eWON Flexy 205 User manual

Ewon®Flexy 205
INSTALLATION GUIDE
IG-0028-00 1.7 en-US
Publicaon date 01/03/2024
ENGLISH

Important User Informaon
Disclaimer
The informaon in this document is for informaonal purposes only. Please inform HMS Networks of any
inaccuracies or omissions found in this document. HMS Networks disclaims any responsibility or liability for any
errors that may appear in this document.
HMS Networks reserves the right to modify its products in line with its policy of connuous product
development. The informaon in this document shall therefore not be construed as a commitment on the
part of HMS Networks and is subject to change without noce. HMS Networks makes no commitment to update
or keep current the informaon in this document.
The data, examples and illustraons found in this document are included for illustrave purposes and are only
intended to help improve understanding of the funconality and handling of the product. In view of the wide
range of possible applicaons of the product, and because of the many variables and requirements associated
with any parcular implementaon, HMS Networks cannot assume responsibility or liability for actual use
based on the data, examples or illustraons included in this document nor for any damages incurred during
installaon of the product. Those responsible for the use of the product must acquire sucient knowledge in
order to ensure that the product is used correctly in their specic applicaon and that the applicaon meets all
performance and safety requirements including any applicable laws, regulaons, codes and standards. Further,
HMS Networks will under no circumstances assume liability or responsibility for any problems that may arise as
a result from the use of undocumented features or funconal side eects found outside the documented scope
of the product. The eects caused by any direct or indirect use of such aspects of the product are undened and
may include e.g. compability issues and stability issues.

Table of Contents
1. Preface .................................................................................................................................. 1
1.1. About This Document ........................................................................................................ 1
1.2. Document history ............................................................................................................. 1
1.3. Related Documents ........................................................................................................... 1
1.4. Trademark Informaon ...................................................................................................... 1
2. Product Summary .................................................................................................................... 2
2.1. Introducon .................................................................................................................... 2
2.2. Modular Concept of the Ewon® Flexy 205 .............................................................................. 2
2.2.1. Ewon® Flexy 205 ....................................................................................................... 3
2.2.2. Extension Cards Detai ................................................................................................ 3
2.3. Features of the Ewon® Flexy 205 .......................................................................................... 3
2.4. General Specicaon of the Hardware Plaorm ..................................................................... 4
2.5. Typical applicaons ........................................................................................................... 4
2.6. Part Numbers .................................................................................................................. 4
3. Safety, Environmental and Regulatory Information ....................................................................... 5
3.1. Scope ............................................................................................................................. 5
3.2. Power Supply ................................................................................................................... 5
3.3. ESD Damage Prevenon .................................................................................................... 5
3.4. Applicable Direcves, Standards and Compliance ................................................................... 5
3.4.1. Conformity to European Direcves ............................................................................... 5
3.4.2. Applicable Safety Standards ........................................................................................ 6
3.4.3. FCC Compliance ........................................................................................................ 6
3.4.4. Cercaons ............................................................................................................ 6
3.5. Reference Standards for Type Tests ...................................................................................... 6
3.5.1. Mounng Recommendaons ...................................................................................... 6
3.5.2. Earthing .................................................................................................................. 8
3.5.3. Environmental Limits ................................................................................................. 8
3.5.4. Label ...................................................................................................................... 8
3.6. Hazardous Locaons - Class 1 Division 2 ................................................................................ 9
3.7. Internal Baery ............................................................................................................... 11
3.8. Field Implementaon & Environmental Condions ................................................................ 11
3.8.1. Ingress Protecon .................................................................................................... 11
3.8.2. Mounng Recommendaons ..................................................................................... 11
3.8.3. Earthing ................................................................................................................. 13
3.8.4. Environmental Limits ................................................................................................ 13
3.8.5. Labelling Informaon ................................................................................................ 13
4. Hardware Description ............................................................................................................. 14
4.1. Label ............................................................................................................................. 14
4.2. Mechanical Dimensions .................................................................................................... 15
4.3. Physical Interface ............................................................................................................ 16
4.3.1. LED Panel ............................................................................................................... 16
4.3.2. Reset Buon ........................................................................................................... 17
4.3.3. SD Card Slot ............................................................................................................ 17
4.3.4. Main Connector of Ewon® Flexy 205 ............................................................................ 17
4.3.5. Two Slots for Extensions ............................................................................................ 17
4.3.6. LAN / WAN Ethernet ports ......................................................................................... 18
5. Extension Cards ...................................................................................................................... 19
5.1. Slot Compability ............................................................................................................ 21
Ewon® Flexy 205
IG-0028-00 1.7 en-US

