FireFlex TOTALPAC X Installation guide

FM-076G-0-11A
Advanced Integrated Fire Protection System
TOTALPAC®X
Owner's Operation
and
Maintenance Manual
DOUBLE INTERLOCK PREACTION SYSTEM
SUREFIRE®RELEASE

Page ii TOTALPAC®X
Integrated Fire Protection System
OWNER'SOPERATION & MAINTENANCE MANUAL
FM-076G-0-11A
Copyright © 2021 FIREFLEX Systems Inc.
All Rights Reserved
Reproduction or use, without express written permission from FIREFLEX Systems Inc, of any portion of this manual is prohibited.
While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy, FIREFLEX Systems Inc
assumes no liability resulting from any errors or omissions in this manual, or from the use of the information contained herein.
TOTALPAC ®is a registered trademark of FIREFLEX Systems Inc.
FIREFLEX Systems Inc. reserves the right to make changes to this manual and the data sheets herewith at any time, without prior
notification.

TOTALPAC®XPage iii
Integrated Fire Protection System
OWNER'SOPERATION & MAINTENANCE MANUAL
FM-076G-0-11A
Table of Contents
Double Interlock Preaction System - SUREFIRE®Release
General Section ..........................................................................................................Section A
1- General description
2- Listings and approvals
3- Applicable standards
4- Environment
5- Features
6- Configuration description
7- System release
Mechanical Section......................................................................................................................Section B
1- Installation, operation & maintenance instructions
1.1 Installation
1.2 Preliminary inspection before placing the system in service
1.3 Placing the system in service
1.4 System operation
1.5 Emergency instructions
1.6 Placing the system back in service after operation
1.7 Inspections & tests
1.8 Maintenance
2- System trim
2.1 Normal condition
Trim Options.................................................................................................................................Section C
1- Shut-off valve & sight glass
2- Anti-column device option
Air Supply.....................................................................................................................................Section D
1- Cabinet air supplies
2- Operation
3- Maintenance and inspection
4- Air supply options
Control Section.............................................................................................................................Section E
1- Remotely controlled unit without release control panel
1.1 Product description
1.2 Technical data
Electrical Section..........................................................................................................................Section F
1- Remotely controlled configuration
Dimensional Data & Cabinet.......................................................................................................Section G
1- Cabinet unit
Limited Warranty..........................................................................................................................Section H

Page iv TOTALPAC®X
Integrated Fire Protection System
OWNER'SOPERATION & MAINTENANCE MANUAL
FM-076G-0-11A
This page is left intentionally blank.

TOTALPAC®X SUREFIRE®Page 1of 2
Integrated Fire Protection System
A
General Section - Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-32A
1- General description
This TOTALPAC®X SUREFIRE®integrated fire protection
system by FIREFLEX Systems Inc. consists of a fail-safe
preaction system trim totally pre-assembled, pre-wired and
factory tested. All electrical and mechanical components
of the system are contained in one single unit.
The only connections required for installation are the water
supply inlet, the water discharge outlet, the main drain, the
electrical trouble, supervisory and alarm connections, as
well as the AC power lines for the release control panel
and optional air compressor. The discharge outlet is
connected to a fixed piping network of automatic
sprinklers. Water is the extinguishing agent.
On system piping network, closed heat sensitive automatic
sprinklers are spaced and located in accordance with
recognized installation standards in order to detect a fire.
Only those sprinklers immediately over or near to fire
operate, minimizing water damage.
Double interlock preaction system with SUREFIRE®release
uses closed automatic sprinklers on the system piping
network, which is supervised with air pressure. The
detection network is installed in parallel with the system
piping network and is designed to operate before a
sprinkler head fuses. Detection system operates first and
gives an alarm signal.
Double interlock preaction system is designed so the
deluge valve will open when both detector on the detection
network activates and a loss of pressure in the system
piping network occurs. When the deluge valve opens,
water will flow into the system piping network and out of
any open automatic sprinklers and any other opening on
the system.
Under normal supervisory condition, a loss of pressure
alone in the system piping network will only give a
supervisory signal.
Fail-safe operation of the TOTALPAC®X SUREFIRE®allows
the opening of the deluge valve when the release control
panel is no more powered under AC power and batteries.
It then operates as a dry pipe system.
Note: Every TOTALPAC®X SUREFIRE®unit is identified with
its unique serial number. This number is located on an
adhesive label inside the main door panel and is used to
maintain a record in our computerized data base. Have
this serial number handy when calling for information on
your unit (format is TOTX####).
2- Listings and approvals
In addition to being fabricated under tight ISO-9001
manufacturing and quality control procedures, your
TOTALPAC®3 SUREFIRE®unit has also been tested and
approved by recognized laboratories.
WARNING Any unauthorized modification or addition made
on-site to a factory built Listed unit will void this Listing.
Such modifications or additions may void the unit's
warranty as well. Consult your nearest FIREFLEX Systems
authorized distributor before proceeding with such
modifications or additions.
3- Applicable standards
The TOTALPAC®X SUREFIRE®complies with the following
standards:
-NFPA-13 Sprinkler Systems
-NFPA-15 Water Spray Fixed Systems
-NFPA-16 Foam-Water Sprinkler and Foam-Water Spray
Systems
-NFPA-72 Fire Alarm Systems
Before installation, the contractor installing the unit shall
also be familiar with the following documents and
standards:
- Applicable Local & State Building Codes
- Any additional requirements of the Local Authority Having
Jurisdiction
4- Environment
TOTALPAC®X SUREFIRE®unit can be installed in none
heated or in a corrosive atmosphere area, depending on
the selected cabinet (see section GCABINET SECTION).
Refer to section ECONTROL SECTION for environment
data.
The unit and its components must be kept free of foreign
matter, contaminated water supplies, and any condition
that could impair its operation or damage the components.
The frequency of the inspections and maintenance will
vary depending on these environmental conditions as well
as the condition of the air supply to the system. The owner
is responsible for maintaining the fire protection system
and devices in proper operating condition. Refer to
section BMECHANICAL SECTION for maintenance
instructions.

