Eurotherm 451 Series User manual

Artisan Technology Group is your source for quality
new and certied-used/pre-owned equipment
• FAST SHIPPING AND
DELIVERY
• TENS OF THOUSANDS OF
IN-STOCK ITEMS
• EQUIPMENT DEMOS
• HUNDREDS OF
MANUFACTURERS
SUPPORTED
• LEASING/MONTHLY
RENTALS
• ITAR CERTIFIED
SECURE ASSET SOLUTIONS
SERVICE CENTER REPAIRS
Experienced engineers and technicians on staff
at our full-service, in-house repair center
WE BUY USED EQUIPMENT
Sell your excess, underutilized, and idle used equipment
We also offer credit for buy-backs and trade-ins
www.artisantg.com/WeBuyEquipment
REMOTE INSPECTION
Remotely inspect equipment before purchasing with
our interactive website at www.instraview.com
LOOKING FOR MORE INFORMATION?
Visit us on the web at www.artisantg.com for more
information on price quotations, drivers, technical
specications, manuals, and documentation
Contact us: (888) 88-SOURCE | sales@artisantg.com | www.artisantg.com
SM
View
Instra

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Manufactured by EUROTHERM AUTOMATION S.A.
ISO 9001 - EN 29001 Certified
Printed in France 12/94 Part No HA 174485 Issue 1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Logic and Analogue Input
Thyristor Units
User
Manual
©Copyright Eurotherm Automation S.A. 1994
All rights reserved. No part of this manual may be reproduced M any form by photostat, microfilm, xerography, recording or any other means,
or incorporated into any information retrieval system. electronic or mechanical, without the written permission of EUROTHERM
AUTOMATION. EUROTHERM AUTOMATION have made every effort to guarantee the accuracy of this spe cification. However. technology
is constantly changing and we LC continually researching and improving ow products which may lead to the modification and omission of data
concerning this specification, and cornequently EUROTHERM cannot be held responsible for any material or bodily damage or any loss or
ensuingcmts.
Printed in France 12/94 Part No HA 174485 Iss.1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

For additional information, please contact your
EUROTHERM office where technicians are at
your service to advise and assist you with
commissioning.
Printed in France 12/94 Part No HA 174485 Issue 1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