5.2. Extension Card Inseron ................................................................................................... 22
5.3. Powering On the Ewon® Flexy 205 with its Extension Cards ..................................................... 23
5.4. Mulple Extension Cards .................................................................................................. 23
5.4.1. Detecon Order ....................................................................................................... 23
5.4.2. Soware Compability of Mulple Cards Combinaon ................................................... 24
5.5. Ethernet Extension Card - FLX 3101 ..................................................................................... 24
6. IP Address & Access to the Web Configuration ............................................................................ 26
6.1. Factory Default IP Sengs ................................................................................................. 26
6.2. Powering On ................................................................................................................... 26
6.3. Connecng to the LAN IP Address ....................................................................................... 26
6.4. Web Interface ................................................................................................................. 27
6.4.1. Detected Cards Displayed in the System Page ................................................................ 27
7. Resetting the Ewon® Flexy 205 .................................................................................................. 28
7.1. Normal Boot Sequence ..................................................................................................... 28
7.2. First Level Reset (User Reset) ............................................................................................. 28
7.3. Second Level Reset (Factory Reset) ..................................................................................... 28
7.4. Reset Impact Matrix ......................................................................................................... 29
Appendix A. Appendix ................................................................................................................ 30
1. Connector Pinout & Related Specicaons ............................................................................. 30
1.1. Main Connector ......................................................................................................... 30
1.2. Specicaon of the External Power Supply ...................................................................... 30
1.3. Digital Output & Digital Inputs ...................................................................................... 31
2. Flexy 205 Products Overview ................................................................................................ 32
2.1. Extension Cards ......................................................................................................... 33
3. Flexy 205 Isolaon Scheme .................................................................................................. 35
3.1. Base Unit .................................................................................................................. 35
3.2. Lisng of Extension Cards ............................................................................................. 36
Ewon® Flexy 205
IG-0028-00 1.7 en-US

1. Preface
1.1. About This Document
1.2. Document history
Version Date Description
1.0 2018-01-12 Ocial release
1.1 2018-11-06 Changed: Flexy 205 label
1.2 2019-01-29 Changed: general review
1.3 2019-08-20 Changed: Safety, Environmental and Regulatory Informaon (page 5)
1.4 2020-01-02 Changed: Digital Output & Digital Inputs (page 31)
1.5 2022-08-02 Changed: product images & logos, adding missing extension cards, update isolaon scheme
1.6 2023-04-17 Changed: Cericaons DK, EIC, UK, ....
1.7 2024-03-01 Added: Hazardous Locaons - Class1 Div2 (page 9) chapter
1.3. Related Documents
Document Author Document ID
Easy Commissioning via SD Card & USB Drive HMS AUG-0062-00
Ebuddy HMS AUG-0063-00
Reference Guide for Ewon® Flexy 205 HMS RG-0008-00
1.4. Trademark Information
Ewon® is a registered trademark of HMS Industrial Networks SA. All other trademarks menoned in this
document are the property of their respecve holders.
Preface Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 1 of 37

