Frecon FR200 Series User manual

FR200 Series Vector control inverter
- 1 -
FR200 series inverters fast installation and commissioning guide
Step 1. Checking the inverter model No.
FR200□-4T-7.5G/011PB
Master series code of
Product:
FR200: Vector control
inverter
Input voltage:
2: 220V(-15%~+30%)
4: 380V(-15%~+30%)
Input voltage phases:
S:Single-phase
T:Three-phase
Industry-specific series
code:
None:Standard Machine
A~Z:Industry-specific
retention
Brake unit:
None: No Braking Unit
B: Built-in brake unit(30kW
following built,37 ~ 75kW optional
built,No built above 90kW)
Adaptable Motor (kW)And Type of
Motor:7.5G:7.5kW(General type)
011P:11kW(Fan pump type)
Figure 1 Produce Model No. Naming Rule
Step 2. Wirings
By step 1 to check and confirm that the purchased inverter is what user need, and
then wirings as below:
1. Main circuit wiring
L1
L2
L3
U
V
W
MCCB
M
Inverter
Power
(+) PB
Braking Resistor(Optional spares)
Figure 2 Main Circuit Wirings
Terminal marks
Designation and function of terminals.
R/L1、S/L2、T/L3
AC power input terminals for connecting to 3-phase AC380V power
supply.
U/T1、V/T2、W/T3
AC output terminals of inverter for connecting to 3-phase induction
motor.
(+)、(-)
Positive and negative terminals of internal DC bus.
PB
Positive and negative terminals of internal DC bus. Connecting
terminals of braking resistor. One end connected to + and the otherto
PB.
Grounding terminal.
2. Control circuit wirings
Different control circuit wirings for different applications, for FRECON product
quick-menu, here take some normal-used wirings as example below:

FR200 Series Vector control inverter
- 2 -
DI1
+24V
DI2
PLC
DI3
COM
DI4
DI5
COM
DI6
Y1 Y2
+10V R1A R1B R1C
R2A R2B R2C
AO1
AI1
GND AI2 485+
AI3 485-
PE
DI7/HI
AO2
GND
Figure 3 FR200 series Control Terminal Diagram
2.1 Frequency given by keypad potentiometer, start or stop the machine controlled by
RUN and STOP button on keypad. Control circuits no need to be wired, directly work with
power on.
2.2 Frequency given by external potentiometer, start or stop the machine controlled by
external switch, Control circuit wirings as below:
Inverter
DI1
COM
AI1
+10V
FWD/STOP
Potentiometer
GND
DI2
REV/STOP
Figure 4 Control terminal wirings
Parameters need to be set as below:
F01.01
Main frequency source given mode
2: AI1
2
F02.00
Start/stop command source
selection
1: External terminal (LED light turn on)
1
2.3 Frequency given by PID, start/stop controlled by external switch, take constant
pressure water supply as an example, control wirings as below:
DI2
+10V
AI1
GND
REV/STOP
400R
Resistance type
pressure gauge
Inverter
DI1
FWD/STOP
COM
Figure 5 Control Terminal Wirings
Parameters need to be set as below:

FR200 Series Vector control inverter
- 3 -
F01.01
Main frequency source given mode
6: Process PID
6
F02.00
Start/stop command source selection
1: External terminal (LED light
turn on)
1
F13.01
PID Digital Given
0.0~100.0%
25.0%
F13.08
Proportional Gain Kp1
0.0~100.0
1.0
F13.09
Integration Time Ti1
0.01~10.00s
0.10s
3. Integrated Wirings Diagram
In many cases, besides the above control wirings, inverter’s fault signal and frequency signal
need to be transferred to upper machine, control signal output and fault reset function added
base on figure 2.2 application mode, inverter’s integrated wirings diagram as below:
DI1
FWD/STOP Inverter
DI2
REV/STOP
DI3
Fault reset
AI1
+10V
Potentiometer
GND
L1
L2
L3
U
V
W
MCCB
M
Power
(+) P
B
Braking resistor(Optional spare)
AO
1
GN
D
Analog
voltmeter
R1A
R1B
R1C Fault output
GND
Figure 6 Integrated Wirings
Step 3 Operations and Display Interface Introduction
Operation panel is a Human-Machine-Interface (HMI), which can change the inverter
function parameter, monitor the inverter work situation, control the inverter run/stop, etc.
The appearance and functional area as below:

