Fancom Aura 14 User manual

g

N.B.: The original, authentic version of this manual is the English version produced by Fancom B.V. or one of its
daughter companies (referred to further as Fancom). Any modifications introduced to this manual by third parties
have neither been checked nor approved by Fancom. Modifications are taken by Fancom to include translations
into languages other than English and the insertion and/or deletion of text and/or illustrations to/from the original
contents. Fancom cannot be held liable for any damages, injury, guarantee claims and other claims relating to this
type of modification, in as far as these modifications result in a content that differs from the original English
version of this manual produced by Fancom. For the latest information about product installation and operation,
please contact the customer service dept. and/or the technical service dept. of the Fancom concerned. In spite of
the care taken when compiling this manual, if you should discover any errors, please inform Fancom B.V. in
writing. Fancom B.V., PO Box 7131, 5980 AC Panningen (the Netherlands).
Copyright © 2018 Fancom B.V.
Panningen (the Netherlands)
All rights reserved. Nothing from this manual may be copied, distributed or translated into other languages, partly
or wholly, without express prior written permission from Fancom. Fancom reserves the right to modify this manual
without notice. Fancom can give no guarantee, neither implicit nor explicit, for this manual. All risks are for the
user.
This manual has been compiled with the utmost care. If, however, you should discover an error, please inform
Fancom B.V.
Art.Nr. 5911936
GB180406

Aura 14
Table of contents
i
1. General introduction .................................................................................................................................. 1
1.1 Documentation with the control computer....................................................................................... 1
1.2 How to use this manual .................................................................................................................. 1
1.3 Fancom Sales & Service Center..................................................................................................... 1
1.4 Safety instructions and warnings.................................................................................................... 2
2. Aura 14 ........................................................................................................................................................ 3
3. Using the Aura 14....................................................................................................................................... 4
3.1 Main parts....................................................................................................................................... 4
3.2 Working with the Aura .................................................................................................................... 4
4. User settings............................................................................................................................................... 5
4.1 Daily management.......................................................................................................................... 5
4.2 Setting the curves........................................................................................................................... 7
4.3 Min max.......................................................................................................................................... 9
5. Alarm ......................................................................................................................................................... 10
5.1 Alarm overview............................................................................................................................. 10
5.2 Setting alarms............................................................................................................................... 13
6. Installing the Aura 14 ............................................................................................................................... 15
6.1 Determine location........................................................................................................................ 15
6.2 Mount the Aura 14........................................................................................................................ 15
6.3 Connect the Aura 14..................................................................................................................... 16
6.4 Connect the Aura 14 to FNet........................................................................................................ 17
7. Installer settings....................................................................................................................................... 18
7.1 Overview....................................................................................................................................... 18
7.2 CFG.............................................................................................................................................. 20
7.3 SYS .............................................................................................................................................. 21
7.4 INS ............................................................................................................................................... 24
7.5 ANA.............................................................................................................................................. 26
7.6 REL .............................................................................................................................................. 29
7.7 NAT .............................................................................................................................................. 32
8. Appendix: System connection settings.................................................................................................. 33
9. Appendix: Connection diagram Aura 14 ................................................................................................ 34
9.1 Powerboard FCA.......................................................................................................................... 34
9.2 Trix board T-5............................................................................................................................... 35
9.3 Trix board T-10............................................................................................................................. 36
10. Appendix: Connection diagram for alarm .............................................................................................. 37
10.1 Single alarm-unit........................................................................................................................... 37
10.2 Multiple alarm-units ...................................................................................................................... 37
11. Technical specifications .......................................................................................................................... 38
11.1 Interior control computer............................................................................................................... 39
11.2 Interior control computer T6.......................................................................................................... 39
11.3 Aura board.................................................................................................................................... 40
12. Appendix: EG-declaration of compliance............................................................................................... 41

Aura 14
General introduction
1
This manual has been created with the utmost care. If, however, you should discover an error, please inform
Fancom B.V..
The documentation consists of the following manuals:
Manual
This manual supplies information about connecting and configuring the control computer and information
about working with the control computer after installation. Always keep the manual close to the control
computer.
Climate manual
This manual supplies information about the basic climate principles (the manual is available on the Fancom
extranet and it can be ordered separately).
The following symbols are used in this manual:
Tips and suggestions.
Note providing recommendations and additional information.
Warning indicating damage to the product if you do not follow procedures carefully.
Warning indicating danger to humans or animals.
Electrical shock hazard. Danger to humans and animals.
Example of a practical application of the described functionality.
Calculation example.
Describes the key combinations for arriving at a particular screen.
Decimals
The control computer and this manual use a decimal point in values. For example: a weight is shown as 1.5 kg
(not as 1,5 kg).
For any questions and support, please contact the local Fancom Sales & Service Center.