2. Product Summary
2.1. Introduction
The Ewon® Flexy 205 is a modular industrial M2M router.
It has been designed to fulll the following key requirements:
• Flexible WAN, allowing within the same product to address dierent Internet connecvity technologies
(Ethernet, Wi-Fi, 4G,…) and securing the investment in case of technology upgrade (eg. 3G > 4G).
• Flexible Field, providing easy connecon to a wide range of external devices, including various eld protocols.
• Flexible Apps, embedding alarms, data logging, remote access, roung and web HMI applicaons with mouse
click based conguraon but also customizaon oering openness and programming tools.
The Ewon® Flexy 205 is fully compable with the Talk2M cloud connecvity services and with the eFive (a VPN
server appliance) for real-me control applicaon.
Figure 1. Housing of the Flexy 205
2.2. Modular Concept of the Ewon® Flexy 205
As the name Ewon® Flexy 205 suggests, it has been designed to enable numerous and various combinaons by
addion of extension cards.
More informaon can be found in the Lisng of Extension Cards (page 36) appendix.
Product Summary Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 2 of 37

Fig. 2 Modular Concept of the Flexy 205
1 Main connector including power input terminals (1 DO and 2 DIs)
2Communicaon interface
3 Placeholder for extension cards
2.2.1. Ewon® Flexy 205
The Ewon® Flexy 205 features:
• 2 DIs and 1 DO.
• 2 free slots allowing the inseron of extension cards.
2.2.2. Extension Cards Detai
The extension cards extend the communicaon features by adding either:
• A WAN communicaon interface (Ethernet WAN, wireless modem, ...)
• A eld communicaon interface (serial, IO card, …)
How the extension cards should be integrated in the Ewon® Flexy 205 is explained in the
Extension Cards (page 19) chapter.
2.3. Features of the Ewon® Flexy 205
The following secon lists the dierent main features supported by the Ewon® Flexy 205.
• Open VPN
• Talk2m connecons
• Data acquision protocols (IO Servers)
• Alarm management and nocaon
• Data logging
• BASIC scripng
• JAVA ETK
• Web server
• ViewON 4 Web HMI
• FTP client and server
• HTTP(S) client (Get & Post requests)
• Ethernet to Serial gateway
•Roung between Ethernet interfaces (WAN to LAN)
•Roung features: IP forwarding, NAT, Port forwarding
Features of the Ewon® Flexy 205 Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 3 of 37

2.4. General Specification of the Hardware Platform
Charactristic Value
Design Industrial design (24 VDC power supply, DIN Rail mounng, extended temperature)
Processor ARM9
Clock Real Time Clock (RTC) with baery backup
Expected lifeme: 10 years
Ethernet Interface 4 congurable LAN/WAN Ethernet ports 10/100 Mbps
Digital Input 2
Digital Output 1
Mounng Latch for DIN rail EN50022 compliant
2.5. Typical applications
Some of the typical applicaons for the Ewon® Flexy 205 are the following ones:
• Remote access of Ethernet, serial and MPI devices
• Industrial VPN router
• Remote monitoring
2.6. Part Numbers
Available Part Numbers
Part Number Type Description
FLEXY20500_00MA Flexy 205 M2M Data Gateway – 4 Ethernet ports
FLEXY20500_00MAH Flexy 205 M2M Data Gateway – 4 Ethernet ports
NOTICE
In the above table, the MA extension stands for Multiple language A (regrouping EN, FR, DE and IT).
The part number syntax is explained in the Label (page 8).
General Specicaon of the Hardware Plaorm Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 4 of 37

