ete Integra 1221 Manual instruction

Setup and Operation Manual
Integra 1221
Panel Mounted Energy Meter
for Single and Three Phase
Electrical Systems
1 Introduction
This document provides operating, maintenance and installation instructions.
This unit measures and displays the characteristics of Single Phase Two Wire
(1P2W), Three Phase Three Wire (3P3W) and Three Phase Four Wire (3P4W)
networks. The measuring parameters include Voltage (V), Current (A),
Frequency (Hz), Power (kW/KVA/KVAr), Power Factor (PF), Imported, Exported
and Total Energy (kWh/kVArh). The unit also measures Maximum Demand
Current and Power, this is measured over preset periods of up to 60 minutes.
This particular model accommodates 0.1A Current Transformers and can be
used with a wide range of CTs. It also comes with a complete communications
capability with built in Pulse and RS485 Modbus RTU outputs, configuration is
password protected. This product is self-powered from any phase of the supply.
1.1 Unit Characteristics
The Integra 1221 can measure and display:
• Phase to Neutral Voltage and THD% (Total
Harmonic Distortion) of all Phases
• Line Frequency
• Current, Maximum Demand Current and Current
THD% of all Phases
• Power, Maximum Power Demand and Power Factor
• Imported, Exported & Total Active Energy
• Imported, Exported & Total Reactive Energy
The unit has a Password-Protected set up menu for:
• Changing the Password
• System Configuration - 1P2W, 3P3W & 3P4W.
• Demand Interval Time
• Reset for Demand Measurements
• Pulsed Output Duration
1.2 Current Transformer Primary Current
This unit requires configuring to operate with the appropriate current
transformer(s). The secondary current is 0.1A. The CT Primary value should be
set according to the CT. It can be used on primary currents up to 9999A. e.g.
For a 250/0.1A CT. CT2 = 0.1, CT1 = 250
On the MID Version, you can only program the CT multiplier ONCE.
This cannot be overridden and must be returned to the factory.
1.3 RS485 Serial –Modbus RTU
This unit is compatible with remote monitoring through RS485 Modbus RTU.
Set-up screens are provided for configuring the RS485 port.
1.4 Pulsed Outputs
The Integra 1221 has Two Pulsed Outputs. One pulsed output is configurable
to active (kWh) or reactive (kVArh) energy. The second pulsed output is fixed to
3200imp/kWh.
2 Start Up Screens
The first screen lights up all display segments
and can be used as a display check.
The second screen indicates the firmware
installed in the unit and its build number.
Please note: The numbers on the product may
vary from those shown here.
The interface performs a self-test and indicates
the result if the test passes.
*After a short delay, the screen will display active energy measurements.
3 Measurements
The buttons operate as follows:
Selects the Power, Voltage, Current, Energy per phase and the
system values.
In Setup Mode, this is “Escape” (hold 3 sec) button.
Selects the Voltage and Current display screens.
In Setup Mode, this is the “Left” (press) button.
Select the Frequency and Power factor display screens.
In Setup Mode, this is the “Up” (press) button.
Select the Power display screens.
In Setup Mode, this is the “Down” (press) button.
Select the Energy display screens.
In Setup mode, this is the “Right” (press) or “Enter” (hold 3 sec) button.
4 Setup
To enter set up mode, hold the button for 3 seconds, until the password
screen appears.
The setup is password-protected so you must
enter the correct password (default ‘1000’) before
continuing.
If an incorrect password is entered, the display will
show:
PASS Err (Error).
To exit the set up menu, hold the button for 3 seconds, the measurement
screen will display.
4.1 Set up Entry Methods
Some menu items, such as Password and CT, require a four-digit number entry
while others, such as supply system, require selection from a number of menu
options.
4.1.1 Menu Option Selection
1. Use the and buttons to scroll through the different options of
the setup menu.
2. Hold the button for 3 seconds to confirm your selection.
3. If an item flashes, then it can be adjusted by the and buttons.
4. Having selected an option from the current layer, hold the button for
3 seconds to confirm your selection.
5. On completion of setting-up, hold the button for 3 seconds, the
measurement screen will then be restored.
4.1.2 Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In
particular, on entry to the setting up section, a password must be entered. Digits
are set individually, from left to right. The procedure is as follows:
1. The current digit to be set flashes and then can be adjusted using the
and buttons.
2. Press the button to move right to the next digit.
3. After setting the last digit, hold the button for 3 seconds to save your
selection.
5 Setup Menu Structure
Set Comms
Set Address 001-247
Set Baud Rate 2400/4800/9600/19200/384000
Set Parity none/odd/even
Set Stop Bits 1 or 2
CT Configuration
Set maximum current that can be monitored according to CT in use.
PT
The PT option sets the Primary Voltage (PT1 100-500000V AC L-N