Page 2of 2TOTALPAC®X SUREFIRE®
A
Integrated Fire Protection System
General Section - Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-32A
5- Features
The TOTALPAC®X SUREFIRE®unit is superior to many other
products which are actually available on the fire protection
market. It is manufactured by FIREFLEX Systems Inc.
which has developed and introduced the concept of
integrated fire protection systems.
Main features are:
Trouble free design for safe and easy application
Available in 5 sizes from 1½" (40 mm) to 6" (150mm)
diameter
Uses the Viking deluge valve
Unit is available either with or without integrated release
control panel
Compact, aesthetic and easy to move
User-friendly standardized owner's manual with every
unit
Unique serial number on every unit
Uses only c-UL-us Listed and FM Approved components
Designed in accordance with NFPA Standards
Trim is fully assembled and tested at the factory
All trims are galvanized steel, Listed and Approved for
250 PSI (1724 kPa) service maximum
Quick connections to water supply and drain at the
bottom, and sprinkler riser on top of unit, all with grooved
end fittings
No open drain cup inside unit
Sturdy 14 gauge steel cabinet, painted fire red with oven
baked polyester powder on phosphate base
Textured rust proof finish
Neoprene gasket on all doors
Separate unlocked access hatch to emergency manual
release
Key-alike locks on all cabinet doors
Manufactured under ISO-9001 quality control procedures
Fail-safe operation upon AC power and batteries loss
6- Configuration description
TOTALPAC®X SUREFIRE®preaction system is built around
the Viking trim using straight through deluge valve
model F-1 (model F-2 is the Halar®coated version for use
in corrosive environments).
The valve is rated up to a maximum of 250 PSI WWP
(1724 kPa) and is available in the following diameters:
1½" (40 mm) 3" (80 mm) 6" (150 mm)
2" (50 mm) 4" (100 mm)
TOTALPAC®X SUREFIRE®preaction system is supplied with
groove/groove deluge valve.
6.1 Double interlock preaction system
The system piping network is pressurized with air or
nitrogen gas. Thepreaction system uses the Viking
deluge valve which open when both the detection network
activates and a loss of pressure in the system piping
network occurs, or anytime the handle of the emergency
release valve is pulled.
If the detection network activates due to fire or malfunction,
the deluge valve will not open.
If the system piping network is broken or an automatic
sprinkler fuses, the deluge valve will not open.
7- System release
7.1 SUREFIRE®release
Preaction system with SUREFIRE®release requires an
electric detection network equipped with compatible
detectors. Release trim for the deluge valve requires a
normally closed solenoid valve controlled by an approved
releasing control panel (if provided with this system, see
section ECONTROLS SECTION and VFR-400 manual for
details).
The release control panel is configured for crossed zones
operation. A first zone is connected to the detection
network; the other one is connected to a pressure switch
used for low air alarm signal.
In fire condition, both the activation of a detector on the
detection network and the fusing of an automatic sprinkler
from the system piping network are required to energize
the normally closed solenoid valve, causing the deluge
valve to open. Water will flow from the preaction system
through opened sprinklers. Automatic sprinkler must open
to allow water to flow from the preaction system.
An additional normally open solenoid valve and a
pneumatic actuator are used to allow fail-safe operation of
the preaction system. When power is applied to the
releasing control panel, if the system piping network is
broken or an automatic sprinkler fuses, a very low air alarm
signal activates the normally open solenoid valve, which
prevent the operation of the pneumatic actuator.
If the releasing control panel has lost power, the preaction
system operates as a dry pipe system. If any automatic
sprinkler fuses from the system piping network, it will
release the pneumatic actuator and open the deluge valve.
Water will flow from the preaction system through opened
sprinklers.

TOTALPAC®X SUREFIRE®Page 1of 8
Integrated Fire Protection System
B
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1- Installation, operation & maintenance
instructions
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section and
section DAIR SUPPLY.
1.1 Installation
1. Conform to local municipal or other codes regarding
installations of fire protection systems.
2. Install the TOTALPAC®X SUREFIRE®unit and connect the
system according to instruction manual and technical
data supplied.
IMPORTANT ! The cabinet must be firmly anchored to the
floor using all four (4) anchoring holes (see section G
CABINET).
Note: The drain collector shall be connected to an open
drain. Do not restrict or reduce drain piping.
3. Install the system piping network in accordance with
applicable standards.
4. Connect all supervisory, alarm and releasing signals to
the remote release control panel (supplied by others),
according to electrical schematics (see section F
ELECTRICAL), as well as detection circuits.
Note: Electrical conduit connectors shall be NEMA-4 type.
5. If applicable, connect the AC power to the air
compressor on a separate breaker in the electric
distribution panel (see section FELECTRICAL).
Notes:
AC power connections must be made by a qualified
installer according to national standards and equipment
specifications.
Do not apply AC power to the equipment yet.
6. Perform preliminary inspection prior to put system in
service (see paragraph 1.2 of the current section).
7. Place the system in service (see paragraph 1.3 of the
current section).
8. Perform the annual inspection sequence (see
paragraph 1.8 of the current section) and test each
detection device and alarm unit.
9. If the system does not operate as it should, make the
necessary corrections according to manuals issued or
consult your distributor or FIREFLEX Systems Inc.
10. Make sure that building owner or a delegated
representative has received instructions regarding the
operation of the system.
WARNING ! TOTALPAC®X SUREFIRE®unit must be installed
in an area not subject to freezing temperatures or physical
damage.
1.2 Preliminary inspection before placing the system in
service
1. Open door to mechanical section.
a) Main water supply valve (D1) must be CLOSED.
b) Priming valve (B1) must be CLOSED.
c) Air supply for system piping network must be CLOSED
(see section DAIR SUPPLY).
d) Flow test valve (B6) and main drain valve (D3) must
be CLOSED.
e) Alarm test valve (B5) must be CLOSED.
f) Gauges (B11, B12, E3 and F4)should show 0 PSI
(0 kPa).
g) If applicable, the shut-off valve (D4) must be OPEN.
2. OPEN the manual emergency release valve (B10) and
make sure the deluge valve (A1) is tripped.
3. Using the built-in contractor's hydrostatic test ports (see
figure 1 of this section and section DAIR SUPPLY), fill
system piping network with water and maintain pressure
as per NFPA-13 requirements.
WARNING ! Do not subject the pressure gauges and
pressure transducer to hydrostatic pressure above 250 PSI
(1724 kPA). Close gauge valves before proceeding with
hydrostatic test.
4. Correct leaks if any before completing test.
5. Verify that main water supply valve (D1) is still CLOSED.
6. OPEN main drain valve (D3) to completely drain the
system piping network.
7. If applicable, apply AC power to the air compressor and
remote release control panel (supplied by others). The
air supply must be CLOSED (see section DAIR SUPPLY).