3. Safety, Environmental and Regulatory Information
3.1. Scope
The present secon addresses safety, environmental and regulatory informaon for the Ewon® Flexy 205.
This safety, environmental and regulatory informaon generally has a similar compliance frame but some aspects
dier. For example: in the case of telecommunicaon extension cards, addional direcves, standards and
instrucons apply.
3.2. Power Supply
The external power supply is a third party device that is not part of this cercaon. The device shall be powered
by an LPS power supply cered according to its more recent UL/ IEC standards or Class2 per NEC or by a
12-24Vdc 100w max. cered for 60°C and for altudes up to 2000m for conformity to ts more recent UL/IEC
standards.
For more informaon, check the Cercaons secon of our website or refer to
Specicaon of the External Power Supply (page 30).
3.3. ESD Damage Prevention
To avoid possible damage to the base unit and / or extension card, please wait 30 seconds aer switching o the
equipment before inserng (or removing) an extension card.
IMPORTANT
Always use ESD precauons when handling extension cards and / or opened base unit as they
contain parts and assemblies suscepble to be damaged by electrostac discharge (ESD).
The printed circuit boards (PCBs) of the Ewon® Flexy 205 described in the present document are parally exposed
when slot llers are removed to place extension cards. In order to avoid ESD damage, the product, when it is
opened, must be handled with the necessary precauon including:
• Grounded ESD funconal work surface
• Personal grounding
•Vericaon that the conguraon is compable with the rmware capabilies before being operated.
The extension cards described in this document are modules exposing both sides of an electronic printed circuit
board.
Therefore, they are packed in an stac ESD bags. In order to avoid ESD damage, the product must be handled
with the necessary precauon as described above.
3.4. Applicable Directives, Standards and Compliance
The Ewon® Flexy 205 belongs to class A Informaon Technology Equipment (ITE). In a domesc environment, this
product may cause radio interference in which case the user might have to take appropriate measures.
3.4.1. Conformity to European Directives
The Ewon® Flexy 205 and its extension cards are in conformity with the following EC direcves:
Safety, Environmental and Regulatory Informaon Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 5 of 37

• RoHS Direcve 2011/65/EU
• EMC Direcve 2014/30/EU
• RE Direcve 2014/53/EU (1)
(1): When applicable, the product conforms to the corresponding RE Direcve arcles: RF spectrum eciency: Art
3(2); EMC: Art. 3 (1)(b); Safety: Art. (3)(1)(a)
3.4.2. Applicable Safety Standards
The Ewon® Flexy 205 and its extension cards are in conformity with the required safety standards.
These safety documentaon can be downloaded on the Cercaons secon of our Ewon Support website.
3.4.3. FCC Compliance
The Ewon® Flexy 205 and its extension cards comply with Part 15 of the FCC Rules. Operang is subject to the
following two condions:
• This device may not cause harmful interference
• This device must accept any interference received, including interference that may cause undesired operaon.
3.4.4. Certifications
The Ewon® Flexy 205 has been cered by authorized bodies.
These cercates can be downloaded as PDF les on the Cercaons secon of our Ewon Support website.
3.5. Reference Standards for Type Tests
The Ewon Flexy 205 and their extension cards have been fully validated on temperature, vibraon and shock
against the requirements of the following standards:
Operang & Storage Temperature:
Test nature Reference Standard
Cold test IEC 60068-2-1
Dry heat test IEC 60068-2-2
Temperature change test IEC 60068-2-14
Cyclic damp heat test IEC 60068-2-30
Vibraon & Shock Tests:
Test nature Reference Standard
Vibraon test (sinusoidal) IEC 60068-2-6
Vibraon test (broad-band random) IEC 60068-2-64
Shock test IEC60068-2-27
3.5.1. Mounting Recommendations
The product is intended to be mounted vercally, label on the right side.
The normal mounng posion of the Ewon® Flexy 205 is wall mounted on a horizontal
Omega type DIN-rail (EN 50022).
Reference Standards for Type Tests Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 6 of 37