451-455-461
USER MANUAL
Page
Chapter 1. INTRODUCTION 1-1
Chapter 2. TECHNICAL SPECIFICATIONS 2-1
2.1 General information common to the 3 series 2-2
2.2 Partial load failure detection 2-3
2.3 Dimensions and weight 2-3
2.4 Installation 2-4
2.5 Internal high speed fuse replacement 2-7
Chapter 3. 451 SERIES SOLID STATE CONTACTORS 3-1
3.1 Main function performed 3-2
3.2 Coding 3-3
3.3 Terminal identification 3-4
3.4 Wiring diagram 3-5
3.5 Partial load failure detection setting 3-11
Chapter 4. 455 AND 461 SERIES POWER UNITS 4-1
4.1 Main function performed 4-2
4.2 Technical characteristics 4-3
4.3 Coding 4-6
4.4 Terminal identification 4-9
4.5 Wiring diagram 4-10
4.6 Input and drive mode configuration 4-21
4.7 461 series settings 4-24
Contents
451-461 User Manual Con .1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Contents (Continued)
Chapter 5. THREE-PHASE WIRING DIAGRAMS 5-1
5.1 451 series solid state contactors 5-2
5.2 455 and 461 series power units 5-4
5.3 "Master-Slave" configuration 5-7
page
APPENDIX. DIAGNOSTICS (455 and 461 series) App-1
Con .2 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Introduction
Chapter 1 INTRODUCTION
The Eurotherm 451-455-461 thyristor unit range offer a vast number of possibilities which,
for the most part, meet the requirements of the low and medium power market. The current
range is from 15 A to 150 A for voltages of up to 660 V rms.
The range is divided into two main groups:
•Solid state contactors (451 series)
The thyristor units, driven by a logic signal, operating in ON/OFF mode with tiring of
the thyristors when the supply voltage changes to zero.
•Power units (455 and 461 series)
The thyristor units driven by an analogue signal emit an output signal proportional
to the thyristor firing angle and burst firing input signal, or a combination of both
signals.
Thyristor unit voltage selection
•Single-phase power supply from 100 to 240 V:
Nominal voltage of unit 240 V.
•Single-phase power supply from 380 to 415 V:
Nominal voltage of unit 440 V.
•Three-phase power supply, mounting 3 wires plus neutral:
Nominal voltage of unit: take into account the voltage between phase and neutral.
•Three-phase power supply, mounting 3 wires (star or delta) or
6wires (open delta):
Nominal voltage of unit: take into account the voltage between phases.
451-461 User Manual 1-1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Introduction
451 series (models 451 to 454)
Three sorts of isolated logic input are available:
•The standard input is suitable for all control signals for solid state contactors,
generated by the Eurotherm controllers.
•The TTL input, available as an option, allows greater sensitivity, without
increasing the current consumption. This input can be driven by a standard
TTL logic.
•The "multi-input", available as an option, is used when several units
must be driven by the same logic signal, and with a minimum current
consumption.
The 451 series can be equipped with a partial load failure detection.
455 series (models 455 to 458)
The input signal and thyristor firing mode configurations are set at order and cannot be
changed (soldered bridge configuration).
The 455 series has a "Slave" output and an inhibition function.
461 series (models 461 to 464)
The input signal and thyristor firing mode configurations are easy to modify by the user
with configuration mini-switches.
The 461 series has current limit, partial load failure detection, gating (except on the 461
model), inhibition functions and the "Slave" output.
1-2 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Contents page
2.1 General information common to the 3 series 2-2
2.2 Partial load failure detection 2-3
2.3 Dimensions and weight . 2-3
2.4 Installation 2-4
2.5 Internal high speed fuse replacement 2-7
Chapter 2
TECHNICAL SPECIFICATIONS
451-461 User Manual 2-1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Chapter 2 TECHNICAL SPECIFICATIONS
2.1 GENERAL INFORMATION COMMON TO THE 3 SERIES
.Supply voltage : +10 % -15 % of the nominal voltage
.Residual load current in locked status : <30 mA
Heat dissipation
Each unit dissipates a maximum of 1.3 W per amp issued.
This dissipation induces a rise in the ambient temperature if the units are mounted in
cabinets.
It is essential to check that the external ambient temperature of the cabinet does not
exceed 50°. Otherwise, provide a fan cooling system.
If this system includes dust removal filters, systematically perform a preventive
cleaning operation every 3 or 6 months depending on the degree of pollution.
Operating temperature: 0°C to 50°C with radiator in vertical position
Storage temperature: -10°C to + 70°C.
Unit cooling
The heat dissipation of the thyristors induces an overheating of the heatsink on which
they are mounted.
Two types of cooling are provided:
- by convection cooling 7 V 4 c o,t, 7/ S4- - CL-
- by fan cooling. 3 / 4 copvlu,61/0 7,C,V
• 15 to 75 A nominal units:
cooling by convection cooling.
•100 to 150 Anominal units:
cooling by fan cooling.
In this case, the unit is equipped with a temperature safety switch which inhibits
thyristor firing in the event of overheating.
2-2 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Model Height Width Depth Weight
mm mm mm kg
451/455/461 247 76 236 3
452/456/462 247 114 236 4
453/457/463 247 152 236 5
454/458/464 280 152 236 5
2.2 PARTIAL LOAD FAILURE DETECTION
Partial load failure detection exists as an option for the 451 series and comes as
standard for the 461 series.
•Partial load failure (PLF) detection principle:
comparison of the load current and voltage (451 series) or
of the power supply (461 series)
to detect an increase in impedance.
•Improved 20% discrimination of the current in the load, does not depend
on supply voltage variations.
•Setting: with a potentiometer on the front fascia from 10 to 100 % of
the unit's nominal current.
•Indication on front fascia with an LED.
•PLF output made via relay switch.
2.3 (OVERALL) DIMENSIONS AND WEIGHT
Table 2.1
451-461 User Manual 2-3
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Model Attachment dimensions
on a vertical wall (mm)
AB
451, 455, 461 0149
462, 456, 462 42 149
453, 454, 457 75 149
458, 463, 464 75 178
2.4 INSTALLATION
Each module is inserted in a pressed steel baseplate.
The baseplate can be mounted:
•on an asymmetrical pair of DIN rails
• or attached on a vertical wall.
Rotation "" / 4 o 4.2 holes
rod Baseplate
Figure 2.1 Attachment
Table 2.2
2-4 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
For assembly:
•tilt the module approximately 20 degrees forwards in relation to the horizontal
•insert the rotation rod in the baseplate recipient (see fig. 2.1)
•raise the module to the horizontal
•turn the lock by a quarter-turn.
The minimum space between 2 modules side by side must be at least 20 mm.
If the modules are mounted on top of each other, it is essential to leave a vertical space of at
least 80 mm between 2 modules, in order to guarantee good ventilation.
For installations in fan-cooled cabinets, it is recommended to fit a fan failure detection device.
For disassembly:
• unlock the top attachment by a quarter-turn
•tilt the module approximately 20 degrees forwards in relation to the horizontal
•release the module from its baseplate.
Warning
Before disassembling the module, make
sure that the heatsink is not hot.
451-461 User Manual 2-5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Terminal blocks Wire cross-sect.
mm2 Tightening torque
N.m
Driver 0.5 to 2.5 0.6
Power 15 A to 40 A 6to 16 1.0
50A to 100 A 16 to 35 2.15
125 and 150 A 35 to 50 4.0
The external wiring is made via the front of the haseplate terminal block, with the module
pulled out.
For low currents, the connections are made with screws.
The power cables are attached to the power terminal blocks marked "L" (Phase) and
"" (Load).
From 125 A, the power cables must be connected using round lugs.
Terminal block parameters
Table 2.3
2-6 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
2.5 INTERNAL HIGH SPEED FUSE REPLACEMENT
The 451 series static contactors and the 455 and 461 series power units (nominal currents
from 15 to 125 A) are equipped with internal high speed fuses.
They are fitted at the rear of the pull-out module.
For the 150 A nominal current, the high speed fuse and its support are external and
driven separately from the thyristor unit.
Important
The high speed fuses are only used to protect the thyristors against
over-loads of wide amplitudes.
The user's installation must be protected (non-high speed fuses,
thermal, magnetic or electromagnetic circuit breaker, suitable
isolating switch) and comply with applicable standards.
In the event of blow-out of the internal fuse, a red indicator light on the front panel of
the unit lights up (except for the 150 A nominal unit).
The fuse can be accessed via the rear of the module.
To replace the fuse:
• pull out the module from its baseplate
•unfasten the 2 fuse attachment screws
•fit the suitable fuse (the references of which are given in the
table overleaf).
Tightening torque 3.5 N.m.
451 -461 User Manual 2-7
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Specifications
Model Current
Max
voltage
References
Eurotherm
Suppliers
Ferraz I.R. Brush G.E.0
451
455
461
15 A 240 V
500 V
CH 380 163
CH 110 153
Q 76650
D97063 E1000.15 15 ET
25 A 240 V
500 V
CH 380 253
CH 110 253
R76651
V 82450 E1000.2.5 25 ET GSG 1000.25
40 A 500 V CH 110 044 R82447 E 1000.40 40 ET GSG 1000.40
55 A 500 V CH 110 753 S75893 E1000.75 75 ET
452
456
462
55 A 660 V CH 120 094 A 99958 EE 1000.90 90 EET
75 A 660 V CH 120 114 B99959 EE 1000.110 110 EET GSG1000.110
453
457
463
100 A 660 V CH 120 154 C99960 EE 1000.150 150 EET GSG1000.150
454
458
464
125 A 660 V CH 120 154 C99960 EE 1000.150 150 EET GSG1000.150
150 A 660 V External fuse
CH 340 025 I H300019
Fuse- holder
CP 171 482 I V98711
Warning
•Do not use fuses other than those given in the table
below. Otherwise, we cannot guarantee the protection
of the unit against over-currents.
The guarantee is subject to the use of the high speed
fuses in this table.
•For the use of different high speed fuses, consult
Eurotherm Automation beforehand.
Table 2.4
2-8 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

