Fire-Lite Alarms BG-12LR User manual

BG-12LR and BG-12LRA
Agent Release Pull Stations
Document 51370 Revision A ECN 00-190 06/16/2000
Door Reattachment
If the door becomes detached, complete the following steps to
reattach the door to the backplate. The door cannot be connected
to the pull station if the unit is mounted to a backbox.
1. Position the door and backplate side by side in the full open
position (i.e. 180-degrees with respect to each other .
2. With the backplate position fixed, move the door behind
the backplate, as shown in the illustration, part A.
3. Align the hinge posts and holes by bringing the door up to
meet the backplate, paying particular attention to the
keying that occurs when the doors post hole is aligned to
the backplates hinge post. Refer to the illustration, part B.
4. With the two pieces aligned and keyed together, slide the
holes down onto the posts. Refer to the illustration, part C.
5. Holding the backplate, close the door slightly to lock the
door and backplate together.
BG12LRf ce.cdr
S itch Contact Rating
Switch contacts are rated for 0.25 A at 30 volts (AC or DC .
Description
The BG-12LR and BG-12LRA Agent Release Pull Stations are
designed for use with FireLite control panels that include agent
release capabilities, such as the Sensiscan 2000 and MRP-4424.
These stations are ideally suited for areas such as clean rooms
and computer rooms, where a chemical agent is used to
extinguish a fire. Both pull stations provide a dual-action,
normally open contact, release initiating point. The BG-12LRA
also includes a manual abort switch, System Normal LED, and
System Activated (release LED. The dual-action stations
require pushing the handle, then pulling the handle down for
activation. Like the entire BG-12 Series of manual fire alarm
stations, the releasing stations are UL listed and meet the ADA
requirement of a 5-lb. Maximum pull force to activate. Operating
instructions are molded into the handle.
Agent Releasing Models Available
BG-12LR. Dual action with screw terminal connections and
key lock/reset. Front of station (door is identified with the words
"AGENT RELEASE" and a symbol illustrating discharge. This
model can be semi-flush-mounted to a standard single-gang
electrical box or surface-mounted to a SB-10 backbox.
BG-12LRA. All features as BG-12LR plus manual abort switch,
System Normal (power-on LED, and System Activated (release
LED. This model must be surface-mounted to an SBA-10
backbox.
Dual Action BG-12LR
Operation
To initiate an agent release, push in the pull
station handle then pull it down. The word
"ACTIVATED" appears after the handle is
pulled down. The agent release pull station
remains in the activated position until reset.
To reset the BG-12LR or BG-12LRA:
1 Unlock and open the station door. Once open, the handle
will return to the "NORMAL" position.
2 Close and lock the door. Closing the door automatically
resets the alarm switch to the "NORMAL" position.
Note: Opening the door will not activate or deactivate the alarm
switch.
BG12LRA ctiv ted.cdr
Dual Action BG-12LRA
(Shown activated)
cth ndle.cdr
Abort Feature (BG-12LRA only)
The operation and reset of the
BG-12LRA agent release pull
station is the same as the BG-
12LR, with the addition of the
Abort Feature:
The System Normal LED will stay
illuminated when the Agent
Release Control Panel is "All
Systems Normal." When the
station has been activated,
initiating the agent release process
in the control panel, the System
Activated LED will illuminate. If
the control panel has been
configured to abort the releasing
of an extinguishing agent, then
pushing and holding-in the abort
switch will cancel the agent release
sequence. Please refer to the
respective agent release control
panel manual for further
instructions about using the Abort
feature.
www.PDF-Zoo.com
Document 51370Revision AECN 00-19006/16/2000
CAUTION
Install the agent release pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire
and Electrical codes and the requirements of the Authority Having Jurisdiction (AHJ . Conduct regular testing of the devices using
appropriate NFPA standards. FireLite is not responsible for devices that have not been properly installed, tested or maintained.
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless
physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.
Abort Plate Wiring (BG-12LRA only)
Connect the wiring from the agent release control panel's Abort Circuit to the wire leads D&E of the normally open abort switch.
Connect 24 VDC (+ to a form-c relay, this relay shall be called the Release Relay. Connect the relay's normally closed contact to the
System Normal LED wire lead A. Connect the relays normally open contact to the System Activated LED wire lead B. Connect the 24
VDC (- to the LED assembly ground wire C.
BG12LRAwiring.cdr
12345678901
1
234567890
1
1
234567890
1
1
234567890
1
1
234567890
1
1
234567890
1
12345678901
Normally O en
Abort Switch
From gent rele se
control p nels
m nu l rele se
circuit or previous
gent rele se
initi ting device
To next gent
rele se initi ting
device or ELR if l st
device on circuit
Wiring Instructions
1 If semi-flush mounted to a single-gang box, proceed to
step #2. Mount the backbox and pull all necessary wiring
through it before wiring the agent release station.
2 Remove the correct amount of wire insulation. The agent
release pull station backplate is molded with a strip gauge
to measure the amount of insulation to be removed.
4 Connect the wiring from the agent release control panel's
Manual Release Circuit, or any previous agent release
initiating device to terminals 1 and 2 on the station's terminal
strip. Connect the next agent release initiating device or
End-of-Line Resistor (ELR to terminals 1 and 2.
5 Maintain consistent polarity with all connections throughout
the manual release circuit.
WARNING! Do not loop wiring under any terminals. Break
wire run to maintain IDC supervision.
BG12LRAcircuit.cdr
*Mount End of line resistor on last unit.
BG12LRWiring2.cdr
www.PDF-Zoo.com