•Mounting the unit on DIN-rail:
Pull the slide lock (located at the boom of the back-side of the unit) downwards and present the unit in front
of the DIN rail. Tilt the Ewon upwards in order to hang it on the upper edge of the DIN rail by its hook. Gently
lt the unit downwards unl it nds its original posion. Pull the slide lock upwards to x and lock the unit on
the DIN rail.
•Removing the unit from DIN-rail:
Release the unit by pulling the slide lock downwards while gently lng the unit upwards.
Free the unit by unhooking it from the upper rail edge.
DIN rail mounting position
# Description
1 DIN rail mounng bracket
Wall mounting position
# Description
1 Wall mounng bracket (suggested screw dimensions 4,2 x 32 mm)
Reference Standards for Type Tests Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 7 of 37

To ensure a proper venlaon of the equipment, a free gap of at least 2 cm must be respected in front of all
upper & lower venlaon openings of the unit.
A free gap of at least 1 cm must be respected on each side of the unit.
Free gap surrounding the Ewon for heat dissipation.
3.5.2. Earthing
Earthing the Ewon is necessary to eliminate unwanted transients and to conform to the EMC
requirements. Therefore, a funconal earth (FE) terminal is available on the main connector as shown in
Specicaon of the External Power Supply (page 30).
Connect this terminal directly to allow impedance ground. Shielded cables have to be used for Ethernet and USB
to comply with the EMC requirements.
3.5.3. Environmental Limits
The equipment will operate properly within the following environmental limits provided it is mounted according
to Mounng Recommendaons (page 6).
Characteristic Value
Operang temperature -25° to +60°C
Storage temperature -40° to +70°C
Relave humidity 10 to 95% non-condensing
Operang altude Up to maximum 2000m
Storage altude Up to maximum 3000m
Mounng Latch for DIN rail EN50022-compliant
3.5.4. Label
The idencaon label of the Ewon® Flexy 205 is placed on the right hand side of the housing. The dierent parts
of the label are described below:
Reference Standards for Type Tests Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 8 of 37

Label Definition
PN Part Number (see syntax in the table below)
SN Serial Number YYWW-SSSS-PP YY = 2 last digits of production year WW = production week number SSSS = Sequential production number
PP = Product Code
MAC MAC address of the Ethernet adapter
Rating Power supply requirements
Marks CE, UL,... logos if applicable
Syntax of the Part Number:
FLEXY12233_44AA [suffix]
Position(s) Description Acce
ptabl
e
value
s
FLEXY Name of the Ewon device model Only Flexy (constant)
1 Single figure
Defines routing capabilities
2 M2M Router
22 Two figures
Defines the type of the motherboard
05 4 configurable LAN/WAN Ethernet ports
33 Two figures
Defines the primary software option
00 No primary software option
44 Two figures
Defines the secondary software option
00 No secondary software option
AA Two capital letters
Defines the firmware language
MA EN + FR + DE + IT
[suffix]= /S Single capital letters
Defines the model type
S This suffix indicates compliance with the UL/IEC/EN 62368-1
standard.
[suffix]= H Single capital letters Defines the model type H This suffix indicates compliance with the UL 121201, 9th Ed.,
and CSA C22.2 NO. 213-17, 3rd Ed., for usage in Hazardous
Locations, Class 1, division 2.
Marks
Marks Description
Conformité Européenne or European Conformity (EC)
UL Recognized - Underwriters Laboraties
Hazardous Locations - Class 1 Division 2 Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 9 of 37

"H" stands for HazLoc (Hazardous Locaons as opposed to OrdLoc - Ordinary Locaon) and refers to Class 1
Division 2 area. The FLEXY20500_00MAH has the same features as the Ewon® Flexy 205 (FLEXY20500_00MA)
except it received official certification to be placed and used in a Class 1 Division 2 area.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D OR non-hazardous locations only.
WARNING
EXPLOSION HAZARD: Do not disconnect while the circuit is live or unless the area is free of ignitable
concentraons.
To ensure a proper venlaon of the equipment, a free gap of at least 2 cm must be respected in front of all
upper and lower venlaon openings of the unit. A free gap of at least 1 cm must be respected on each side of
the unit.
•Where can you place and use the FLEXY20500_00MAH?
The FLEXY20500_00MAH may be used in the yellow area: Class 1, Division 2.
The standard Ewon® Flexy 205, can only be placed and used in the green area: OrdLoc.
WARNING
None of the Ewon® Flexy 205 variant can be placed in the red zone: Class 1, Division 2!
Hazardous Locaons - Class 1 Division 2 Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 10 of 37
3.6. Hazardous Locations - Class 1 Division 2
This chapter concerns the FLEXY20500_00MAH device.