FR200 Series Vector control inverter
- 4 -
Figure 7 Operation panel diagram
3.1 Operation panel button and potentiometer function
There are 8 buttons and 1 analog potentiometer, functions of every button as table 1.
Table 1 Operation Panel Buttons Function Table
Symbol
Name
Function
Escape
Enter or exit Level I menu
Enter
Enter the menu interfaces level by level, and
confirm the parameter setting
Increment
Increase data or function code
Decrement
Decrease data or function code
Shift
Select the displayed parameters in turn in the stop
or running state, and select the digit to be modified
when modifying parameters
Multifunction
Perform function switchover (such as jog run and
quick switchover of
command source or direction) according to the
setting of F16.00
potentiometer
With the same function as AI1/AI2
Run
Start the inverter in the keypad control mode
Stop/Reset
Stop the inverter when it is in the running state and
perform the reset operation when it is in the fault
state. The functions of this key are restricted in
F16.01.
+
Key combinations
The inverter will free stop when the run and stop
key are pressed simultaneously
3.2 Quick-menu (user customized parameters) instruction
For ease of normal-used parameters quick setting, FR series inverters software
version higher than V1.07, factory menu mode changed to quick-menu (F00.01=1),
default quick parameters refer to schedule.
Display difference between quick menu and basic menu (F00.01=0) is 2nd grade, for
ease of user distinguish the difference and switch method as below:

FR200 Series Vector control inverter
- 5 -
Menu
Mode
Quick Menu
Basic Menu
Display
Difference
(2nd)
F01.01.
Function code last
digit with decimal point, no flash.
Function code last digit no
decimal point, flash.
Functional
Distinction
1、Press or , set
function code switch up or down
according to F17 group.
2、Press can’t go back
1st grade menu.
1、Press or , switch up or
down according to order of function code
01, 02…
2、Press can go back to 1st grade
menu.
(
F01
)
Inter-switch
Method 1, switch to basic menu
by changing F00.01=0.
Method 2, when show 2nd menu,
keep press button,
auto-switch to basic menu.
Method 1, switch to quick menu by
changing F00.01=1.
Method 2, when show 2nd menu, keep
press button, auto-switch to
quick-menu.
If the default quick-parameters can’t meet the user demand, user can self-define
the quick-parameters according to the actual situation; detailed method is to change F17
group function code.
F17 group supply max 30 groups of user customized parameters, F17 group
parameter show value 00.00, means the user function code is null. When entering
user-defined parameter mode, displayed function code defined by F17-00~F17-29, order
keep the same with F17 group, skip on 00.00. Two digits in left side of decimal point mean
function code group, right side mean the position of the function code group. For example:
05.15 means F05.15. F00~F20 group corresponds to decimal point left side two digits
00~20, U00 and U01 group corresponds to 48 and 49. Set as 21~46 mean the user
function code null. When right side 2 digits per group more than setting group function
code number, also mean user function code null.
Appendix:shortcut menu factory parameter
Param.
Parameter Name
Setting Range
Default
Attr
F00.00
Setting of User
Password
0~65535
0
×
F00.01
Display of
Parameters
0: Display all parameters
1
×
1: Only display F00.00, F00.01 and
user-defined parameters
F17.00~F17.29
2: Only display A0-00, A0-01, and the
parameters different with factory default
F00.03
G/P type display
0: G type (constant torque load)
0
×
1: P type (variable torque load
e.g. fan and pump)
F01.01
Master Frequency
Command Source
0:Master digital setting (F01.02)
1
×
1: keypad potentiometer
2: Analog input AI1
3: Communication
4: Multi-reference
F01.01