Aura 14
General introduction
2
Before installing and commissioning the Aura 14, read the safety instructions, provisions and conditions carefully.
This paragraph contains a number of general safety instructions. The installation of the device and remedying of
any malfunctions should be performed by a certified electrical installer according to the applicable norms. The
guarantee does not apply if this product is installed in any other way than is indicated by Fancom and if the
product's motor has been opened and changes have been made to the product.
Disconnect power before installation or before carrying out any maintenance to the control computer.
You must be able to switch off the device using a bipolar main switch.
Take precautions against electrostatic discharge (ESD) when working on the control computer. Ensure
the workplace is clean and dry.
Use the wiring/cables indicated on the connection diagrams and follow all. Only apply power after the
wiring has been connected correctly. Incorrect connections can cause permanent damage. Before a
new fuse is placed, the cause of the defect should be remedied by an authorized installer. Only replace
a defective fuse by a fuse of the same type (see connection diagram).
Inspect the control computer regularly for any damage. Report any damage to your installer
immediately. A damaged control computer is dangerous! Do not use running water (high pressure
cleaners) to clean your control computer. The control computer is water resistant, but not waterproof!
Do not switch off the computer when houses are unoccupied; otherwise there is the risk of
condensation in the computer.
The installation, of which this product is a part, must be equipped with a reliable, independent alarm
system, for example, a minimum/maximum thermostat. We advise you to test the alarm system every
day for proper functioning.
If the product is part of a climate control system, the oxygen levels in the areas being controlled must
always be maintained under all circumstances - even in emergency situations. We advise you to use an
emergency system (emergency power supply unit, emergency opening systems, option for manual
operation) to guarantee the oxygen levels. This system must be regularly tested for proper functioning.
The control computer is a piece of electronic apparatus. There is always a risk of a malfunction
occurring. Fancom has made every effort to ensure that an alarm is given in the event of an emergency.
Unfortunately, a 100% guaranteed cannot be provided as not all circumstances are under Fancom
control. Fancom cannot be held liable for any damage caused by incorrect settings and/or non or partial
functioning of the entire installation. Ask your installer if the alarm outputs of each control computer
have been connected to a separate alarm circuit.
Connect each Fancom device according to the applicable legislation/regulations of the local energy
provider.
Check that the mains voltage and frequency, for which this computer is suitable, correspond to the
mains voltage and frequency on site.
Low-voltage and high-voltage wires may not be placed parallel to each other but may cross each other.
When using metal ducts, Fancom advises grounding the ducts at the ends and at as many other places
as possible.
Connect the computers to one group, from the main distributor.
Keep signal and power cables as short as possible.

Aura 14
Aura 14
3
The Aura 14 controller is used for climate control in the agricultural sector. It regulates ventilation and heating for
one section. The Aura 14 can be used with various ventilation systems:
ProFlow
NatuFlow
EasyFlow
CentralFlow
Triac control with or without vortex damper
Analog control with or without vortex damper
Air inlet control
Activating fans (combi-control)

Aura 14
Using the Aura 14
4
This chapter describes the main parts and the operation of the Aura 14.
The Aura 14 can be operated on the touch screen.
1. Touch screen
The Aura 14 screens are divided in three sections:
1. Title bar: Displays the name of the selected screen (e.g. Overview), the actual day number (based on the
curve), the date and time and provides access to right fly-over menu (installation and user menu).
2. Working area: Displays the data of user or installation settings of the control computer.
3. Menu selection and alarm bar: Provides buttons to navigate through available menus (e.g. curve) and an
alarm indicator to navigate to more details.

Aura 14
User settings
5
With daily management you can set the temperature and ventilation settings manually. If a curve is used, the daily
management overwrites the settings temporary.
The left dial displays the actual temperature. The right dial displays the actual ventilation. In both dials the actual
control value is displayed as a red marker. The highlighted green area displays the lower boundary comfort zone
(related to setpoint heating) and the upper boundary comfort zone (related to max diff alarm). The actual status
will light up:
: Heating active
: Thermal control (used as cooling)
: Number of additional fans in use
Use the dials as follows:
1. Tap the dial you want to set. A pop up of the dial appears:
2. Set the value by tapping :
Tap to increase or decrease the value step by step.
Hold the to quickly increase or decrease the value.
3. Tap to confirm or to cancel all the settings in the popup window.