Page 2of 8TOTALPAC®X SUREFIRE®
B
Integrated Fire Protection System
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1.3 Placing the system in service
1. Verify that the main water supply valve (D1) is CLOSED.
Verify that the system has been properly drained.
2. Verify that all automatic sprinklers are set and that
inspector's test valve and/or piping auxiliary drain valves
are CLOSED.
3. CLOSE main drain valve (D3). Verify that the manual
emergency release valve (B10) is CLOSED.
4. Air supply must be OPEN (see section DAIR SUPPLY).
5. Establish recommended supervisory pressure to the
system piping network (see paragraph 2.1 NORMAL
CONDITION of the current section and section DAIR
SUPPLY).
Note: On system provided with air pressure maintenance
device (air supply style "B"), verify that the APMD bypass
valve (E8) is CLOSED and that APMD input and output
valves (E6 and E7) are OPEN.
6. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
7. Reset the remote release control panel (supplied by
others). Solenoid valve (F1) should CLOSE.
8. OPEN flow test valve (B6).PARTIALLY OPEN main water
supply valve (D1).
9. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
10.FULLY OPEN the main water supply valve (D1).
11. Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1NORMAL CONDITION of the current
section).
12. Check and repair all leaks.
13. On new installation, system that has been placed out of
service, or where new equipment has been installed,
trip test the system to verify that all equipment functions
properly (see paragraph 1.7.2FULL FLOW TRIP TEST of
the current section).
14.Notify the AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is in service.
Note: When a valve has been removed from service and is
subject to freezing or will be out of service for an extended
period of time, all water must be removed from the priming
chamber, trim piping, water supply piping and any other
trapped areas.
1.4 System Operation
1.4.1 In the SET condition
System water supply pressure enters the priming chamber
of the deluge valve (A1) through the priming line which
includes a normally open priming valve (B1), strainer (B2),
restricted orifice (B3) and spring loaded check valve (B4).
Water pressure is trapped in the priming chamber of the
deluge valve (A1) by aspring loaded check valve (B4),
normally closed solenoid valve (F1), normally open
solenoid valve (F2), pneumatic actuator (F3),PORV (B9)
(pressure operated relief valve) and manual emergency
release valve (B10). The pressure in the priming chamber
holds the deluge valve clapper closed, keeping the outlet
chamber and system piping dry.
1.4.2 In a fire condition
When an automatic sprinkler fuses, the low air pressure
condition activates the low air supervisory switch (E4).
This switch, along with detection condition at the remote
release control panel, energize the solenoid valve (F1)
when both circuits are activated.
Pressure from the priming chamber of the deluge
valve (A1) is released to the open drain manifold faster
than it is supplied through the restricted orifice (B3). The
deluge valve clapper opens to allow water to flow into the
piping network and alarm devices, causing water flow
alarms connected to the alarm pressure switch (C1) and
the optional water motor alarm (C2) to activate. When an
automatic sprinkler fuses, water will flow from the system
piping network.
When the deluge valve (A1) opens, the sensing end of the
PORV (B9) is pressurized, causing it to open. It then
continually vent the priming chamber, preventing the
closure of the deluge valve. The deluge valve can only be
reset after the system is taken out of service.
Note: If the solenoid valve (F1) is energized, the deluge
valve (A1) will open but the water will be trapped in the
system piping network. Alarm devices (C1 and optional
C2) will operate.
1.4.3 Manual operation
Anytime the handle of the manual emergency release
valve (B10) is triggered, pressure is released from the
priming chamber of the deluge valve (A1) causing deluge
valve to open. Water will flow into the system piping
network and alarm devices (C1 and optional C2) will
operate. The PORV (B9) keeps the deluge valve open.
When an automatic sprinkler fuses, water will flow from the
system piping network.
1.4.4 Supervisory condition
If an automatic sprinkler opens prior the operation of the
detection system or any time the supervisory pressure is
lost in the system piping network, the low air pressure
switch (E4) will give a low air pressure signal to the remote
release control panel and the normally open solenoid
valve (F2) is energized by the remote release control
panel, keeping the deluge valve (A1) closed.