FR200 Series Vector control inverter
- 6 -
5: PLC
6: Process PID output
7: X7/HI pulse input
8:AI2
9:AI3
F02.00
Run command
0: Keypad control (LED off)
0
×
1: Terminal control (LED on)
2: Communication control (LED
blinking)
F02.01
Running direction
0: Forward
0
△
1: Reverse
F02.12
Stop mode
0: Ramp to stop
0
×
1: Coast to stop
F03.00
Accel time 0
0.0~6000.0s
15.0s
△
F03.01
Decel time 0
0.0~6000.0s
15.0s
△
F04.00
Function of
terminal DI1
0: No function
1
×
F04.01
Function of
terminal DI2
1: Running forward (FWD)
2
×
F04.02
Function of
terminal DI3
2: Running reverse (REV)
7
×
F04.03
Function of
terminal DI4
3: Three-wire control
13
×
F05.02
Relay 1 output
function
2: Fault output
2
×
F08.01
Power rating of
motor 1
0.1~1000.0kW
Model
defined
×
F08.02
Rated voltage of
motor 1
60~660V
Model
defined
×
F08.03
Rated current of
motor 1
0.1~1500.0A
Model
defined
×
F08.04
Rated frequency
of motor 1
20.00~Fmax
Model
defined
×
F08.05
Rated speed of
motor 1
1~30000
Model
defined
×
F08.30
Autotuning of
motor 1
0: No autotuning
0
×
1: Static autotuning of async motor
2: Rotary autotuning of async motor
F11.10
Protection action
1
Unit's place: Bus undervoltage
03000
×
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to run

FR200 Series Vector control inverter
- 7 -
3: Fault protection disabled
Ten's digit :Power input phase
Loss (Err09)(Same as unit's place )
Hundred's digit :Power output
phase loss(Err10)(Same as unit's place )
Thousand's digit:Motor overload
(Err11)(Same as unit's place )
Ten thousand's digit:Inverter
overload(Err11)(Same as unit's place )
F13.00
PID setting
0: F13.01 digital setting
0
×
1:keypad potentiometer
2:AI1
3: Communication
4:Multi-Reference
5: DI7/HI pulse input
6: AI2
7:AI3
F13.01
PID digital setting
0.0~100.0%
50.0%
△
F13.02
PID feedback
0:AI1
0
×
1:AI2
2: Communication
F13.08
Proportional gain
Kp1
0.0~100.0
1.0
△
F13.09
Integration time
Ti1
0.01~10.00s
0.10s
△

FR200 Series Vector control inverter
- 8 -
Preface
Thank you for choosing FRECON developed and produced FR200 series
vector control inverter.
FR200 series vector control inverter is mainly positioned as a high-end market for OEM
customers and the specific requirements of fan and pump load applications,its flexible design, both
embedded SVC and VF control in one,can be widely used for speed control accuracy, torque
response speed, low-frequency output characteristics and other situations with higher requirements.
This user manual supplies a detailed description of FR200 series vector control inverter includes
product characterization, structural features, parameter setting, operation and commissioning,
inspection maintenance and other contents. Be sure to carefully read through the safety precautions
before use, and use this product on the premise that personnel and equipment safety is ensured.
IMPORTANT NOTES
◆To illustrate the details of the products,pictures in this manual based on products with outer
casing or safety cover being removed. When using this product, please be sure to well install
outer casing or covering by the rules, and operating in accordance with the manual contents.
◆The illustrations this manual for illustration only andmay vary with different products you have
ordered.
◆The company is committed to continuous improvement of products, product features will
continue to upgrade, the information provided is subject to change without notice.
◆If you are using have questions, please contact our regional agents or our customer service
center. Customer Service Tel 0755 -33067999.
◆The company's other products please visit our website. http://www.frecon.com.cn