Aura 14
User settings
6
The heating control ensures it does not become too cold in the section. If the temperature drops below the set
value, the computer will make a correction.
Dial 1
Setting the setpoint heating.
Setting the minimum ventilation temperature.
Setting the maximum ventilation temperature.
Setting the setpoint cooling.
The ventilation control ensures there is always a settable minimum amount of fresh air. If the temperature in the
house becomes too high, the controller will provide extra ventilation.
Dial 2
Setting of the minimum ventilation.
Setting of the maximum ventilation.
Readout of the ventilation status.

Aura 14
User settings
7
Dial 2
Readout of the control value (left) and a readout of the actual ventilation.
Readout of the actual position of the vortex damper.
Readout of the actual position of the air inlet.
Readout of the active additional fans.
There are 10 bending points. At a bending point start by entering the day number; the settings at this bending
point apply to this day number.
Readout of the bending points of the curve (maximum 10).
Setting of the day on which the new curve values must apply.
Setting of the curve value for setpoint heating.

Aura 14
User settings
8
Setting of the curve value for start temperature ventilation.
Setting of the curve value for setpoint thermal control.
The day number is a counter increased by the controller each day at midnight by one up to a maximum
of 999. If the day number is 0 it will not change. The Aura 14 then controls without the curve, even if the
bending points have been set.
If a curve is used, the day number is the basis used to calculate the setpoints from the relevant curve. If
a negative day number is set, the Aura 14 will control without using the curve, until the day number is a
positive number. A negative day number is also increased at midnight by one, except the jump from day
–1 to day +1 (a jump of 2).
There are 10 bending points. At a bending point start by entering the day number; the settings at this bending
point apply to this day number.
Readout of the bending points of the curve (maximum 10).
Setting of the day on which the new curve values must apply.
Setting of the curve value (%) for minimum ventilation.
Setting of the curve value (%) for maximum ventilation.

Aura 14
User settings
9
Readout of the highest, actual and lowest measured temperatures of the section.
Followed by the time of measurement.
Readout of the highest, actual and lowest measured temperatures of the extra
temperature sensor. Followed by the time of measurement.
Readout of the highest, actual and lowest measured temperatures of the thermal
temperature control. Followed by the time of measurement.
Readout of the highest, actual and lowest measured temperatures of the outside
temperature. Followed by the time of measurement.
The highest and lowest temperatures are measured in the last 24 hours.

Aura 14
Alarm
10
Request the alarm overview using the alarm button .
There are two buttons:
1. Alarm overview to readout the status.
2. Alarm settings to change the alarm settings.
Types of alarm
There are two types of alarm:
1. LOUD: A loud alarm means a report is shown on the screen and a siren is sounded (if connected). Take
action immediately.
2. SILENT: With a silent alarm (warning), a report will appear on the screen. This type of alarm is usually less
serious. An active process can be stopped, if required.
With both types an alarm message will appear on the screen.
Alarms can be set to LOUD or SILENT, if required. For nearly all the alarms the user decides the limits outside
which alarms must be given.
Status
Readout / setting the alarm status:
Alarm stand by: no alarm (stand by mode).
Alarm test: test the alarm and after reset the status will be changed to Alarm
stand by.
Alarm recovered: there was an alarm which has been recovered. The controller
switches off the alarm, but the alarm status remains visible.
Silent alarm: alarm message shown on display only.
Alarm temp. off: switch off the current alarm. When the alarm situation has been
cancelled, this status will automatically become Alarm stand by. Always check
that the status has reverted to Alarm stand by.
Alarm disabled: switch off the alarm entirely. Only do this when houses are
unoccupied. Do not forget to reset the status to Alarm stand by.
Alarm: the type of alarm is shown on the display.
-: function not in use.

Aura 14
Alarm
11
Message
Readout of the alarms (see table below).
Temperature alarms
Alarm
Action
Min.room temp. (abs)
Max.room temp. (abs)
Min.room temp. (dif)
Max.room temp. (dif)
Roomtemp. failure
Min.extra temp.(dif)
Max.extra temp.(abs)
Max.extra temp.(dif)
Extra temp. failure
Therm.temp. failure
Min.therm.temp.(dif)
Max.therm.temp.(abs)
Max.therm.temp.(dif)
Minimum alarm
Check wiring and sensors.
Check if the heater works properly (if available).
Check minimum difference alarm settings.
Maximum alarm
Check wiring and sensors.
Check if the cooling works correctly (if available).
Check maximum difference alarm settings.
Check absolute maximum alarm settings.
Ventilation alarms
Alarm
Action
Minimum DSR
Check the vortex damper, fans or central exhaust.
Maximum DSR
DSR failure
Check wiring and DSR sensor.
If the fan or airflow transmitter uses DSR feedback, the control
computer continually checks the DSR.
System alarms
Alarm
Action
Backup alarm
The control computer will be active on factory settings. Please check the
settings.
Watchdog alarm
Communication alarm
Setting changed
Stack overflow
Communication assignment
EPROM error
RAM error
The control computer also tests a number of functions of the
control computer itself. Always warn the installer if a system
alarm occurs.