TOTALPAC®X SUREFIRE®Page 3of 8
Integrated Fire Protection System
B
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1.4.5Fail-safe condition
If the remote release control panel is unable to energize
the solenoid valve (F1), the system will operate as a dry
pipe system with the help of the pneumatic actuator (F3)
and the normally open solenoid valve (F2) being disabled.
1.5 Emergency instructions
To take system out of service
WARNING ! Placing a control valve or detection system out
of service may eliminate the fire protection capabilities of
the system. Prior to proceeding, notify all local
AUTHORITIES HAVING JURISDICTION. Consideration should
be given to employ a fire patrol in the affected areas.
After a fire, verify that the fire is OUT and that placing the
system out of service has been authorized by the
appropriate local AUTHORITY HAVING JURISDICTION.
Sprinklers piping that have been subjected to a fire must
be returned to service as soon as possible. The entire
system must be inspected for damage, and repaired or
replaced as necessary.
1. CLOSE main water supply valve (D1).
2. OPEN main drain valve (D3).
Note: Electric alarms controlled by a pressure switch
installed at the ¾"-NPT (20mm) connection (C2) for a non-
interruptible alarm signal cannot be shut-off until the
deluge valve (A1) is reset or taken out of service.
3. Air supply must be CLOSED (see section DAIR SUPPLY).
4. OPEN flow test valve (B6).
5. CLOSE priming valve (B1).
6. Replace any automatic sprinkler that have opened,
been damaged or exposed to fire conditions.
7. Perform all recommended maintenance procedures
(see paragraph 1.8 MAINTENANCE in the current section).
8. Return the system to service as soon as possible (see
paragraph 1.6 PLACING THE SYSTEM BACK IN SERVICE
AFTER OPERATION of the current section).
Note: When a system has been removed from service and
is subject to freezing or will be out of service for an
extended period of time, all water must be removed from
the priming chamber, trim piping, water supply piping and
any other trapped areas.
1.6 Placing the system back in service after operation
1. Verify that the system has been properly drained. Verify
that all automatic sprinklers are set and/or inspector's
test valve and system piping auxiliary drain valves are
CLOSED.
2. Verify that the main water supply valve (D1) is CLOSED,
and that the manual emergency release valve (B10) is
CLOSED.CLOSE main drain valve (D3).
3. Air supply must be OPEN (see section DAIR SUPPLY).
4. Restore supervisory pressure to the system piping
network (see section DAIR SUPPLY).
Note: On system provided with air pressure maintenance
device (air supply style "B"), verify that the APMD bypass
valve (E8) is CLOSED and that APMD input and output
valves (E6 and E7) are OPEN.
5. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
6. Reset the remote release control panel (supplied by
others). Solenoid valve (F1) should CLOSE.
7. OPEN flow test valve (B6).PARTIALLY OPEN main water
supply valve (D1).
Note: Do not open main water supply valve (D1) until
gauge (B11) shows stabilized pressure.
8. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
9. FULLY OPEN the main water supply valve (D1).
10.Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1NORMAL CONDITION of the current
section).
11. Check and repair all leaks.
12.Notify the local AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is back in service.

Page 4of 8TOTALPAC®X SUREFIRE®
B
Integrated Fire Protection System
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1.7 Inspections and tests
NOTICE: The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
It is imperative that the system be inspected and tested on
a regular basis in accordance with NFPA-25. Refer to
Inspections and Tests recommended in Viking technical
data describing individual components of the preaction
system used.
The frequency of the inspections may vary due to
contaminated or corrosive water supply, corrosive
atmospheres, as well as the condition of the air supply to
the system. For minimum maintenance and inspection
requirements, refer to NFPA-25. In addition, the
AUTHORITY HAVING JURISDICTION may have additional
maintenance, testing, and inspection requirements that
must be followed.
WARNING ! Any system maintenance that involves placing
a control valve or detection system out of service may
eliminate the fire protection capabilities of that system.
Prior to proceeding any testing, notify all local AUTHORITIES
HAVING JURISDICTION. Consideration should be given to
employment of a fire patrol in the affected areas.
1.7.1System piping network low air supervisory test
1. To prevent operation of the deluge valve (A1) and filling
of the piping network with water during the test, CLOSE
main water supply valve (D1) and OPEN flow test
valve (B6).
2. If applicable, verify that the shut-off valve (D4) is OPEN.
3. FULLY OPEN the inspector's test valve on the system
piping network, or the main drain valve (D3).
4. Verify that low air supervisory signal operate within
acceptable time period and continue without
interruption.
5. CLOSE the inspector's test valve, or the main drain
valve (D3).
6. CLOSE priming valve (B1).
7. Establish recommended supervisory pressure to the
system piping network (see section DAIR SUPPLY).
8. OPEN priming valve (B1). Verify that the pressure
indicated at the priming pressure gauge (B11) is equal
to, or greater than the pressure indicated at the water
supply pressure gauge (B12).
9. PARTIALLY OPEN main water supply valve (D1).
10. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
11. FULLY OPEN the main water supply valve (D1).
1.7.2Full flow trip test
Performance of a full flow trip test is recommended
annually during warm weather. Consider coordinating this
test with operation testing of the releasing devices.
Caution !Performance of this test will cause the deluge
valve (A1) to open and the system piping network to be
filled with water.If it is not required to fill the system piping
network with water, use the shut-off valve (if applicable)
(see paragraph 1.7.4OPERATION OF THE SHUT-OFF VALVE of
the current section).
To trip test the electric release system
1. Trip the deluge valve (A1) by performing the following
paragraph “a” or “b”.
a) Open the inspector's test valve from the system
piping network. Energize the solenoid valve (F1) from
the remote release control panel (supplied by others).
b) Open the door of the manual emergency release
valve (B10) and trigger the handle.
2. The deluge valve (A1) should open. Alarm devices (C1
and optional C2) should operate. The piping network
will be filled with water.
3. Verify adequate flow through the inspector's test valve
from the system piping network.
When trip testing is complete
1. Perform steps 1 through 5of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.
1.7.3 Main drain test
A main drain test shall be conducted to determine whether
there has been a change in the condition of the water
supply piping and control valves.
Test procedure
1. Record the pressure indicated by the water supply
gauge (B12).
2. If applicable, CLOSE the alarm control valve.
3. FULLY OPEN the flow test valve (B6).
4. Record residual pressure.
5. CLOSE the flow test valve (B6) slowly.
6. Record the time taken for supply water pressure to
return to the original pressure.
7. Compare results from previous inspections or initial
commissioning. Any important variation from those
results must be investigated.
Note: A main drain test shall be conducted any time the
main water supply valve (D1) is closed and reopened at
the system.