FR200 Series Vector control inverter
- 9 -

FR200 Series Vector control inverter
- 10 -
Contents
Preface.......................................................................................................................................................... - 8 -
Contents..................................................................................................................................................... - 10 -
Chapter 1 Safety Precautions ............................................................................................................... - 12 -
1.1 Safety Considerations ................................................................................................................... - 12 -
1.2 Precautions..................................................................................................................................... - 14 -
Chapter 2 Product Information............................................................................................................. - 16 -
2.1 Nameplate information.................................................................................................................. - 16 -
2.2 Information of FR200 Product Model........................................................................................... - 17 -
2.3 Technical Features of FR200........................................................................................................ - 18 -
2.4 Parts Drawing................................................................................................................................. - 20 -
2.5 Configuration, Mounting Dimensions and Weight...................................................................... - 21 -
2.6 Flange mounting dimensions........................................................................................................ - 23 -
2.7 External Dimensions of Keypad ................................................................................................... - 25 -
2.8 18.5-75kW Keypad plate open operation.................................................................................... - 26 -
Chapter 3 Installation and Wiring......................................................................................................... - 27 -
3.1 Installation Environment................................................................................................................ - 27 -
3.2 Installation Direction, Space and Cooling.................................................................................... - 27 -
3.3 Fixed manner.................................................................................................................................. - 29 -
3.4 Remove & Mount Keypad and Cover.......................................................................................... - 30 -
3.5 Dust cover installation and removal(Optional accessories)................................................. - 33 -
3.6 Configuration of Peripheral Devices............................................................................................ - 34 -
3.7 Wiring way....................................................................................................................................... - 38 -
3.8 Terminal Configuration................................................................................................................... - 39 -
3.9 EMI Solutions.................................................................................................................................. - 48 -
Chapter 4 Operation and display.......................................................................................................... - 50 -
4.1 Introduction of Keypad................................................................................................................... - 50 -
4.2 Viewing and Modifying Function Codes...................................................................................... - 52 -
4.3 Viewing Status Parameters........................................................................................................... - 52 -
4.4 Motor Auto-tuning........................................................................................................................... - 53 -
4.5 Password Setting........................................................................................................................... - 53 -
4.6 Keypad lock .................................................................................................................................... - 53 -
4.7 Shortcut menus function code description.................................................................................. - 54 -
Chapter 5 List of Parameter................................................................................................................... - 55 -
5.1 Standard Function Parameters..................................................................................................... - 56 -
Chapter 6 Specification of Parameters............................................................................................... - 78 -
Group F00 System Parameters.......................................................................................................... - 78 -
Group F00 Frequency command........................................................................................................ - 81 -
Group F02 Start/Stop Control Start/Stop Control.............................................................................. - 84 -
Group F03Accel/Decel Parameters................................................................................................... - 87 -
Group F04 Digital Input........................................................................................................................ - 89 -
Group F05 Digital Output..................................................................................................................... - 95 -
Group F06Analog and Pulse Input.................................................................................................... - 99 -
Group F07Analog and Pulse Output............................................................................................... - 103 -

FR200 Series Vector control inverter
- 11 -
Group F08 Parameters of Motor 1....................................................................................................- 104 -
Group F09 V/f Control Parameters of Motor 1.................................................................................- 105 -
Group F10 Vector Control Parameters of Motor 1 ..........................................................................- 108 -
Group F11 Protection Parameters....................................................................................................- 110 -
Group F12 Multi-Reference and Simple PLC Function..................................................................- 114 -
Group F13 Process PID.....................................................................................................................- 118 -
Group F14 Swing Frequency, Fixed Length, Count and Wakeup.................................................- 120 -
Group F15 Communication Parameters...........................................................................................- 123 -
Group F16 Keys and Display of Keypad Parameters.....................................................................- 124 -
Group F17 User-defined Display Parameters..................................................................................- 125 -
Group U00 Status Monitoring ............................................................................................................- 126 -
Group U01 Fault Record....................................................................................................................- 127 -
Chapter 7 Maintenance and Troubleshooting..................................................................................- 129 -
Chapter 8 Maintenance and Inspection.............................................................................................- 133 -
8.1 Inspection.......................................................................................................................................- 133 -
8.2 Maintenance..................................................................................................................................- 134 -
Appendix A: Modbus Communication Protocol..............................................................................- 136 -
Appendix B: Accessories.....................................................................................................................- 142 -
B.1 Braking Resistor...........................................................................................................................- 142 -
B.2 Uploading and Downloading Module.........................................................................................- 142 -

FR200 Series Vector control inverter
- 12 -
Chapter 1 Safety Precautions
Safety Precautions
Safety signs in this manual:
DANGER:indicates the situation in which the failure to follow operating requirements may result
in fire or serious personal injury or even death.
CAUTION: indicates the situation in which the failure to follow operating requirements may cause
moderate or slight injury and damage to equipment.
Users are requested to read this chapter carefully when installing, commissioning and repairing
this product and perform the operation according to safety precautions as set forth in this chapter
without fail. FRECON will bear no responsibility for any injury and loss as a result of any violation
operation.
1.1 Safety Considerations
The use phase
Safety
class
Considerations
Before
Installation
Danger
◆Do not install the product if the package is with water, or
component is missing or broken.
◆Do not install the product if the label on the package is not
identical to that on the inverter.
Caution
◆Be careful of carrying or transportation. Risk of devices
damage.
◆Do not use damaged product or the inverters missing
component .Risk of injury.
◆Do not touch the parts of control system with bare hands. Risk
of ESD hazard.
Installation
Danger
◆Installation base shall be metal or other non-flammable
material. Risk of fire.
◆Do not install inverter in an environment containing explosive
gases, otherwise there is danger of explosion.
◆Do not unscrew the fixing bolts, especially the bolts with red
mark.
Caution
◆Do not leave cable strips or screws in the inverter. Risk of
inverter damage.
◆Install the product at the place with less vibration and no direct
sunlight.
◆Consider the installation space for cooling purpose when two
or more inverters are placed in the same cabinet.
Wiring
Danger
◆Wiring must be performed by authorized and qualified
personnel. Risk of danger.
◆Circuit-breaker should be installed between inverter and the
mains. Risk of fire.
◆Make sure the input power supply has been completely
disconnected before wiring. Failure to comply may result in
personnel injury and/or equipment damage.
◆Since overall leakage current of this equipment may be bigger
than 3.5mA, for safety's sake, this equipment and its associated
motor must be well grounded so as to avoid risk of electric
shock.
◆Never connect the power cables to the output terminals (U/T1、