Aura 14
Alarm
12
If the value responsible for causing the alarm comes within the alarm limits again, the situation is
considered recovered and the alarm is no longer active. The siren automatically disables and the alarm
status changes into Alarm recovered. This message remains visible so you can see what caused the
alarm. Press to change the alarm status into Alarm temp. off followed by Alarm stand by.
If an alarm occurs the LED strip and the ‘menu selection and alarm bar’ will flash red. Perform the following
actions in case of a:
1. Press . The alarm overview displays the alarm status Alarm and shows the alarm message.
2. Press once more. The siren will temporarily go off and the alarm status changes to Alarm temp. off. The
alarm message remains visible to investigate what caused the problem.
3. Solve the alarm situation. When the alarm situation is solved the alarm status changes into Alarm stand by.
1. Press . The alarm overview displays the alarm status Alarm and shows the alarm message.
2. Solve the alarm situation.
3. Press once more. The alarm message will disappear and the alarm status changes into Alarm temp. off
followed by Alarm stand by.
If the alarm is disabled the control computer will not generate any alarm messages (except system
alarms). Never switch the alarm off during regular operation.
The alarm can be fully disabled, e.g. when the house is empty. Disable the alarm as follows:
1. Press .
2. Change the alarm status to Alarm disabled. The control computer will give a warning to indicate that the
entire alarm system has been disabled and will flash red.
Reactivate the alarm by changing the alarm status to Alarm stand by. The alarm message states that the alarm
has been disabled and is active again. The message will be cleared from the alarm overview.
Fancom advises testing the alarm weekly for correct functioning. During the test the control computer
will give a loud alarm.
Test the alarm as follows:
1. Press .
2. Change the alarm status to Alarm test. The LED strip and the ‘menu selection and alarm bar’ will flash red
and the control computer prepares an alarm message. The Alarm overview displays the alarm message.
3. Clear the alarm by pressing . The alarm status changes into Alarm stand by.

Aura 14
Alarm
13
Abs. Maximum alarm
If the house temperature is higher than the set Abs. maximum alarm, the control
computer will give a maximum temperature alarm.
Max. difference alarm
The control computer gives a maximum temperature difference alarm if the house
temperature is above: Calculated Start temperature ventilation + Calculated
bandwidth + Max. difference alarm or Setpoint thermal control + Max. difference
alarm.
Calc. start temp. ventilation
20ºC
Calculated bandwith
4ºC
Ventilation is maximum at
24ºC
Setpoint therm. ctrl
24ºC
Max. difference alarm
3ºC
Max. difference alarm
3ºC
Calculated alarm limit
27ºC
Calc. alarm limit
27ºC
An alarm will occur if a temperature becomes higher than the maximum
alarm limit: 20 + 4 + 3 = 27°C.
On hot summer days the temperature in a section can be very high. This
can result in a maximum alarm or the difference alarm will have to be set
high. This is not desirable with lower temperatures; the maximum alarm
limit would then be unnecessarily high. In order to provide effective alarms
(max. difference alarm as small as possible) the computer increases the
alarm limit parallel to the outside temperature, as soon as this is higher than
the point at which ventilation is maximum.
Calc. start temp. ventilation:
20ºC
Calculated bandwith:
4ºC
Ventilation is maximum at:
24ºC
Setpoint therm. ctrl:
24ºC
Outside temperature:
25ºC
Max. difference alarm:
3ºC
Max. difference alarm:
3ºC
Calculated alarm limit:
28ºC
Calc. alarm limit:
27ºC
An alarm will occur if a temperature becomes higher than the maximum
alarm limit: 25 + 3 = 28°C.

