OUTPUT STATUS
High(Max.) Mode: Tuning fork switch will be actuated 3 seconds after the power is on.
Relay is NC and red LED indication is on. When tuning fork is covered by testing medium,
vibration stops and relay becomes NO Red LED indication is off.
SC28P/N When powered with 12~55 Vdc, top of housing would light up with green LED.
Low(Min.) Mode: Tuning fork switch will be actuated 3 seconds after the power is on.
Relay is NO and red LED indication is off. When tuning fork is covered by testing medium,
vibration stops and relay becomes NC. Red LED indication is on.
Flashing red indicates abnormal: Possible causes overloads or short-circuit load back,
equipment malfunction or wear tuning fork probe.
Flashing red indicates abnormal: Possible causes overloads or short-circuit load back,
equipment malfunction or wear tuning fork probe.
High(Max.) Mode: Tuning fork switch will be actuated 3 seconds after the power is on.
Relay is NC and red LED indication is off. When tuning fork is covered by testing medium,
vibration stops and relay becomes NO. Red LED indication is on.
DIN & Cable type
M12 x 4Pin type
Low(Min.) Mode: Tuning fork switch will be actuated 3 seconds after the power is on.
Relay is NO and red LED indication is on. When tuning fork is covered by testing medium,
vibration stops and relay becomes NC. Red LED indication is off.
It represents Blinking
Figure 4 Min./ Max. Mode
Min. Mode Max.Mode
Level
PNP/NPN
Output 1 3 1 3 1 2 1 2
Switch open
Red
LED
(DIN& Cable)
Switch closed Switch open Switch closed
Instrument
faliure
Switch open
Red
LED
(M12x 4Pin)
08-SCX-2A0012-B5-EM,10/18/2023
Tel: 886-2-22696789 Fax: 886-2-22686682
Email: info@fine-tek.com http://www.fine-tek.com
No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 23678, Taiwan.
F i n e T e k C o . , L t d .
SIMPLE TROUBLESHOOTING
Error Cause Solution
Power Supply indicator
(Green Light) is off and the
switch is not conductive.
The signal lamp is normal
and the switch output is
incorrect.
Output Indicator (Red Light)
is flashing.
The tuning fork does not
sense the material, but the
switch indicates it exists.
The tuning fork sensed the
material, but the switch
indicates it does not exist.
No power supply.
Power doesn't meet the
specification.
Power on or check the wiring and repair.
Check the nameplate and
power 12~55 Vdc
Check the wiring diagram and correct it.
The control circuit wiring is
incorrect.
The wiring for high/low level is
incorrect. Check the wiring and repair.
The tuning fork is worn,
deformed or demaged. Contact with the local sales representative.
Liquid density sensed < 0.7g/cm³ ,
the selected model is not applicable
to use
Contact with the local sales representative.
The tuning fork is stuck or
agglomerated by the material.
Check the tuning fork and remove the
sediment.
Horizontal Installation:
INSTALLATION
1. Do not install near substance inlet.
Position hole
Inlet
Position hole
Position hole
2. When installing the product DIN connector
wiring down direction, the position hole
plug must be upward direction.
If not, incorrect installation could be
damage the product.
Vertical Installation:
1. Opening of the two fork blades is to be as
the flow direction.
2. Do not install near substance inlet.