FR200 Series Vector control inverter
- 13 -
V/T2、W/T3) of the AC drive. Pay attention to the marks of the
wiring terminals and ensure correct wiring. Failure to comply will
result in damage to the AC drive.
◆Install braking resistors at terminals (+)and PB only. Failure to
comply may result in equipment damage.
◆AC 220V signal is prohibited from connecting to other
terminals than control terminals R1A、R1B、R1C andR2A、R2B、
R2C. Failure to comply may result in equipment damage.
Caution
◆Since all adjustable frequency AC drives from FRECON have
been subjected to hi-pot test before delivery, users are
prohibited from implementing such a test on this equipment.
Failure to comply may result in equipment damage.
◆Signal wires should to the best of the possibility be away from
main power lines. If this cannot be ensured, vertical
cross-arrangement shall be implemented, otherwise interference
noise to control signal may occur.
◆If motor cables are longer than 100m, it is recommended
output AC reactor be used. Failure to comply may result in faults.
Before
Power-on
Danger
◆Inverter shall be power-on only after the front cover is
assembled. Risk of electrical hazard.
Caution
◆Verify that the input voltage is identical to the rated voltage of
product, correct wiring of input terminals R/L1, S/L2, and T/L3
and output terminals U/T1, V/T2, and W/T3, wiring of inverter
and its peripheral circuits, and all wires should be in good
connection. Risk of inverter damage.
After Power-on
Danger
◆Do not open the cover after power.Rick of electrical hazard.
◆Do not touches any input/output terminals of inverter with bare
hands. Rick of electrical hazard.
Caution
◆If auto tuning is required, be careful of personal injury when
motor is running. Risk of accident.
◆Do not change the defaults of parameters. Risk of devices
damage.
During
Operation
Danger
◆Non-professionals shall not detect signals during operation.
Risk of personal injury or device damage.
◆Do not touch the fan or the discharging resistor to check the
temperature. Failure to comply will result in personal burnt.
Caution
◆Prevent any foreign items from being left in the devices during
operation. Risk of device damage.
◆Do not control start/stop of inverter by ON/OFF of contactor.
Risk of device damage.
Maintenance
Danger
◆Maintenance and inspection can only be performed by
professionals . Risk of personal injury.
◆Maintain and inspect devices after power is off. Risk of
electric hazard.
◆Repair or maintain the AC drive only ten minutes after
the AC drive is powered off. This allows for the residual
voltage in the capacitor to discharge to a safe value.
Failure to comply will result in personal injury.
◆All pluggable components can be inserted or pulled out
only when power has been turned off.
◆Set and check the parameters again after the AC drive
is replaced.

