flowair T-box User manual

T-box
MANUAL
INSTRUKCJA
instrukcja obsługi / user manual / руководство пользователя / Gebruikershandleiding

66 67www.owair.com
TABLE OF CONTENTS
Installation.....................................................................................................66
Navigation.....................................................................................................66
Technical data.............................................................................................67
First run............................................................................................................68
Main screen ..................................................................................................70
Main menu ............................................................................................. 70
Time............................................................................................................71
Date.............................................................................................................71
Calendar...................................................................................................72
Language.................................................................................................75
Integrated units...................................................................................76
Reset...........................................................................................................76
Antifreeze ................................................................................................77
Leading sensor.....................................................................................77
Controller lock......................................................................................78
External gas detector ....................................................................... 78
Information menu..............................................................................79
BMS..............................................................................................................79
LEO fan heaters.......................................................................................... 80
LEO COOL fan cooler/heater ...........................................................84
LEO EL fan heaters................................................................................... 88
KM mixing chambers ...........................................................................92
LEO D destraticators...........................................................................98
ROBUR gas heaters .............................................................................. 100
ROBUR mixing chambers ...............................................................102
ELiS air curtains ..................................................................................... 106
ELiS DUO air curtain-fan heater combo units.................108
Slim air curtains ..................................................................................... 112
OXeN heat recovery units .............................................................. 116
OXeN EL heat recovery units ....................................................... 120
Cube Rooftop units..............................................................................123
Alarms............................................................................................................ 128
T-box controller has a built-in sensor for measuring air
temperature in the room. To ensure proper measure-
ments, the controller should be installed at a height of
approx. 1.5 m above the ground in a place with good air
circulation. Do not place it near heat sources, lighting, air
inlets, windows and door openings, etc.
If temperature sensor was chosen in a T-Box menu as
„installed in unit”, T-box controller can be mounted out
of area i.e. technical room.
INSTALLATION
12
return to previous screen with
save of changes
change of parameter value
change of unit group
return to previous screen without
save of changes
menu navigation
NAVIGATION

67www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
TECHNICAL DATAINSTALLATION
sterownik T-box
Ustawianie adresu
w modułach DRV**
moduł DRV
lub Cube
moduł DRV
Podłączanie sterownika T-box
do modułu DRV lub Cube
max. 800 m* screen
* Dotyczy łącznie wszystkich urządzeń podłączonych do sterownika T-box
** W przypadku urz ądzeń Cube adresy ustawia serwis podczas pierwszego uruchomienia
T-box controller
DRV module
addressing**
DRV module
or Cube
DRV module
T-box controller connection to
DRV module or Cube
pair twisted
max. 800 m* screen
* Applies to all devices connected to T-box controller in line
** In case of Cube devices addressing is beeing done by service during first startup
Name Description
Power supply 24 VDC
Way of control touch screen
Temperature adjustment
range +5 ÷ +45°C
Operating temperature range 0 ÷ +60°C
Temperature sensor built-in
Protection degree IP20
Installation on the wall
Casing ABS plastic, RAL 9003
Max. number of connected
units 31
Dimensions (HxWxD) 130 x 115 x 35 mm
DRV SW1 ADDRESS SETTING
DRV SW2 ADDRESS SETTING
In the case, when T-box in BMS network is the last device, SW1
switch should be set in T120 position.
Last DRV
in line
Others DRV
in line
SW 2
T120
SW 2
T120
1 2 4 8 16 Y1
1
0
Address: 1
1 2 4 8 16 Y1
1
0
Address: 2
1 2 4 8 16 Y1
1
0
Address: 3
1 2 4 8 16 Y1
1
0
Address: 4
1 2 4 8 16 Y1
1
0
Address: 5
1 2 4 8 16 Y1
1
0
Address: 6
1 2 4 8 16 Y1
1
0
Address: 7
1 2 4 8 16 Y1
1
0
Address: 8
1 2 4 8 16 Y1
1
0
Address: 9
1 2 4 8 16 Y1
1
0
Address: 1
0
1 2 4 8 16 Y1
1
0
Address: 11
1 2 4 8 16 Y1
1
0
Address: 1
2
1 2 4 8 16 Y1
1
0
Address: 1
3
1 2 4 8 16 Y1
1
0
Address: 1
4
1 2 4 8 16 Y1
1
0
Address: 1
5
1 2 4 8 16 Y1
1
0
Address: 1
6
1 2 4 8 16 Y1
1
0
Address: 19
1 2 4 8 16 Y1
1
0
Address: 20
1 2 4 8 16 Y1
1
0
Address: 21
1 2 4 8 16 Y1
1
0
Address: 22
1 2 4 8 16 Y1
1
0
Address: 23
1 2 4 8 16 Y1
1
0
Address: 24
1 2 4 8 16 Y1
1
0
Address: 25
1 2 4 8 16 Y1
1
0
Address: 26
1 2 4 8 16 Y1
1
0
Address: 27
1 2 4 8 16 Y1
1
0
Address: 28
1 2 4 8 16 Y1
1
0
Address: 29
1 2 4 8 16 Y1
1
0
Address: 30
1 2 4 8 16 Y1
1
0
Address: 31
1 2 4 8 16 Y1
1
0
Address: 17
1 2 4 8 16 Y1
1
0
Address: 18
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1
1 2 4 8 16 Y1
1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1 1 2 4 8 16 Y
1
1 2 4 8 16 Y1
1 2 4 8 16 Y
1
1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1 1 2 4 8 16 Y1
1 2 4 8 16 Y1