451 series
Contents page
3.1 Main function performed 3-2
3.2 Coding 3-3
3.3 Terminal identification 3-4
3.4 Wiring diagram 3-5
3.4.1 Power 3-5
3.4.2 Power supply 3-7
3.4.3 Partial load failure detection output 3-8
3.4.4 Logic input 3-8
3.4.5 Multi-input 3-9
3.5 Partial load failure detection setting 3-11
Chapter 3
451 SERIES
SOLID STATE CONTACTORS
451-461 User Manual 3-1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

451 series
Chapter 3. 451 SERIES SOLID STATE CONTACTORS
3.1 MAIN FUNCTION PERFORMED
"ON/OFF" thyristor firing as a function of a logic input signal.
Setting of thyristor firing to zero voltage.
As a option, partial load failure detection.
Application:
Resistive load with low temperature coefficient (low resistance variation).
3-2 451-461 User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

451 series
Model Nominal current
Current
code
451 15 A(500 V max) 081
451 25 A (500 V max) 082
451 40 A (500 V max) 083
451 55 A (500 V max) 062
452 55 A (660 V max) 062
452 75 A (660 V max) 113
453 100 A (660 V max) 114
454 125 A (660 V max) 117
454 150 A (660 V max) * 100
Nominal
voltage
Voltage
code
120 V 10
240 V 13
277 V 32
440 V 28
500 V 29
660 V 30
Fan power supply
(for 453 and 454) *
Code
115 V 11
230 V 36
85-115 V and 200-260 V 41
100-130 V and 200-260 V 19
350-450 V and 200-260 V 43
380-500 V and 200-260 V 47
170-230 V and 200-260 V 42
425-575 V and 200-260 V 44
240-320 V and 200-260 V 46
Options Code
TTL logic input 10
"M ult- in p ut" for single control
of several units connected in
series
24
Partial load failure (PLF)
detection.
Contact open in alarm 37
Partial load failure (PLF)
detection.
Contact closed in alarm 37/83
Unit without baseplate 76
Over-load detection * 68
3.2 CODING
Model / Current code / Voltage code / Fan power supply / Option / 00
*The external fuse mounted on a fuse-holder is the subject of a separate
order under the reference LA 171760
*See page 3-7
*Only with PLF option
451-461 User Manual 3-3