FR200 Series Vector control inverter
- 14 -
1.2 Precautions
1.2.1 Motor Insulation Inspection
When the motor is used for the first time or when the motor is reused after being kept, or when
periodical inspection is performed, insulation inspection shall be conducted with motor so as to avoid
damaging the inverter because of the insulation failure of the motor windings. The motor wires must be
disconnected from the inverter during the insulation inspection. It is recommended to use the 500V
mega meter, and the insulating resistance measured shall be 5MΩ at least.
1.2.2 Motor Thermal Protection
If the motor rating does not match that of the inverter, especially when the rated power of the
inverter is higher than that of the motor, adjust motor protection parameters in the inverter or install
thermal relay to protect motor.
1.2.3 Operating with the Frequency Higher than Grid Power Frequency
Output frequency of FR200 is 0.00Hz~600.00Hz. If FR200 is required to operate above 50.00Hz,
please take the endurance of mechanical devices into consideration.
1.2.4 Mechanical Vibrations
Inverter may encounter mechanical resonance point of the load device at certain output
frequencies which can be avoided by setting the skip frequency parameters of the inverter.
1.2.5 Motor Heat and Noise
Since output voltage of inverter is PWM wave and contains a certain amount of harmonics, so
that the temperature, noise and vibration of the motor will be higher than those when the inverter runs
at grid power frequency.
1.2.6 Voltage-sensitive device or capacitor on output side of the AC drive
Do not install the capacitor for improving power factor or lightning protection voltage-sensitive
resistor on the output side of the AC drive because the output of the AC drive is PWM wave.
Otherwise, the AC drive may suffer transient overcurrent or even be damaged.
1.2.7 Contactor at the I/O terminal of the AC drive
When a contactor is installed between the input side of the AC drive and the power supply, the AC
drive must not be started or stopped by switching the contactor on or off. If the AC drive has to be
operated by the contactor, ensure that the time interval between switching is at least one hour since
frequent charge and discharge will shorten the service life of the capacitor inside the AC drive.
When a contactor is installed between the output side of the AC drive and the motor, do not turn off the
contactor when the AC drive is active. Otherwise, modules inside the AC drive may be damaged.
1.2.8 Applied with the Rated Voltage
Apply FR200 with the rated voltage. Failure to comply will damage inverter. If required, take a
transformer to boost or step-down voltage.
1.2.9 Do Not Apply a 3-Phase Input Inverter to 2-Phase Input Applications
Do not apply a 3-phase input FR inverter to 2-phase input applications. Otherwise, it will result in
faults or damage inverter.
1.2.10 Lightning Protection
FR200 has integrated lightning over-current protection device which has certain self-protection
capacity against the lightning. Additional protection devices have to be installed between inverter
and power supply in the area where lightning occurs frequently.
1.2.11 Altitude De-rating
In places where the altitude is above 1000 m and the cooling effect reduces due to thin air, it is
necessary to de-rate the AC drive. Contact FRECON for technical support.
1.2.12 some special usages
If wiring that is not described in this manual such as common DC bus is applied, contact the agent
or FRECON for technical support.
1.2.13 Cautions for Inverter Disposal
The electrolytic capacitors on the main circuit and PCBA may explode when they are burnt.
Emission of toxic gas may be generated when the plastic parts are burnt. Please dispose inverter as
industrial wastes.
1.2.14 Adaptable Motor
The standard adaptable motor is adaptable four-pole squirrel-cage asynchronous induction motor
or PMSM. For other types of motor, select a proper AC drive according to the rated motor current.
The cooling fan and rotor shaft of non-variable-frequency motor are coaxial, which results in
reduced cooling effect when the rotational speed declines. If variable speed is required, add a more
powerful fan or replace it with variable-frequency motor in applications where the motor overheats
easily.

FR200 Series Vector control inverter
- 15 -
The standard parameters of the adaptable motor have been configured inside the AC drive. It is
still necessary to perform motor auto-tuning or modify the default values based on actual conditions.
Otherwise, the running result and protection performance will be affected.
The AC drive may alarm or even be damaged when short-circuit exists on cables or inside the
motor. Therefore, perform insulation short-circuit test when the motor and cables are newly installed or
during routine maintenance. During the test, make sure that the AC drive is disconnected from the
tested parts.

FR200 Series Vector control inverter
- 16 -
Chapter 2 Product Information
2.1 Nameplate information
Fig.2-1 Nameplate information
Model Explanation
Model show on product nameplate contains information below
FR200□-4T-7.5G/011PB
Master series code of
Product:
FR200: Vector control
inverter
Input voltage:
2: 220V(-15%~+30%)
4: 380V(-15%~+30%)
Input voltage phases:
S:Single-phase
T:Three-phase
Industry-specific series
code:
None:Standard Machine
A~Z:Industry-specific
retention
Brake unit:
None: No Braking Unit
B: Built-in brake unit(30kW
following built,37 ~ 75kW optional
built,No built above 90kW)
Adaptable Motor (kW)And Type of
Motor:7.5G:7.5kW(General type)
011P:11kW(Fan pump type)
Fig.2-2 Model Explanation