68 69www.owair.com
FIRST RUN
active language
Searching of connected units.
Selection of language Setting of date
Setting of time
DevicesTime
DataLanguage
13PM
August

69www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
12:55PM
Devices
Check that all devices have been found. If not, check:
• correctness of connection of the A-A, B-B communication signal,
• power connection of the device,
• if address have been set correctly; each device must have a dierent address set, (in Cube devices the address is set by
the service during the rst start-up)
• if the SW2 dipswitch on the last device in line is set to T120 position. (in Cube devices, the dipswitch is set by the
service during the rst start-up)
Setting of desired temperature.group of devices
water heater
gas heater
electric heater
destraticator
ventilation unit
rooftop units
water heater with
mixing chamber
gas heater with
mixing chamber
air curtain-fan heater
combo unit
air curtain
device no 8 in LEO
group
LEO
LEO KM
LEO
EL DUO
LEO
DELiS
OXeN
Cube
ROBUR
ROBUR
KM
fan cooler / heater
air curtain
LEO
COOL
Slim

70 71www.owair.com
MAIN SCREEN Main menu
long press turn on/off of the controller
long press main menu
short press units menu
alarms
setting of desired temperature time
setting antifreeze
date
setting
selection of
leading sensor
calendar controller lock
language selection
integrated units hardware
version
restore factory settings BMS settings
set temperature
measured temperature
date, time
settings lock active
BMS mode active
calendar active
calendar active - settings forced
the icon informs about changed position of
OXeN dampers, or about Cube device start-
up, the fans are suspended during this time.
Enter to the menu after entering the
password: 2014
long
press
external gas
detector
settings
4:05PM
12:55PM General settings

71www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Time Calendar
Date
Setting of time
Setting of date
• For each day you can set up to 20 on/o events,
• Start time of new event is also the end time of previous event,
• For each event you can set any temperature for units, in the
range of 5 – 45oC, For each event you can set for KM an
air ow and dampers
• opening degree, for OXeN an air ow,
• Events for each day can be set individually or they can be
copied from day, which was already set.
Activation of calendar is signalized on main screen via
following icons:
There were ad hoc set other parameters than
the settings programmed in the calendar:
• desired temperature,
• air ow for OXeN,
• the capacity or degree of opening of the KM
and Cube dampers
• system were OFF and was turned on (to turn
on the system press and hold for 2 s the
calendar icon on main screen),
• system were ON and was turned o (to turn
o the system press and hold for 2 s the
calendar icon on main screen).
Ad hoc settings stays as long as time of current
event in calendar. With start of next event,
units will operate according to programmed
settings.
calendar active – SYSTEM ON
calendar active – SYSTEM OFF
calendar active – settings forced.
Date
Time
13PM
August

72 73www.owair.com
Calendar – Adding the ON event
In given example SYSTEM will be turned on at 6:15 and
the units will maintain temp. 12oC.
SYSTEM WILL OPERATE USING CURRENT SETTINGS UNTIL
NEW EVENT WILL BE SET.
KM – additional settings for KM group
OXeN – additional settings for OXeN group
Cube – additional setting of Cube group.
activation/deactivation of calendar
moving to the next day
adding the event
event – system ON
copying events on the following days
event – system OFF
removing the events
Calendar
Weekly programer
New task
Weekly programer
Monday
4:15AM
7:00AM
11:30PM
4:00PM 6:00PM Tue
7:00AM
9:00AM
Cube

73www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
For OXeN it is possible to set an air ow in current event.
For KM it is possible to set an air ow and dampers
opening degree in current event.
When the dampers are closed (no ventilation), it
is possible to select the operating mode of the
fan after reaching desired temperature. Fan can
operate continuously or be turned o.
Weekly programer
OXeN
Weekly programer
KM

74 75www.owair.com
Calendar – Adding the OFF event
In given example units will be turned o at 16:00.
SYSTEM WILL BE TURNED OFF UNTIL THE NEXT EVENT,
ACCORDING TO CALENDAR SETTINGS.
Weekly programer
New task
4:00PM
Cube
It is possible to set airow and damper’s degree of
opening for a given zone.
When the therm mode is activated, the fans
of the Cube will work in thermostatic mode
- they will turn o after reaching the preset
temperature in the room.
When Auto mode is activated, the Cube’s
throttle will be adjusted automatically until
the set temperature is economically reached.
OK
ON
50%
ON
Therm
Auto
Therm
Auto
Calendar
Cube