TOTALPAC®X SUREFIRE®Page 5of 8
Integrated Fire Protection System
B
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1.7.4 Operation of the optional shut-off valve
Inspection of the system can be implemented without filling
the system piping network with water. The use of shut-off
valve (D4) and sight glass assembly (D5) allows to verify
the operation of the system and prevents water from
reaching the piping network.
1. CLOSE the shut-off valve (D4) to isolate the system
piping network.
2. Execute the full flow trip test (see paragraph 1.7.2 of the
current section). The deluge valve (A1) should open.
3. Using a flashlight in one of the sight glasses, verify that
water flows through the sight glass assembly (D5).
When trip testing is complete
1. Perform steps 1 through 5 of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6 PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.
1.8 Maintenance
NOTICE: The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
The system shall be maintained in full operation condition
at all times.
All troubles or impairments shall be corrected promptly
consistent with the hazard being protected.
Refer to MAINTENANCE INSTRUCTIONS provided in Viking
Technical Data describing individual components of the
system used.
The air supply shall be maintained in full operating
condition at all times (refer to section DAIR SUPPLY).
The following requirements are based upon NFPA-25.
Records
Records of inspections, tests and maintenance of the
system and its components shall be made available to the
AUTHORITY HAVING JURISDICTION upon request. Typical
records include, but are not limited to: valves inspection;
flow, drain, and pump tests, and trip test of the deluge
valves.
Acceptance test records should be retained for the life of
the system or its special components. Subsequent test
records should be retained for a period of one (1) year
after the next test. The comparison determines
deterioration of system performance or condition and the
need for further testing or maintenance.
1.8.1 Monthly
1. Inspection of gauges (water supply (B12) and priming
chamber (B11) pressure) to ensure good condition and
normal water supply pressure.
2. Control valve shall be externally inspected. The valve
inspection shall verify the following:
a) The gauges indicate that normal supply water
pressure is being maintained.
b) The valve is free of physical damage.
c) All valves are in the appropriate open or closed
position (see paragraph 2.1 of the current section).
d) There is no leakage from the alarm drains.
1.8.2 Quarterly
1. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
2. Conduct system piping network low air supervisory test
(see paragraph 1.7.1 of the current section).

Page 6of 8TOTALPAC®X SUREFIRE®
B
Integrated Fire Protection System
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
1.8.3 Semi-annually
1. Main water supply valve (D1) switch shall be operated
to verify the switch actuation upon movement of the
hand wheel.
2. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
3. Perform functional test of all components of the system.
1.8.4 Annually
1. Perform full flow trip test (see paragraph 1.7.2of the
current section).
2. Record indicating the date of the last trip, tripping time
and name of the organization conducting the test shall
be maintained at a location available for review by the
AUTHORITY HAVING JURISDICTION.
3. Perform main drain test (see paragraph 1.7.3 of the
current section).
1.8.5 Every 5 years
1. Test on gauge (gauge precision required: less than 3%
of the full scale).
2. Perform test on control valve operation.
3. Deluge valve (A1) and their associated strainers, filters
and restriction orifices shall be inspected internally.
4. Perform main drain test (see paragraph 1.7.3 of the
current section).
2- Double interlock preaction system with
SUREFIRE®release
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section and
section DAIR SUPPLY.
2.1 Normal condition
1.Valves
a) Main water supply valve (D1) is OPEN.
b) All upstream water supply valves are OPEN.
c) Priming valve (B1) is OPEN.
d) Flow test valve (B6) is CLOSED.
e) Main drain valve (D3) is CLOSED.
f) Alarm test valve (B5) is CLOSED.
g) Manual emergency release valve (B10) is CLOSED
(handle in vertical position).
h) Air supply is OPEN (see section DAIR SUPPLY).
i) All gauge valves are OPEN.
j) Shut-off valve (D4) is OPEN (if applicable).
2. Gauges
a) Water supply pressure (B12) shall not exceed
175 PSI (1207 kPa) or 250 PSI (1724 kPa).
b) Priming chamber pressure (B11) should be equal to,
or higher than, water supply pressure (B12).
c) System piping network (E3 and F4)shall be at 35 PSI
(242 kPa) or 55 PSI (380 kPa) (see section DAIR
SUPPLY).
3. Pressure switches & settings (factory set)
a) Alarm pressure switch (C1) should activate when
pressurized higher than 5 PSI (34 kPa).
b) Low air pressure switch (E4) should activate when
pressurized lower than 25 PSI (173 kPa) or 45 PSI
(311 kPa) (see section DAIR SUPPLY).

