button on the ACU or
via the remote reset.
• Check that the vane switch is functional. Clean
the vane, fan or grille if soiled.
? Error code F. and 1flash alternately?
! On burner start-up, the ACU has not detected
a flame during the safety time. In the parameter
“Number of start-up attempts”, it is possible to
program up to three start-up attempts. If one
of the further start-up attempts is successful,
warning signalling stops automatically once the
post-purge time has elapsed.
! Ignition is not working properly.
• Clean the spark electrode and check for correct
distance, see page18 (Maintenance).
• Check the connection of the ignition cables for
damage or moisture.
▷ The spark plug must be fitted correctly.
• Check the ignition spark optically and acoustically
from the fan side during the 4-second ignition
time.
! Poor flame signal due to incorrect burner adjust-
ment.
• Readjust gas pressurepG, see page 8 (Ad-
justing the heater).
! Poor flame signal due to dirty/badly connected
flame rod.
• Clean the flame rod and check for correct dis-
tance, see page18 (Maintenance).
• Check the cable connection, cable and terminal
boot for damage or moisture. The terminal boot
must be fitted correctly.
• Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.
! Air in the gas pipe.
• Vent the gas pipe.
! Valves do not open.
• Remove the valve plug on the combination con-
trolCG and measure the voltage betweenL1
andN during the safety time. If the voltage is
not adequate, first replace the CG and return it
to the supplier.
Attention! Only commission the new ACU once
the short-circuit or fault on the valve output of
the CG has been remedied. Otherwise, the new
ACU will be damaged.
• If the fault continues to be signalled, there may
be a short-circuit on the valve output. Return
the burner control unit to the manufacturer for
inspection.
! Short-circuit on ignition output.
• Replace fine-wire fuse F2 (3.15A, slow-acting,
H) and check the safety function, see page20
(Checking the safety functions and burner opera-
tion).
? Error code F. and 1flash alternately and the
light is red?
! The fault could not be rectified. The programmed
number of start-up attempts having failed, the
ACU initiates a fault lock-out.
• Reset using the RESET button on the ACU or
via the remote reset.
• Rectify the cause of the fault as described for
warning F.1.
? Error code F. and 2flash alternately?
! The flame has gone out during operation. If a
restart has been programmed, an automatic re-
start is carried out provided that the burner has
been in operation for at least 2s beforehand.
• Poor flame signal due to incorrect burner adjust-
ment. Readjust gas pressurepG, see page8
(Adjusting the heater).
• Poor flame signal due to dirty or badly connected
flame rod. Clean the flame rod and check for
correct distance, see page18 (Maintenance).
• Check the cable connection for damage or mois-
ture. The terminal boot must be fitted correctly.