75www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Calendar – Copying events
day from which events will be copied
day selected for copying events from PN day
day with already programmed operation
schedule – you can also copy here the events
from PN day
day without programmed operation schedule
Calendar – Removing events
Language
events selected
to remove conrmation of
events removal
active language
Language
Weekly programer
Delete task
Weekly programer
Copy
7:00AM
8:15PM
9:15AM9:00AM
10:00PM
4:00PM 4:15PM 7:00PM
Mon ThuTue
SatFr
Wed
Sun
Tue

76 77www.owair.com
Integrated units Reset
searching for units integrated with system
active
unit
deactivated unit
– not operating
Restore default settings.
Reset to default settings?
Yes No
Devices
long press displays the DRV software
System information
LEO M 01
CURTAIN MAIN
DRV-V 2.1
2.0.0-2d-....

77www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
The correction of sensor measurements is also possible.
Antifreeze Leading sensor
Automatic protection against too low temperature in
the room. When temperature in the room drops below
desired temperature, LEO and KM units are turned on:
• valves (if installed) opens,
• fan is turned on at 100% of eciency,
• KM dampers are closed, unit operates using recirculating air.
Units operate until the temperature in the roomis higher
of 1oC than antifreeze temperature, protecting the hall
against too low temperature inside and freeze of heating
medium in the exchanger.
active temperature sensor
leading sensor is the sensor built
in T-box controller
leading sensor is the local sensor. When it is
selected, operation of each unit is regulated
locally
Temperature sensor

78 79www.owair.com
External gas detector
The SYSTEM enables cooperation with an external CO2
sensor, humidity sensor, etc. - two-stage alarm signal.
The OXeN, KM and Cube capacity setpoint and the KM
and Cube damper opening will be changed automatical-
ly depending on the alarm signal.
The central unit must be connected to one DRV OXeN,
DRV KM control module or a controller in the Cube
device.
In the menu, indicate to which device the central unit is
connected.
In the example given, the control unit has been connect-
ed to DRV KM No. 7.
Controller lock
To activate the lock:
1. Set password
2. Conrm OK
Free 4-digit password can be set.
After returning to main screen and 30 s of inactivity,
controller will be locked automatically.
Gas detector
Controller lock

79www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
System information BMS – settings
Basic information about software and hardware version.
ID – setting unit adress: from 1 to 247
BAUD – setting data transmission speed: from 9600 to
230400 bit/s
Physical layer: Modbus RTU
Protocol: RS485
System information

80 81www.owair.com
LEO-type fan heaters
air ow setting – 3-steps
selection of operating mode
readings
destratication
short
press Operating modes
heating – heating medium valve is opened when
measured temperature is lower than desired
temperature
cooling – heating medium valve is opened when
measured temperature is higher than desired
temperature
ventilation – valve is constantly closed, fan
operates continuously at selected speed
Manual – fan operates with constant, selected
speed
Auto – automatic fan regulation depending on
desired and measured temperature
active operating mode
Operating modeSettings

81www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Operating modes Air ow setting
air ow setting during operation in manual mode Automatic air ow regulation according to desired and
measured temperature, manual air ow regulation is not
possible - inactive menu.
In MANUAL mode after reaching desired
temperature fan can operate continously on
selected step: 1, 2, 3 or be turned o - select OFF.
SettingsSettings
In AUTO mode after reaching desired temperature
fan can operate continously on selected step: 1, 2, 3
or be turned o - select OFF.
Airow AUTO

82 83www.owair.com
heater activated for operation in
destratication mode
activation of destratication mode
setting of temperature dierence (dierence
between temperature under the ceiling and
temperature in the occupied zone), at which
LEO heaters will be turned on
selection of heaters, which should operate in
destratication mode
LEO heaters can optionally operate in destratication
mode (only heaters installed under the ceiling). When
the measured temperature drops to the set temperature
only fan starts. When the heat under the ceiling is not
enough, and the temperature continues to decline
(-1oC from the setpoint) valve will open.
The heater must be equipped with T3 sensor (optional
equipment).
Destratication
DestraticationDestratication

83www.owair.com
POLSKIENGLISHРУССКИЙNEDERLANDS
Readings
Temperature
under the
ceiling
ON/OFF
valve
Temperature in
the room
To read temperatures near the unit, external tempera-
ture sensors PT-1000 must be connected to DRV control
module.
Readings

84 85www.owair.com
LEO COOL
Settings
LEO COOL
Operating mode
LEO
COOL
LEO COOL
-type fan cooler / heater
air ow setting – 3-steps
selection of operating mode
readings
short
press Operating modes
heating – heating medium valve is opened when
measured temperature is lower than desired
temperature
cooling – heating medium valve is opened when
measured temperature is higher than desired
temperature
ventilation – valve is constantly closed, fan
operates continuously at selected speed
Manual – fan operates with constant, selected
speed
Auto – automatic fan regulation depending on
desired and measured temperature
active operating mode
Other manuals for T-box
3
Table of contents
Other flowair Control Unit manuals