Appendix B. Troubleshooting
Appendix B.1. Communication Problems
If no communication is being experienced between a Profibus Master and a FieldServer Profibus Slave, check for
the following most common issues:
The Node_ID must match the System_Station_Address in the configuration. Having these two parameters
match in the configuration tells the FieldServer that the buffer referenced in the Node_ID refers to the buffers
in the Profibus card attached to the FieldServer.
The gsd file must match the FieldServer hardware being used
FieldServer offers several hardware platforms that support Profibus. Each hardware platform
requires its own gsd file. Ensure that the gsd file being used is the correct file for the hardware
platform in use.
The gsd file can be opened with a text editor. The Vendor and model name can be checked in this
file. For the FieldServer X30 Profibus Slave, the Vendor is “HMS Industrial Networks AB”, and the
Model Name is “ANYBUS-S PDP”. The current revision is 1.5, which uses Hardware revision 1.6 and
software release 1.2.
The byte count for the gsd profile must match the byte count configured in the FieldServer
The gse being used is either going to allow the Client (via the network configuration tool) to select the
bytes to be used, or the byte make-up will be fixed and specified in the gse. Either way, the largest
byte offset used by the Client must match the largest byte offset configured in the FieldServer.
When selecting byte count with a network configuration tool, the total amount of bytes/words/bits
setup per Input/Output buffer in the FieldServer configuration Map Descriptors must match those
selected in the network configuration tool otherwise a connection length mismatch will occur and the
connection will not be established. The FieldServer shows the connection size it expects on the F
(driver message) screen in the RUI utility in order that this value may be checked against the network
configuration tool.
The direction of the communications (Input/Output Buffer) may be incorrectly configured.
Buffer names can be confusing, especially when looking at the Slave. The buffers are named
according to their direction of communication in the Master. Hence, an Input buffer in the Slave will
write data to the Master, and data will be received from the Master in the output buffer.
Remember that as a Slave, the FieldServer will have to write data into the input buffer
(function=Wrbc), and read data from the output buffer (function=Rdbc).
The Data Type/Offset/Length combination may be incorrectly set up
In the FieldServer configuration, the Offset Parameter refers to the buffer offset in bytes (starting at
0), regardless of data type. The Length parameter always refers to length in items, which means Float
data will be the number of float values, Word data will be the number of words, etc
.The Profibus card may be faulty.
If this is the case, then there will be an error message in the FieldServer RUI error screen indicating
that the card could not be reached. Check for this message. If it is there, try opening up the