or 100-500000V AC L-L) and the Secondary Voltage (PT2 100-276V
AC L-N or 100-480 L-L) of the Voltage Transformer (PT) that may be
connected to the meter.
Note: The unit is able to measure from 57.7V AC L-N however
PT2 must be set from 100-276V AC L-N.
Set Pulse
Pulsed Output-Use this section to configure the Pulsed Output Type.
Units- kVArh (default); kWh.
Pulse Rate- Configure the number of pulses to relate to a defined
amount of Total Energy.
Pulse Duration- The energy monitored can be active or reactive and
the pulse width can be selected as 200, 100 or 60mS.
Set Demand
DIT (Demand Integration Time) - This sets the period (in minutes) in
which the Current and Power readings are integrated for maximum
demand measurement. The options are 0; 5; 8; 10; 15; 20; 30 or 60
minutes.
Demand Method- Within this menu, you are able to set whether the
demand is displayed using a sliding or fixed method
Set Time Backlight- The back light is a programmable time (in minutes) that
determines how long this remains on for before this goes into
standby.
Display Scroll - Within this menu, you can determine how long the
screen is displayed for before it scrolls to the next screen.
Set System
Sytem Type- The unit has a default setting of 3 Phase 4 Wire (3P4W).
Use this section to set the type of electrical system.
3P4W/3P3W/1P2W
CT Connections -The CT connections can be reversed through the
“Set Sys Cnct” menu, choosing between Forward (Frd) or Reversed
(Rev) depending on the system.
Set Password- Use this menu to create a custom 4 digit password.
Auto Scroll- Use this menu to determine whether you would like he
display to scroll through the various display screens.
Reset The meter provides a function to reset the maximum demand value
of current and power.
Energy/Demand/All
6 Specifications
6.1 Measured Parameters
The unit can monitor and display the following parameters of a Single Phase
Two Wire (1P2W), Three Phase Three Wire (3P3W) or Three Phase Four Wire
(3P4W) system.
6.1.1 Voltage and Current
• Phase to Neutral Voltages 57.7-276V AC (L-N).
•Phase to Phase Voltages 100-480V AC (L-L).
• Percentage Total Voltage Harmonic Distortion (V %THD) for each Phase to
Neutral (not for 3P3W supplies).
• Percentage Total Voltage Harmonic Distortion (V% THD) between Phases (3
Phase supplies only).
• Current %THD for each Phase.
• Burden <15VA (nom 2VA)
• Self powered from any phase
6.1.2 Power factor and Frequency and Max. Demand
• Frequency in Hz
• Instantaneous power:
• Power 0-3600 MW
• Reactive power 0-3600 MVAr
• Volt-amps 0-3600 MVA
• Maximum Demand Power since last reset
• Power factor
• Maximum Neutral Demand Current, since the last reset (for 3P4W supplies
only)
6.1.3 Energy Measurements
• Imported/Exported active energy 0 to 9999999.9 kWh
• Imported/Exported reactive energy 0 to 9999999.9 kVArh
• Total active energy 0 to 9999999.9 kWh
• Total reactive energy 0 to 9999999.9 kVArh
6.2 Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire
capacity. Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) or
Three Phase Four Wire (3P4W) unbalanced. Line frequency measured from L1
Voltage or L3 Voltage. Three current inputs in a single physical terminal (RJ12)
for connection of external CTs. Nominal rated input current 0.1A AC RMS.
6.3 Accuracy
• Voltage 0·5% of range maximum
• Current 0·5% of nominal
• Frequency 0·2% of mid-frequency
• Power factor 1% of unity (0.01)
•Active power (W) ±1% of range maximum
• Reactive power (VAr) ±1% of range maximum
• Apparent power (VA) ±1% of range maximum
• Active energy (Wh) Class 1 IEC 62053-21
• Reactive energy (VARh) ±1% of range maximum
• Total harmonic distortion 2% up to 63rd harmonic
• Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
Warnings
During normal operation, voltages hazardous to life
may be present at some of the terminals of this unit.
At voltages below that specified in the Range of Use
the meter may shut down. However, voltages
hazardous to life may still be present at some of the
terminals of this unit.
Installation and servicing should be performed only by
qualified, properly trained personnel abiding by local
regulations.
Ensure all supplies are de-energised before attempting
connection or other procedures.
Terminals should not be user accessible after
installation and external installation provisions must
be sufficient to prevent hazards under fault conditions.
This unit is not intended to function as part of a system
providing the sole means of fault protection - good
engineering practice dictates that any critical function
be protected by at least two independent and diverse
means.
The unit does not have internal fuses therefore external
fuses must be used for protection and safety under
fault conditions.
Never open-circuit the secondary winding of an
energized current transformer.
This product should only be operated with the CT
secondary connections earthed.
If this equipment is used in a manner not specified by
the manufacturer, protection provided by the
equipment may be impaired.
Caution: Risk of
Electric Shock

6.4 Auxiliary Supply
This product is self-powered from any of the three phases.
6.5 Interfaces for External Monitoring
Three interfaces are provided:
• Pulse output 1 indicating real-time measured energy (configurable)
• Pulse output 2 3200IMP/kWh (not configurable)
The Modbus configuration (baud rate etc.) and the pulse relay output
assignments (kW/kVArh) are configured through the set-up screens.
6.5.1 Pulse Output
Opto-coupler with potential free SPST-NO Contact
(Contact rating 5-27V DC / Max current input: Imin 2mA and Imax 27mA DC).
The pulse output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.001 = 1 Wh/VArh
0.01 = 10 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000 = 1000 kWh/kVArh
Pulse width 200/100/60 mS.
6.5.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be
configured from the set-up menu:
Baud rate: 2400, 4800, 9600, 19200, 38400
Parity: none (default) / odd / even
Stop bits: 1 or 2
RS485 Network Address: 3 digit number - 001-247
Modbus™ Word order Hi/Lo byte order is set automatically to normal as
defined in IEEE 754. It cannot be configured from the set-up menu.
6.6 Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor
degree. Accuracy is verified under nominal value (within the specified tolerance)
of these conditions.
• Ambient temperature 23°C ±1°C
• Input waveform 50 or 60Hz ±2%
• Input waveform Sinusoidal (distortion factor < 0·005)
• Auxiliary supply voltage Nominal ±1%
• Auxiliary supply frequency Nominal ±1%
• Auxiliary supply waveform (if AC) Sinusoidal (distortion factor < 0·05)
• Magnetic field of external origin Terrestrial flux
6.7 Environment
• Operating temperature -25°C to +55°C*
• Storage temperature -40°C to +70°C*
• Relative humidity 0 to 95%, non-condensing
• Altitude Up to 3000m
• Warm up time 1 minute
• Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
• Shock 30g in 3 planes
*Maximum operating and storage temperatures are in the context of typical daily
and seasonal variation.
6.8 Mechanics
• Enclosure Style DIN 96 panel mount
• Dimensions 96x96x62 mm
• Panel cut-out 92x92mm
• Panel thickness 1-5 mm
• Protection rating Front IP54, Rear IP30
• Material UL 94-VO
• Weight 340 g
7 Installation and Maintenance
7.1 Installation notes
Units should be installed in a dry position, where the ambient temperature is
reasonably stable and will not be outside the range -25 to +55⁰C.
Vibration should be kept to a minimum.
Preferably, mount the Integra so that thedisplay contrast isnot reduced by direct
sunlight or other high intensity lighting.
7.2 Input Wiring and Fusing
Voltage lines must be fused with a fast blow AC fuse 1A maximum. Auxiliary
supply lines must be fused with a slow blow fuse rated 1A maximum. Choose
fuses of a type and with a breaking capacity appropriate to the supply and in
accordance with local regulations.
A switch or circuit breaker allowing isolation of supplies to the unit must be
provided.
7.3 Wire Size
Voltage and current terminal blocks will accept 0.5mm² to 2.5mm² stranded
cable.
7.4 Maintenance
The front of the case should be wiped with a dry cloth only, using minimal
pressure. If necessary wipe the rear case with a dry cloth.
No user serviceable parts.
8 Declaration of Conformity
We, Tyco Electronics UK Ltd, declare under our sole responsibility as the
manufacturer that the poly phase multifunction electrical energy meter “Integra
1221” correspond to the production model described in the EC-type examination
certificate and to the requirements of the Directive 2004/22/EC EC type
examination certificate number 0120/SGS0251. Identification number of the NB
0120.
9 Dimensions
10 Installation
10.1 Single phase two wires
10.2 Three phase three wires
Please note for 3P3W configuration L2 is connected through the neutral
and not V2.
10.3 Three phase four wires
The maximum number of products that can be connect is a single chain is
20 products.
Explanation of Symbols
Refer to manual
Danger of electric shock
Do not discard
While TE has made every reasonable effort to ensure the accuracy of the information in this
catalogue, TE does not guarantee that it is error-free, nor does TE make any other representation,
warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the
right to make any adjustments to the information contained herein at any time without notice. TE
expressly disclaims all implied warranties regarding the information contained herein, including, but
not limited to, any implied warranties of merchantability or fitness for a particular purpose. The
dimensions in this catalogue are for reference purposes only and are subject to change without
notice. Specifications are subject to change without notice. Consult TE for the latest dimensions and
design specifications. TE connectivity (logo), TE (logo) and TE Connectivity are trademarks of the TE
Connectivity Ltd. family of companies. Crompton is a trademark of Crompton Parkinson and is used
by TE Connectivity under a licence. Other logos, product and company names mentioned herein may
be trademarks of their respective owners
TE Energy –innovative and economical solutions for the electrical power industry:
cable accessories, connectors & fittings, insulators & insulation, surge arresters,
switching equipment, street lighting, power measurement and control.
Tyco Electronics UK Ltd
TE Energy
Freebournes Road
Witham, Essex CM8 3AH
Phone: +44 (0)870 870 7500
Fax: +44 (0)870 240 5289
Email: Crompton.info@te.com
www.crompton-instruments.com
Project 2251. Drawing No. CI-3K97301
Rev.12 13/03/2017
Other ete Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Spectra Precision
Spectra Precision Focus 8 Series user guide

Winland Electronics
Winland Electronics TempAlert MTA-1 quick start guide

Geo
Geo Solo II CT user manual

Allendale Electronics
Allendale Electronics AE-MAN-DS user manual

Dynamica
Dynamica HALO DB-20 instruction manual

Johnson Matthey
Johnson Matthey TRACERCO PED-IS user manual