Specifications
Minimum Device Requirement:
BLE 4.0 devices running iOS® 7.0 or Android™ 5.0
(Latest compatibility at www.fieldpiece.com)
Battery Type: 2 x AAA, NEDA 24A, IEC LR03
Battery Life: 150 hours typical alkaline. LED blinks red when
battery replacement is needed.
Auto Power Off: 2 hours (APO can be disabled)
Wireless Range: 350 feet (107 meters) line of sight.
Obstructions affect distance.
Radio Frequency: 2.4 GHz
Operating Environment: 32°F to 122°F (0°C to 50°C) at <75% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH
(with batteries removed)
Temperature Coefficient: 0.1 x (specified accuracy) per 1.8°F
(32°F to 64°F, 82°F to 122°F), per 1°C (0°C to 18°C, 28°C to 50°C)
Weight: 0.33 lbs (150 g)
Flexible Probe: 0.36" (9mm) diameter; 9.25" (235mm) length
US Patent: www.fieldpiece.com/patents
Relative Humidity (%RH)
Sensor Type: Capacitance polymer film
Hysteresis: ±1%RH typical (Excursion of 10% to 90% to 10%RH)
Measurement Range: 0%RH to 100%RH
Accuracy: (At 73.4°F (23°C))
±2.5% (10%RH to 90%RH); ±(5%) <10%RH, >90%RH
Response Time: 60 seconds typical for 90% of total range
Temperature
Sensor Type: Precision thermistor
Measurement Range: -4°F to 140°F (-20°C to 60°C)
Accuracy: ±(1°F) 32°F to 113°F, ±(0.5°C) 0°C to 45°C;
±(2°F) -4°F to 32°F, 113°F to 140°F, ±(1°C) -20°C to 0°C, 45°C to 60°C
Quick Start
1 Install the Fieldpiece Job Link® system app on
yourmobile deviceandsignup foran account
if you're a new user.
2 Removethesinglescrewof the yellowbattery
cover and install 2 x AAA batteries.
3 Press for 1 second to power on.
4 OpenMeasurementsin the Job Link® app and
favorite the probe to the tool manager.
5 Remove protective slip cover from tip.
6 Viewlivemeasurementsonyourmobiledevice
up to 350 feet away.
What's Included
Job Link® System Flex Psychrometer Probe
1 Protective Slip Cover
2 x AAA Batteries
Operator's Manual
1 Year Limited Warranty
Description
The JL3RH Job Link® System Flex Psychrometer
Probe sends air measurements directly to the
Fieldpiece Job Link® app up to 350' away.
Measure %RH, dry bulb, wet bulb, dew point,
and enthalpy at a register/grille, in the duct, or
just walking around. Bend the flexible probe and
slide the magnet to conveniently configure the
JL3RH to your situation.
The rubberized protective housing is both
ergonomic and rugged for daily use. Flip the
switch and app immediately knows which
side of the system you're going to place your
psychrometer probe.
Use the long wireless range, strong
magnet, and flexible probe for quick and easy
psychrometrics testing.
Maintenance
CLEANING: Clean the exterior with a damp
cloth. Do not use detergents or solvents. Do not
touch the sensor.
BATTERIES: When the LED slow blinks Red,
the batteries must be replaced. Ensure the
power is OFF. Remove the single screw from the
yellow battery cover. Install 2 x AAA batteries.
Monitor battery life in the app's tool manager.
SENSOR CARE: Cover the sensor with the
slip cover when not in use. Extreme conditions
or exposure to solvent vapor may offset the
RH sensor. To re-calibrate, place the sensor in a
controlled environment of 75%RH and between
68°F - 86°F for a period of 24 hours. To create a
75%RH environment, add wet salt to a clean
open container (bottle cap). Be careful to not
let the solution touch the probe. Place this
container and the probe in a large sealed bag
at room temperature, undisturbed for 24 hours.
Job Link® System
Flex Psychrometer
Probe
OPERATOR'S
MANUAL
Model JL3RH
www.fieldpiecejoblink.com
WARNING
Prevent damage, do not drill holes blindly into a plenum that
houses the evaporator or heat exchanger.
Fieldpiece