FR200 Series Vector control inverter
- 17 -
2.2 Information of FR200 Product Model
Table 2-1 FR200 Product model and technical data
Model No.
Power
capacity
KVA
Rated
Input current
A
Rated output
current
A
Applicable motor
kW HP
3-Phase:220V,50/60Hz Range:-15%~+30%
FR200-2T-0.7B
3.5
5.3
4.2
0.75
1
FR200-2T-1.5B
5.5
8.5
7.5
1.5
2
FR200-2T-2.2B
7.5
11.6
9.5
2.2
3
FR200-2T-4.0B
11.7
18
17
3.7、4
5
FR200-2T-5.5B
17.3
26.5
25
5.5
7.5
FR200-2T-7.5B
22
33.5
32
7.5
10
FR200-2T-011B
31
47.5
45
11
15
FR200-2T-015B
41.5
63
60
15
20
FR200-2T-018
52
79
75
18.5
25
FR200-2T-018B
FR200-2T-022
63
96
91
22
30
FR200-2T-022B
FR200-2T-030
77.5
118
112
30
40
FR200-2T-030B
FR200-2T-037
104
158
150
37
50
FR200-2T-037B
FR200-2T-045
122
185
176
45
60
FR200-2T-055
145
221
210
55
70
FR200-2T-075
173
263
250
75
100
3-Phase:380V,50/60Hz Range:-15%~+30%
FR200-4T-0.7G/1.5PB
1.5
3.4
2.5
0.75
1
FR200-4T-1.5G/2.2PB
3
5.0
4.2
1.5
2
FR200-4T-2.2GB
4
5.8
5.5
2.2
3
FR200-4T-4.0G/5.5PB
6
11
9.5
3.7、4
5
FR200-4T-5.5G/7.5PB
8.9
14.6
13
5.5
7.5
FR200-4T-7.5G/011PB
11
20.5
17
7.5
10
FR200-4T-011G/015PB
17
26
25
11
15
FR200-4T-015G/018PB
21
35
32
15
20
FR200-4T-018G/022PB
24
38.5
37
18.5
25
FR200-4T-022G/030PB
30
46.5
45
22
30
FR200-4T-030G/037PB
40
62
60
30
40
FR200-4T-037G/045P
57
76
75
37
50
FR200-4T-037G/045PB
FR200-4T-045G/055P
69
92
91
45
60
FR200-4T-045G/055PB
FR200-4T-055G/075P
85
113
112
55
70
FR200-4T-055G/075PB
FR200-4T-075G/090P
114
157
150
75
100
FR200-4T-075G/090PB
FR200-4T-090G/110P
134
160*
176
90
125
FR200-4T-110G/132P
160
190*
210
110
150
FR200-4T-132G/160P
192
232*
253
132
175
FR200-4T-160G/185P
231
282*
304
160
210
FR200-4T-185G/200P
240
326*
350
185
250
FR200-4T-200G/220P
250
352*
377
200
260
FR200-4T-220G/250P
280
385*
426
220
300
FR200-4T-250G/280P
355
437*
470
250
330
FR200-4T-280G/315P
396
491*
520
280
370
FR200-4T-315G/355P
445
580*
600
315
420