TOTALPAC ®X SUREFIRE ® Page 7 of 8
Integrated Fire Protection System B
Mechanical Section - Double Interlock Preaction System - SUREFIRE ® Release
FM-076G-0-52A
Figure 1 - Detailed system trim schematic
Typical double interlock preaction system with SUREFIRE ® release (3" (80 mm) system shown)
B7
B8
E4
A1
FM-061H-0-394A
FIELD CONNECTION
TO OPEN DRAIN
(bottom entry)
FIELD CONNECTION
TO WATER SUPPLY
(bottom entry)
FIELD CONNECTION TO
SPRINKLER PIPING NETWORK
F4
CONTRACTOR'S
HYDROSTATIC TEST PORT
(water supply side)
1
C1
D2
B5
B13
B6
CONTRACTOR'S
HYDROSTATIC TEST PORT
(system side)
F3
D1
B9
D3
B11
B12
B4
B2
B1
C2
B3
E9
To Air Supply
System Trim
B10
TOTALPAC X Base
(shown without enclosure)
F5
F1
F2
Trim components
A1 Deluge valve
B1 Priming valve (N.O.)
B2 Strainer
B3 1/16" (1.6 mm) Restricted orifice
B4 Spring loaded check valve
B5 Alarm test valve (N.C.)
B6 Flow test valve (N.C.)
B7 Drip check valve (N.O.)
B8 Drain check valve
B9 PORV (pressure operated relief valve)
B10 Manual emergency release valve (N.C.) (shown in
closed position)
B11 Priming pressure water gauge & valve (N.O.)
B12 Water supply pressure gauge & valve (N.O.)
B13 Clapper check valve
C1 Alarm pressure switch (PS10-1)
C2 ¾"-NPT (20 mm) connection to optional water motor
gong (strainer to be supplied by contractor)
D1 Main water supply valve (N.O.)
D2 Riser check valve
D3 Main drain valve (N.C.)
E4 Air supervisory pressure switch (PS40-2)
E9 Float check valve assembly
F1 24VDC solenoid valve (N.C.)
F2 24VDC solenoid valve (N.O.)
F3 Pneumatic actuator
F4 Pneumatic actuator pressure gauge & valve (N.O.)
F5 5/64" Restricted orifice

Page 8of 8TOTALPAC®X SUREFIRE®
B
Integrated Fire Protection System
Mechanical Section -Double Interlock Preaction System - SUREFIRE®Release
FM-076G-0-52A
This page is left intentionally blank.

TOTALPAC®XPage 1of 2
Integrated Fire Protection System
C
Trim Options
FM-076G-0-61B
Preaction trim options
1. Shut-off valve & sight glass
The shut-off valve & sight glass option is intended to be
used for applications where testing of the system operation
without filling the sprinkler piping network is desirable and
where it is critical that all functions of the preaction system
be tested under actual discharge conditions. Examples of
such applications are freezers, ovens, museums, data
processing and other hazards where the possibility of
water leaking from the piping system is to be avoided at all
costs.
Operation of the shut-off valve
Inspection of the system can be implemented without filling
the sprinkler piping network with water.
1. CLOSE the sprinkler piping network shut-off valve (D4);
the valve is supervised on the same circuit as the main
water supply valve (D1).
2. OPEN the main drain valve (D3).
3. Simulate the operation of the system to open the deluge
valve (A1); see annual test under section B
INSPECTION AND MAINTENANCE. Using a flashlight in the
sight glasses, verify that water flows through the sight
glass assembly (D5).
4. Once tests are completed, make sure the main drain
valve (D3) is completely CLOSED.Return the system in
service as per section BPLACING THE SYSTEM BACK IN
SERVICE.
5. Fully OPEN the shut-off valve (D4).
Figure 1 –Shut-off valve & sight glass
(system is shown without cabinet for clarity)
TOTALPAC XBase
(shown without enclosure)
Point flashlight
HERE
Sight Glass
Assembly (D5)
Main Drain
Valve (D3)
Deluge Valve (A1) or
Flow Control Valve (A2)
Riser Check
Valve (D2)
Supervised Shut-off
Valve (D4)
FM-061H-0-355A
2. Anti-column device option
The model LD-1 anti-column device is an optional trim
component designed for use with preaction sprinkler
system. The anti-column device automatically prevents an
unwanted water column from establishing within the
system riser. On preaction sprinkler systems, the anti-
column device prevents water from columning downstream
of the easy riser check valve.
Figure 2 – Anti column device detail
From sprinkler riser
To drain collector FM-061H-0-146A

Page 2of 2TOTALPAC®X
C
Integrated Fire Protection System
Trim Options
FM-076G-0-61B
This page is left intentionally blank.

TOTALPAC ®X Page 1 of 10
Integrated Fire Protection System D
Air Supply - Preaction System
FM-076G-0-119A
1. Cabinet Air Supplies
Preaction sprinkler system using air pressure for
supervisory or releasing purposes is provided with either
internal or external supervised air supply.
WARNING Pressures other than the factory pressure
settings may affect the operation of the system.
Three (3) styles of air supplies are available for the
TOTALPAC ®X units depending on needs or configurations.
These air supplies are all factory assembled, mounted in
the cabinet and pressure tested. Following is the
description of those options.
1.1 Air supply Style "A" (refer to figure 2)
Used only for the sprinkler piping network of preaction
systems. Air supply style "A" includes the air compressor
mounted inside the TOTALPAC ®X cabinet with its
supervisory trim and options. Air compressor is of the
oilless piston type without reservoir and is factory piped to
the sprinkler piping system riser, all within the
TOTALPAC ®X cabinet.
A factory wired isolation switch (see figure 2 in section E
CONTROLS SECTION) is also provided in the TOTALPAC ®X
cabinet, allowing powering off the air compressor while
some maintenance work on the unit is done, without
disturbing the rest of the system.
To connect non-energized AC power to the air
compressor, refer to field wiring diagram (see section F
ELECTRICAL SECTION).
Table 1 - Air compressor F.L.A. (full load amp) rating
Air compressor
size
115Vac
60Hz
208Vac
60Hz
230Vac
60Hz
1/6 HP 5.0 Amp 2.3 Amp 2.5 Amp
1/3 HP 7.4 Amp 3.5 Amp 3.7 Amp
1/2 HP 10.0 Amp 4.9 Amp 5.0 Amp
1 HP 18.0 Amp 7.7 Amp 9.0 Amp
Air compressor
size
220Vac
50Hz
240Vac
50Hz
0.12 KW 1.3 Amp 1.3 Amp
0.25 KW 2.5 Amp 2.6 Amp
0.56 KW 4.0 Amp 4.5 Amp
1.2 KW 6.0 Amp 6.0 Amp
Note : Selection of the appropriate wire size is the
responsibility of the installing contractor.
1.2 Air supply Style "B" (refer to figure 3)
Used only for the sprinkler piping network of preaction
system, when an external air supply is provided by others
(either a compressor, plant air or dry nitrogen cylinders)
and piped to the air inlet port of the unit.
Air supply style "B" provides an APMD (air pressure
maintenance device) trim, factory mounted in the
TOTALPAC ®X cabinet. The APMD regulates and restricts
the inlet pressure. It allows an outlet pressure range from
5 PSI to 75 PSI (34 kPa to 517 kPa) ±2 PSI (14 kPa). An
internal ball check valve prevents back flow.
Warning : When air supply style "B" is selected, the air
supply should be provided and installed by the sprinkler
contractor OUTSIDE of the TOTALPAC ®X cabinet. Air
supply is NOT provided with the unit.
1.3 Air supply Style "D" (refer to figure 4)
Mainly used with preaction system protecting refrigerated
spaces and freezers, where a special dry external air
supply unit is piped directly to the system riser inside the
freezer itself, as shown in NFPA-13. Air supply style "D"
provides only an air supervisory and shut-off trim.
Ambient temperature at the special external air supply unit
location should not exceed 104°F (40°C). Refer to NFPA
and Factory Mutual Codes & Standards for details on
refrigerated spaces applications. Air supply style "D" can
also be used when the contractor prefers to provide his
own air supply & regulation trim, mounted outside the
TOTALPAC ®X cabinet.
Note : External air supply MUST always be restricted to
insure that the air supply cannot replace air as fast as it
escapes when an automatic sprinkler operates.
Warning : When air supply style "D" is selected, the air
supply should be provided and installed by the sprinkler
contractor OUTSIDE of the TOTALPAC®X cabinet. Air
supply is NOT provided with the unit.