3.7. Internal Battery
The Ewon® Flexy 205 contains a CR2032 baery. This baery is used to maintain the real me clock up-to-date
even when the unit is not powered.
Here is a list of risks and recommendaons regarding the baery:
• Risk of explosion if the baery is replaced by an incorrect type. The baery is not intended to be replaced by
the consumer: the product shall be returned to the manufacturer for replacement.
• Do not ingest baery, chemical burn hazard.
• Keep new and used baeries away from children.
• If the cell baery is swallowed, it can cause several internal burns in just 2 hours and can lead to death.
• If the equipment’s enclosure do not close securely, stop using the product and keep it away from children.
• If you think baeries might have been swallowed or placed inside any part of the body, seek immediate
medical aenon.
IMPORTANT
Risk of explosion if the baery is replaced by an incorrect type. The baery is not intended to be
replaced by the consumer: the product shall be returned to the manufacturer for replacement.
3.8. Field Implementation & Environmental Conditions
3.8.1. Ingress Protection
The Ewon® Flexy 205 has an IP20 protecon grade. Therefore, the Ewon® Flexy 205 is NOT suited for outdoor
mounng.It has to be integrated in an electrical cabinet, protected from excessive heat, humidity and dust. Do
not push any sharp object into the air vents or openings of the equipment.
3.8.2. Mounting Recommendations
The product is intended to be mounted vercally, label on the right side.
The normal mounng posion of the Ewon® Flexy 205 is wall mounted on a horizontal
Omega type DIN-rail (EN 50022).
•Mounting the unit on DIN-rail:
Pull the slide lock (located at the boom of the back-side of the unit) downwards and present the unit in front
of the DIN rail. Tilt the Ewon upwards in order to hang it on the upper edge of the DIN rail by its hook. Gently
lt the unit downwards unl it nds its original posion. Pull the slide lock upwards to x and lock the unit on
the DIN rail.
•Removing the unit from DIN-rail:
Release the unit by pulling the slide lock downwards while gently lng the unit upwards.
Free the unit by unhooking it from the upper rail edge.
Internal BaeryEwon® Flexy 205
IG-0028-00 1.7 en-US Page 11 of 37

DIN rail mounting position
# Description
1 DIN rail mounng bracket
Wall mounting position
# Description
1 Wall mounng bracket (suggested screw dimensions 4,2 x 32 mm)
To ensure a proper venlaon of the equipment, a free gap of at least 2 cm must be respected in front of all
upper & lower venlaon openings of the unit.
A free gap of at least 1 cm must be respected on each side of the unit.
Field Implementaon & Environmental Condions Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 12 of 37

Free gap surrounding the Ewon for heat dissipation.
3.8.3. Earthing
Earthing the Ewon is necessary to eliminate unwanted transients and to conform to the EMC
requirements. Therefore, a funconal earth (FE) terminal is available on the main connector as shown in
Specicaon of the External Power Supply (page 30).
Connect this terminal directly to allow impedance ground. Shielded cables have to be used for Ethernet and USB
to comply with the EMC requirements.
3.8.4. Environmental Limits
The equipment will operate properly within the following environmental limits provided it is mounted according
to Mounng Recommendaons (page 6).
Characteristic Value
Operang temperature -25° to +60°C
Storage temperature -40° to +70°C
Relave humidity 10 to 95% non-condensing
Operang altude Up to maximum 2000m
Storage altude Up to maximum 3000m
Mounng Latch for DIN rail EN50022-compliant
3.8.5. Labelling Information
The OEM User Manual (for integrators) must provide clear instrucons, to the OEM, explaining the labeling
requirements, opons and OEM User Manual instrucons that are required.
The host OEM User Manuel (Ewon's manual) must contain clear instrucons on how end users can nd and/or
access the module and the FCC ID.
Field Implementaon & Environmental Condions Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 13 of 37