Aura 14
Alarm
14
Calc. start temp. ventilation:
20ºC
Calculated bandwith:
4ºC
Ventilation is maximum at:
24ºC
Setpoint therm. ctrl:
24ºC
Outside temperature:
25ºC
Max. difference alarm:
3ºC
Max. difference alarm:
3ºC
Calculated alarm limit:
27ºC
Calc. alarm limit:
27ºC
Absolute maximum alarm:
26ºC
An alarm will occur if a temperature becomes higher than the maximum
alarm limit: 24 + 3 = 27°C. The maximum alarm is however limited by the
absolute maximum alarm to 26°C.
Min. difference alarm
The control computer gives a minimum temperature difference alarm if the house
temperature is below: Setpoint heating or Setpoint thermal control - Min. difference
alarm.
Start temperature ventilation:
20ºC
Min. difference alarm:
4ºC
Calc. min. alarm limit:
16ºC
An alarm will occur if the temperature becomes lower than 16ºC.
Alarm switch-on time
Setting of the time length (hours and minutes) after which the control computer can
give an alarm. During this period of time the control computer cannot give an alarm
e.g. to prevent an alarm is giving during the warming up period.
Warming up the section. A section has to be warmed up from 10ºC to
20ºC. This should take approximately five hours. Set the temperature
required and the time to 05:00 hours. After five hours, when the section
should have reached the correct temperature, the alarm will automatically
become active.
Large temperature jump in a farrowing pen. In a farrowing pen the
temperature has to increase from 19ºC to 24ºC. This should take about two
hours, so the time is set to 02:00.
Temperature sensor faulty
Measurements from connected sensors (except the outside sensor) are reliable as long as measurements are
between -99.9ºC and +99.9ºC. Outside these limits, the measurements are unreliable. The control computer will
give an alarm. This can mean that the temperature sensor has not been correctly connected or is defective. The
screen displays # at the temperature readout.

Aura 14
Installing the Aura 14
15
1. Determine location
2. Mount the Aura 14
3. Connect the Aura 14
Takes into account the following guidelines:
Figure 1: required edge distances
Never place the Aura 14 in a place where the weather has direct influence (not in the sun, not in places
where the temperature can rise sharply etc.).
Never mount the Aura 14 near water pipes, drainage pipes etc.
Never mount the Aura 14 in a humid and/or dusty room and certainly not in the room where the animals
are present.
Mount the Aura 14 at such a height that you can control the Aura 14 easily (eye level) and square on a
solid backing. The swivels should be positioned at the bottom.
Mount the Aura 14 as follows:
1. Mark the screw holes by using the drilling template (taking into account the required edge distances).
2. Open the cover and fasten the control computer in the mounting holes on the corners.

Aura 14
Installing the Aura 14
16
Connect the Aura 14 as follows:
1. Open the cover.
2. Connect the Aura 14 to the manual switch.
3. Connect the manual switch to the main supply (be sure power is disconnected).
4. Connect other (signal wires) to the Aura 14, see chapter Technical specifications.
5. Close the cover.
Always use the cable swivels when connecting the Aura 14. Use the sealing discs supplied to seal off
any unused swivels. Use a sealant to seal all swivels, after the computer has been connected, to
prevent the entry of moisture, dust and/or aggressive gasses.
Check that the mains voltage and frequency, for which this computer is suitable, correspond to the
mains voltage and frequency on site.
Be sure that the Aura 14 is properly grounded. When using metal cable trays, grounding at one point of
the tray is recommended.
The Aura 14 should be possible to shut down with a double pole switch.
Connect the Aura 14 to a group from the main distributor and mount in separate cable trays.
Limit the length of the signal wires much as possible; avoid crossing high/low voltage wires.
To protect against lightning, place an over voltage protection device in the power supply of the Aura 14.
Condensation should never occur in the control computer.

Aura 14
Installing the Aura 14
17
Use of the terminal resistor depends on the location of the control computer in FNet. Control computers or end
stations at the beginning of the network require a terminal resistor. Depending on the device type a 120 Ohm
resistance, a jumper or a dipswitch is used to terminate the control computer.
Example: Setting the terminal resistor FNet
Four control computers connected using FNet.
Control computers 1 and 4 are at the end of the network. These control computers must be terminated.
Control computers 2 and 3 are looped. These looped control computers do not require a terminal
resistor.
The Fancom Greenlink cable (UTP 1x2x0.8mm, unshielded twisted pair) used to wire the FNET and I/O
net. Maximum cable length = 1200 meters.
Table of contents
Other Fancom Controllers manuals
Popular Controllers manuals by other brands

OLYS
OLYS MPPT5010 user manual

Avlite
Avlite AV-OL-CTRL-T3 Installation & service manual

FASTRON.
FASTRON. FTM1 Series user manual

Munters
Munters Farm Center Pro Manual for use and maintenance

Munters
Munters BA1701 instruction manual

fluidra
fluidra Astral Pool SLX Light Connect Lite installation instructions