Page 2 of 10 TOTALPAC ®X
D
Integrated Fire Protection System
Air Supply - Preaction System
FM-076G-0-119A
2. Operation
2.1 Air supply Style "A" (refer to figure 2)
To apply air supply
Establish AC power for the air compressor by activating
the correspondent circuit breaker at the electrical
distribution panel. Start air compressor by activating the
compressor isolating switch (E15) located on the junction
box of the unit (see figure 2 in section E CONTROLS
SECTION).
If the air compressor motor fails to start or slows down
under load, shut the air compressor off. Check that the
supply voltage agrees with the motor nameplate.
To close air supply
Turn off the compressor isolating switch (E15) (see
figure 2 in section E CONTROLS SECTION).
To adjust air supply
The air compressor cut-off pressure switch (E2) is factory
set. This switch should not need any adjustment but if
necessary, follow the instructions below:
WARNING The adjustment screw of the cut-out/cut-in
differential pressure switch (E2) (small screw to the right)
is factory set. DO NOT CHANGE ITS SETTING. Any
unauthorized modification of this adjustment screw will
void the system warranty and may also prevent the system
from operating normally.
1. Remove the metal cover of the compressor air pressure
switch (E2).
2. To raise the cut-out pressure of the air compressor, turn
the cut-out adjustment screw (middle) half a turn
CLOCKWISE. Use the same method turning the cut-
out adjustment screw COUNTER-CLOCKWISE to lower
the air compressor cut-out pressure.
Figure 1 - Air pressure adjustment
INCREASE PRESSURE
LINE MOTOR LINE
Turn clockwise to increase
both cut-out and cut-in
pressure adjustment
Factory set
DO NOT CHANGE !
FM-072Q-0-109B
Note : Do not turn the cut-out adjustment screw (middle) all
the way down in one shot. Proceed by steps.
3. OPEN the main drain valve (D3) and let the pressure
drop until the air compressor restarts. Check pressure
reading on the system pressure gauge when the air
compressor stops again. Repeat until the desired
pressure is reached. Once all done, replace the metal
cover on the switch (E2).
2.2 Air supply Style "B" (refer to figure 3)
To apply air supply
1. Turn on upstream air supply.
2. OPEN APMD (air pressure maintenance device) input
valve (E6) by placing handle in line with valve body.
3. OPEN APMD output valve (E7) by placing handle in line
with the valve body.
4. OPEN bypass valve (E8) by placing handle in line with
valve body in order to accelerate filling of sprinkler
piping network by air pressure, while piping is initially
filled.
5. Once the piping network pressure is reached, CLOSE the
bypass valve (E8) by placing handle crossways to valve
body, and kept in this position.
Note: The bypass valve (E8) must be kept closed once the
system is filled with air.
To close air supply
1. CLOSE APMD output valve (E7) by placing handle
crossways to valve body.
2. CLOSE APMD input valve (E6) by also placing handle
crossways to the valve body.
3. Be sure bypass valve (E8) is CLOSED (handle crossways
to valve body).
To adjust air supply
1. Verify that APMD input valve (E6) and APMD output
valve (E7) are both OPEN (handle in line with the valve
body).
2. Be sure that bypass valve (E8) is CLOSED (handle
crossways to valve body) prior to performing this
operation.
3. Loosen lock nut of the APMD (E5) and turn pressure
adjustment nut clockwise to increase air pressure or
counter-clockwise to decrease pressure.
4. Tighten lock nut.
Note: Depending on site conditions, the internal filter of the
APMD may need maintenance on a regular basis. Refer to
Viking data sheet #127 for more details.
2.3 Air supply Style "D" (refer to figure 4)
To apply air supply
1. Turn on upstream air supply.
2. OPEN air shut-off valve (E6).
To close air supply
1. CLOSE bypass air shut-off valve (E6).