4. Hardware Description
4.1. Label
The idencaon label of the Ewon® Flexy 205 is placed on the right hand side of the housing. The dierent parts
of the label are described below:
Label Definition
PN Part Number (see syntax in the table below)
SN Serial Number YYWW-SSSS-PP YY = 2 last digits of producon year WW = producon week number SSSS = Sequenal producon number
PP = Product Code
MAC MAC address of the Ethernet adapter
Rating Power supply requirements
Marks CE, UL,... logos if applicable
Syntax of the Part Number:
FLEXY12233_44AA [suffix]
Position(s) Description Acce
ptabl
e
value
s
FLEXY Name of the Ewon device model Only Flexy (constant)
1 Single gure
Denes roung capabilies
2 M2M Router
22 Two gures
Denes the type of the motherboard
05 4 congurable LAN/WAN Ethernet ports
33 Two gures
Denes the primary soware opon
00 No primary soware opon
44 Two gures
Denes the secondary soware opon
00 No secondary soware opon
AA Two capital leers
Denes the rmware language
MA EN + FR + DE + IT
[sux]= /S Single capital leers
Denes the model type
S This sux indicates compliance with the UL/IEC/EN 62368-1
standard.
[sux]= H Single capital leers Denes the model type H This sux indicates compliance with the UL 121201, 9th Ed.,
and CSA C22.2 NO. 213-17, 3rd Ed., for usage in Hazardous
Locaons, Class 1, division 2.
Hardware Descripon Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 14 of 37

Marks
Marks Description
Conformité Européenne or European Conformity (EC)
UL Recognized - Underwriters Laboraes
4.2. Mechanical Dimensions
Figure 2. Mechanical Dimensions
In the above picture:
•Unit: Dimensions are in millimeters (mm).
•Accuracy: Suited only for implementaon drawings (rounded @ full mm).
Shaded areas show provisions of empty space that should be considered in the implementaon arrangement.
The provision of empty space in front of the slot llers is spared for the connectors of extension cards. Even if the
applicaon requires no extension card(s), it is good pracce to plan the free space anyhow, in case an extension
card is inserted later on.
Mechanical Dimensions Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 15 of 37

4.3. Physical Interface
This secon addresses the interface that represents the Ewon® Flexy 205. The items numbered in the image
below are explained subsequently in separate paragraphs.
Figure 3. Base Unit Interface
1LED panel.
2RESET buon - BI1.
3SD card slot.
4Main connector.
Used to connect the power supply and the digital I/O.
52 slots llers.
Can be removed and replaced by extension cards.
6Main board communicaon interfaces: 4 Ethernet Ports.
4.3.1. LED Panel
The LED panel displays the system status and is located boom to the 4 Ethernet ports. The following table
explains the common LEDs of all base units.
Physical Interface Ewon® Flexy 205
IG-0028-00 1.7 en-US Page 16 of 37
Other manuals for Flexy 205
2
Table of contents
Other eWON Gateway manuals
Popular Gateway manuals by other brands

Inovonics
Inovonics EN7380 Installation and operation manual

ECKELMANN
ECKELMANN LAN Gateway Operating instruction

THOMSON
THOMSON TCW770 user manual

RTA
RTA 460BSUS-NNA4 Product user guide

IEI Technology
IEI Technology DRPC-230-ULT5 Series user manual

Grandstream Networks
Grandstream Networks GXW-410x user manual