This manual suits for next models

1

Other Fire-Lite Alarms Control Unit manuals

Fire-Lite Alarms I300-6 User manual

Fire-Lite Alarms

Fire-Lite Alarms I300-6 User manual

Fire-Lite Alarms MMF-300 Series User manual

Fire-Lite Alarms

Fire-Lite Alarms MMF-300 Series User manual

Popular Control Unit manuals by other brands

Aqua Medic M-Ventil Pulse Operation manual

Aqua Medic

Aqua Medic M-Ventil Pulse Operation manual

Aircable ACC1600 user guide

Aircable

Aircable ACC1600 user guide

flakt woods KSOM Installation and connecting instructions

flakt woods

flakt woods KSOM Installation and connecting instructions

caenrfid Lepton7 R7100C Technical information manual

caenrfid

caenrfid Lepton7 R7100C Technical information manual

AutomationDirect IronHorse GSDA-AI-A8 user manual

AutomationDirect

AutomationDirect IronHorse GSDA-AI-A8 user manual

Alfalaval SRC PN10 instruction manual

Alfalaval

Alfalaval SRC PN10 instruction manual

Alfalaval Unique 7000 Series instruction manual

Alfalaval

Alfalaval Unique 7000 Series instruction manual

Ebmpapst RM-ECd Operating and maintenance instructions

Ebmpapst

Ebmpapst RM-ECd Operating and maintenance instructions

FRO­NIUS Power Control Card operating instructions

FRO­NIUS

FRO­NIUS Power Control Card operating instructions

IMG STAGE LINE LDC-400 instruction manual

IMG STAGE LINE

IMG STAGE LINE LDC-400 instruction manual

GSM Activate AD4IN1V8 manual

GSM Activate

GSM Activate AD4IN1V8 manual

red lion Graphite GMDIO installation guide

red lion

red lion Graphite GMDIO installation guide

Delta MultiChoice 13 Series installation instructions

Delta

Delta MultiChoice 13 Series installation instructions

Astral Pool System VRAC Basic Installation and maintenance manual

Astral Pool

Astral Pool System VRAC Basic Installation and maintenance manual

Tripp Lite Power Accessory Module PAM-3 instruction sheet

Tripp Lite

Tripp Lite Power Accessory Module PAM-3 instruction sheet

Aero-motive 19105 installation instructions

Aero-motive

Aero-motive 19105 installation instructions

Electronics MagnaValves 500-24 instruction manual

Electronics

Electronics MagnaValves 500-24 instruction manual

AKG AMM 10 - User instructions

AKG

AKG AMM 10 - User instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.