
17
6. Commissioning
6.1
6.2
6.3
6.4
6.5
Preliminary inspections
First start-up or restart after long inactivity
Shut-down
Flow rate calibration
Flow rate balance
6.1 Preliminary inspections
6.1.1 Electrical
• Verify that the voltage on terminals L1, L2 and L3 is that shown on the plate of the unit
(tolerance allowed) ±5%, which can be checked with a tester. If voltage changes occur
frequently, please contact our technical department to choose suitable protections.
• Verify the complete tightness of the fuse holder caps.
• Verify that the crankcase heaters (if applicable) are powered correctly: to check whether the
heaters are working properly, check that the bottom of the compressor is at a temperature of
10 to 15 °C higher than the ambient temperature.
• Power and check the correct direction of rotation for the three-phase version, which should be
clockwise looking at the motor from the fan side. Otherwise, invert any two of the phase
conductors.
6.1.2 Hydraulic
• Make sure that the water circuit has been previously cleaned: it is recommended to wash the
water circuit via by-passing the unit and then check the cleanliness of the system filter.
• The machines are shipped with open vents and drains, which must be closed during
installation when filling the water circuit. Labels indicate their positions.
• Make sure that the hydraulic system has been bled, thereby eliminating any residual air. The
operation must be performed by loading gradually and opening the venting devices set up by
the installer in the upper part of the system.
• If you are using glycol water you can move the antifreeze set-point. The value must be equal
to the value of the freezing temperature of the fluid plus 6K.
6.1.3 Cooling
• Check that there is no refrigerant leak, possibly using a leak detector.
6.2 First start-up or restart after long inactivity
6.2.1 Start-up
Activate the machine according to that described in the relative command section.
6.2.1.1 Checks during operation
• Check that the machine does not generate abnormal noise or excessive vibrations.
• After a few hours of operation verify that the crown of the liquid and humidity indicator
indicates a dry circuit.
• Verify that the machine operates within the optimum working range.
• Verify that there is no excessive presence of bubbles in the liquid indicator. If there are this
indicates low refrigerant.
• A few minutes after the compressors are started, during the summer mode cycle, make sure
that the condensing temperature is 18±4K higher than the air temperature entering the
condenser and that the average evaporating temperature is approximately 5K lower than the
water temperature leaving the utility exchanger.
• Verify that the overheating temperature of the refrigerant is between 5 and 7K. To verify:
- Measure the temperature with a contact thermometer placed on the intake pipe of the
condenser .
- Read the temperature indicated on the pressure gauge connected to the inlet.
- The difference between these temperatures provides the overheating value.
• Verify that the subcooling temperature of the refrigerant is between 4 and 8K. To verify:
- Measure the temperature with a contact thermometer placed on the outlet pipe from the
condenser.
- Read the temperature indicated on a pressure gauge connected to the liquid outlet of the
condenser.
- The difference between these temperatures provides the subcooling value.
6.3 Shut-down
6.3.1 Temporary shut-down
Disable the machine according to that described in the relative command section.
Do not disconnect the power supply by acting on the disconnecting switch on board the
machine or the main switch of the system. If there is no voltage, the crankcase heaters and
the antifreeze heaters cannot work, thereby, posing a risk of freezing.
The antifreeze protection function is only active if the unit is in “STAND-BY” mode. In case
of operation, the unit controls pump start-up.
To safeguard the system and the units, we recommend installing an electrical heater on
the connection pipes, or to fully empty the system.
The pump must be installed and supplied by the user. We recommend keeping the pump
supplied even during periods of prolonged system inactivity to enable proper operation of
the antifreeze function.
6.3.2 shutting down for long periods;
Not using the unit for a long period of time requires the following operations to be performed:
• Disable the unit in any mode of operation it may be, from the control panel.
• Set the remote switch to "OFF" (if present) after having turned off the unit.
• Disable the internal terminal units by setting the switch of each unit to "off".
• Set the main switch of the system to ''off''.
• Close the water valves.
If, during the period of inactivity the temperature drops below zero, the system must be
fully empties or topped up with antifreeze liquid.
6.4 Flow rate calibration
Once the pump has started, verify that the fluid flow rate of the utilities is within the expected
values for the unit.
To verify:
• Use pressure gauges set before and after the circulating pump to measure the pressure
difference.
• Verify that the pressure difference measured is equal to the pressure drop in the system,
including the heat exchanger.
To correct:
• Turn the valve installed downstream of the pump to increase or decrease the pressure
difference.
• Mark the position of each valve to reposition it in the same position after closing for
maintenance operations.
If there are no pressure gauges:
• Verify the temperature difference between the utility fluid input and output when the unit is
operating regularly (all compressors on).
• The difference in water temperature between input and output must be between 4° and 6°C: