TECHNICAL FEATURES
Sicurgas
OPERATION
ATTENTION! in case of alarm:
1. put out all naked flames;
2. close the valve of the gas contactor or of the LPG cylinder;
3. do not switch lights on or off; do not switch on electrically powered appliances or devices;
4. open doors and windows to enhance ventilation of the environment;
5. do not use telephones in the room where gas has been detected.
When the alarm ceases, find the cause which triggered the alarm and act accordingly.
If the alarm continues and the cause of the gas leak cannot be identified or eliminated, abandon the
premises and notify emergency services from outside.
SOME OF THE MOST COMMON SUBSTANCES WHICH CAN TRIGGER A FALSE ALARM:
wine, liquor, alcohol, deodorants, stain removers, paint thinners, hair spray, excessive water steam.
Sicurgas also allows you to set the
type of acoustic alarm, see figure
to the side
7MAINTENANCE AND CLEANING
Pay attention to extreme temperature or humidity values.
The detector must always be on to provide the maximum safety.
Have authorised technicians perform routine, extraordinary maintenance and decommission the
appliance.
Regularly check its correct operation by means of the specific button or a test gas.
OTHER TEST METHODS COULD DAMAGE THE APPLIANCE.
If the catalyst sensor is exposed to gas concentrations higher than the LEL for a few minutes, it could lose
sensitivity.
Clean the appliance using a soft cloth without detergents or solvents.
Type A appliance.
Case in shock-proof insulating material.
Degree of protection IP42.
Operating environment temperature/humidity:
from -10 to 40°C, max. 90 RH%.
Power supply 230Vac 50Hz.
Consumption 4 VA.
Range of pre-alarm relay contacts 1(1)A 250Vac
Range of alarm relay contacts 6(2)A 250Vac
Maximum power of solenoid valve controlled by alarm
relay: 450VA at 230Vac 50Hz
Relays sealed to avoid sparks when switching.
Jumper to select operating mode of relay, stable or
by pulses.
Catalyst sensor for gas detection.
Internal luminous and acoustic alarms.
Volumetric value of triggering threshold:
(% LEL) 6-9% for natural gas.
(% LEL) 7-10% for LPG.
In compliance with the standard EN 50194.
INTERMITTENT RINGING
jumper JP3
up (A)
CONTINUOUS RINGING
jumperJP3
down (B)
goes back to the non-alarm position and the red and yellow LEDs flash alternately indicating the silencing
period. If you press the switch again during these 10 minutes, the detector immediately resumes normal
operation.
When the 10 minutes elapse, the detector automatically resumes normal operation.
Therefore when you know that you must use substances which could trigger a false alarm, you may silence
the detector beforehand to avoid alarms and switching off of the gas stove (due to triggering of the gas
shut-off valve).