TOTALPAC ®X Page 3 of 10
Integrated Fire Protection System D
Air Supply - Preaction System
FM-076G-0-119A
3. Maintenance and inspection
IMPORTANT : Advise local authorities of the necessary
work over the fire protection equipment. In order to avoid
accidental water release, it is considered good practice to
completely close the main water supply valve (D1) while
doing maintenance work.
3.1 Air supply Style "A" (refer to figure 2)
The Style “A” air accumulator should be drained once a
year. The amount of moisture pumped into the system
and how quickly it accumulates is proportional to the
amount of humidity in the air and how long the compressor
is in operation.
To drain the air supply accumulator
At least once a year, OPEN air option drain valve (E12) until
all condensate water is drained from the air receiver.
CLOSE air option drain valve.
Safety valve pressure
A safety relief valve is provided on standard compressor
and is preset at the factory. Do not adjust or exceed
safety relief pressure other than those preset at the
factory.
WARNING The relief valve and outlet pipe of the air
compressor may become very hot during normal
operation. Do not touch the valve, compressor heads or
outlet piping until the compressor has been turned off and
allowed to cool.
WARNING Do not unscrew relief valve head entirely off
while the compressor is operating. Ejection of valve parts
could cause severe injury.
3.2 Air supply Style "B" (refer to figure 3)
The Viking Model D-2 APMD (air pressure maintenance
device) (E5) is a pressure regulator that automatically
reduces the supply air pressure to a pre-set requirement
when connected to a constantly maintained air supply
(plant air, external tanked air compressor or dry nitrogen
tank).
Determine the appropriate pressure to be maintained in the
system. Refer to table 2 or table 3 of the current section.
If adjustment is necessary, refer to paragraph 2.2 of the
current section.
To clean APMD (air pressure maintenance device)
1. Turn off external air supply.
2. CLOSE APMD output valve (E7) by placing handle
crossways to valve body.
3. CLOSE APMD input valve (E6) by also placing handle
crossways to the valve body.
NOTE : Never disconnect or disassemble the APMD (E5)
without closing those isolation valves.
4. Carefully loosen the union between the outlet of
APMD (E5) and the outlet isolation valve (E7) to relieve
pressure.
5. Remove and clean air pressure maintenance device
APMD (E5) filter. If admission filter is blocked, replace
with filter kit (part #03007 A).
Refer to Viking data sheet #127 for additional details.
3.3 Air supply Style "D" (refer to figure 4)
The air or nitrogen supply provided must be continuous,
clean, dry and oil free.
Determine the appropriate pressure to be maintained in the
system. Refer to table 2 or table 3 of the current section.

Page 4 of 10 TOTALPAC ®X
D
Integrated Fire Protection System
Air Supply - Preaction System
FM-076G-0-119A
Table 2 - Water pressure up to 175 PSI (1207 kPa)
System type Air supply
Style
Air
regulator
Compressor
start
Compressor
stop
Low air
supervisory
Low air
alarm
Double interlock
Electric/pneu-lectric
release
A n/a 15 PSI
(103 kPa)
20 PSI
(138 kPa)
12 PSI
(83 kPa)
10 PSI
(69 kPa)
B or D 20 PSI
(138 kPa) n/a n/a 12 PSI
(83 kPa)
10 PSI
(69 kPa)
Single interlock
FIRECYCLE ® III release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
23 PSI
(159 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
23 PSI
(159 kPa)
Double interlock
FIRECYCLE ® III release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
23 PSI
(159 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
23 PSI
(159 kPa)
Single interlock
SUREFIRE ® release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
23 PSI
(159 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
23 PSI
(159 kPa)
Double interlock
SUREFIRE ® release
A n/a 30 PSI
(207 kPa)
35 PSI
(241 kPa)
25 PSI
(172 kPa)
23 PSI
(159 kPa)
B or D 35 PSI
(241 kPa) n/a n/a 25 PSI
(172 kPa)
23 PSI
(159 kPa)
Table 3 - Water pressure from 175 PSI to 250 PSI (1207 kPa to 1724 kPa)
System type Air Supply
Style Air Regulator Compressor
Start
Compressor
Stop
Low Air
Supervisory
Low Air
Alarm
Double interlock
Electric/pneu-lectric
release
A n/a 15 PSI
(103 kPa)
20 PSI
(138 kPa)
12 PSI
(83 kPa)
10 PSI
(69 kPa)
B or D 20 PSI
(138 kPa) n/a n/a 12 PSI
(83 kPa)
10 PSI
(69 kPa)
Single interlock
FIRECYCLE ® III release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
43 PSI
(297 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
43 PSI
(297 kPa)
Double interlock
FIRECYCLE ® III release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
43 PSI
(297 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
43 PSI
(297 kPa)
Single interlock
SUREFIRE ® release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
43 PSI
(297 kPa)
B or D 55 PSI
(379 0 kPa) n/a n/a 45 PSI
(310 kPa)
43 PSI
(297 kPa)
Double interlock
SUREFIRE ® release
A n/a 50 PSI
(345 kPa)
55 PSI
(379 kPa)
45 PSI
(310 kPa)
43 PSI
(297 kPa)
B or D 55 PSI
(379 kPa) n/a n/a 45 PSI
(310 kPa)
43 PSI
(297 kPa)
Other manuals for TOTALPAC X
3
This manual suits for next models
1
Table of contents
Other FireFlex Protection Device manuals

FireFlex
FireFlex TOTALPAC X Installation guide

FireFlex
FireFlex TOTALPAC2 Manual

FireFlex
FireFlex TOTALPAC X Installation guide

FireFlex
FireFlex TOTALPAC N2 Installation guide

FireFlex
FireFlex TOTALPAC X Installation guide

FireFlex
FireFlex TOTALPAC N2 Installation guide

FireFlex
FireFlex TOTALPAC2 User manual

FireFlex
FireFlex TOTALPAC2 User manual