OPERATING IINSTRUCTIONS ((remote ccontrol vversions)
The gas valve has two control knobs ;
Turn the main burner control (shown on left hand
side of control valve) knob fully anti-clockwise.
Turn ignition knob (shown on right hand side of con-
trol valve) slightly left towards the ignition position
until reaching the stop, press down and hold for a
few seconds until pilot gas is flowing.
Continue pressing down the knob while turning fur-
ther to the left to activate the piezo spark, continue
to hold the knob down for a further 10 seconds after
the pilot has been lit. If the pilot does not light
repeat the previous steps.
Upon lighting the pilot and after the further 10 sec-
onds, release the knob and turn further to the left to the ON position. The main burner will light and be controlled
in accordance with the main burner control knob setting. Adjust the main burner
control knob to the desired setting.
If the pilot is extinguished during use of the fire, you must wait three minutes before
repeating the ignition procedure.
To turn the main burner OFF whilst keeping the pilot flame lit, turn the ignition con-
trol knob to the pilot position then only the pilot will remain lit.
To shut the fire off completely, press the ignition control knob down and continue
turning to the right from the pilot position to the OFF position.
A safety interlock prevents re-ignition of the pilot flame until the thermocouple has
cooled sufficiently to allow the magnetic valve unit to reset itself.
The remote control unit allows operation of the main burner between maximum and
pilot only setting. It does not turn the pilot on or off.
The remote control handset incorporates an inbuilt safety feature to prevent the
main burner being activated or turned up accidentally. It is necessary to press but-
ton 1 and 2 (see illustration) simultaneously to turn the fire up.
To turn the fire down press button 3 only.
REPLACING TTHE BBATTERIES ((remote ccontrol vversions oonly)
Handset - Remove cover from rear of handset and insert 1 x ‘PP3’ (9 volt) battery - Replace cover
Appliance - Ensure aappliance iisooff aand ccool. Remove cover from top of receiver box. The cover is protected by
reflective foil, and located towards the right hand side, underneath the burner unit. Insert 4 x ‘AA’ (1.5 volt) bat-
teries - Replace cover.
FLUE SSPILLAGE MMONITORING SSYSTEM
This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason
then several reasons may be suspected. If a door or window has been opened creating a draught, then pilot dis-
turbance could be the problem, and removal of the draught should resolve this. The fire can then be re-lit in
accordance with the previous section. A sealing grommet may have been ommited when the fire was installed,
and the original installer should be called to check this, the gas pressure and pipework.
If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF,
call in your installer to check the flue and ventilation and carry out any remedial work required. DO NOT allow
the appliance to be used until the flue system is passed as safe.
CLEANING
Before carrying out any of the following operations, ensure that the fire is OFF and completely cold. Debris that
may form on the firebed should be periodically removed by a competent person. Large deposits could indicate
deterioration of the flue. This should be repaired by a competent person, and the fire serviced before further use.
3
11
22
33
5.1
6.0
7.0
8.0