FR200 Series Vector control inverter
- 18 -
FR200-4T-355G/400P
500
624*
650
355
470
FR200-4T-400G/450P
565
690*
725
400
530
FR200-4T-450G/500P
623
765*
800
450
600
FR200-4T-500G/560P
670
835*
860
500
660
FR200-4T-560G/630P
770
960*
990
560
750
FR200-4T-630G/710P
855
1050*
1100
630
840
means FR200-2T-045 and FR200-4T-90G/110P or above is provided with an external-mounted DC
reactor in shipment as default
2.3 Technical Features of FR200
Table 2-2 Technical features of FR200
Project
Specifications
Power input
Rated input
voltage (V)
3-phase 380 V (-15%~+30%)
Rated input
current (A)
See table 2-1
Rated input
frequency
(Hz)
50Hz/60Hz,tolerance±5%
Power output
Applicable
motor(kW)
See table 2-1
Rated output
current(A)
See table 2-1
The
maximum
output voltage
(V)
0~rated input voltage, error<±3%
The
maximum
output
frequency
(Hz)
0.00~600.00 Hz,unit0.01Hz
Control
characteristics
V/f patterns
V/f control
Sensor-less vector control 1
Sensor-less vector control 2
Speed range
1:50 (V/f control)
1:100 (sensor-less vector control 1)
1:200(sensor-less vector control 2)
Speed
accuracy
±0.5% (V/f control)
±0.2% (sensor-less vector control 1 & 2)
Speed
fluctuation
±0.3% (sensor-less vector control 1 & 2)
Torque
response
< 10ms (sensor-less vector control 1 & 2)
Starting
torque
0.5Hz: 180% (V/f control, sensor-less vector control 1)
0.25Hz: 180% (sensor-less vector control 2)
Basic functions
Carrier
frequency
0.7kHz~16kHz
Overload
capability
G Model:150% Rated Current 60s,180% Rated Current
10s,200% Rated Current 1s.
P Model:120% Rated Current 60s,145% Rated Current
10s,160% Rated Current 1s.
Torque boost
Automatic torque boost;Manual torque boost 0.1%~
30.0%
V/F Curve
Three ways:Three ways: straight; multi-point type; N
Th-type V / F curve(1.2 Th -type、1.4 Th -type、1.6 Th

FR200 Series Vector control inverter
- 19 -
-type、1.8 Th -type、2 Th -type)
Acceleration
and
deceleration
Curve
Line or curve acceleration and deceleration mode.
Four kinds of acceleration and deceleration time,Ramp
Time Range :0.0~6000.0s
DC brake
DC brake start frequency: 0.00~600.00Hz
DC brake time:0.0s~10.0s
DC brake current:0.0%~150.0%
Basic functions
Jog brake
Jog frequency range:0.00Hz~50.00Hz.
Jog deceleration time: 0.0s~6000.0s.
Simple PLC、
Multi-speed
Through the built-in PLC or control terminal to achieve
up to 16 speed running
Built-in PID
Facilitate the realization of process control loop control
system
Automatic
voltage
adjustment
(AVR)
When the grid voltage changes, can automatically
maintain a constant output voltage
Fast current
limit function
Minimize over current fault protection inverter running
Over voltage
Over current
System automatically limits of current and voltage during
operation to prevent frequent
Run
Command
source
Given the control panel, control terminal, serial
communication port given.
Frequency
given
Sevkeinradlswoafysfrtoeqsuweintcchy sources: digital
setting, keyboard potentiometer setting, analog
Voltage, given analog current reference pulse is given,
the serial port is given, multi-speed given, PLC is given,
the process PI D reference. There are several ways to
switch
Input terminal
7 Switch input terminals, one way to make high-speed
pulse input.
3-channel analog inputs, including 2-way 0~10V / 0~
20mA voltage and current options,
a way to support -10~+10 V input
output
terminal
2-way switch output terminal, which supports a
maximum road speed 100kHz pulse output.
2 relay output terminals.
2 analog output terminal, and optional voltage and
current.
Featured
functions
Parameter copy、parameter backup、flexible parameter displayed &
hidden. Common DC bus(Contains below 30 KW).
Various master & auxiliary command and switchover.
Reliable speed search started.
A variety of Accel / Decel curves programmable.
Timing control、fixed length control、count function.
Three faults recorded.
Over excitation brake、overvoltage stall protection programmable、under
voltage stall protection programmable、restart upon power loss.
Four kinds of Accel/Decel time.
Motor thermal protection.
Flexible fan control.
Process PID control、simple PLC、16-step speed control programmable.
Wobble frequency control.
Multi-functional key programmable、field-weakening control.
High-precision torque control、V/f separated control、torque control at

FR200 Series Vector control inverter
- 20 -
sensor-less vector control.
Protection
function
Provide fault protection dozen:Overcurrent、Overvoltage、Undervoltage、
Overtemperature、Overload Etc Protection.
Display and
keyboard
LED Display
Display Parameters
Key lock and
function
selection
Realize some or all of the keys locked, scope definition
section keys to prevent misuse
Run and stop
monitoring
information
In the run or stop can be set to monitor U00 group four
objects were.
Environment
Place of
operation
Indoors, no direct sunlight, free from dust, corrosive
gases,
flammable gases, oil mist, water vapor, water drop and
salt, etc.
Altitude
0~2000m
De-rate 1% for every 100m when the altitude is above
1000 meters
Ambient
temperature
-10℃~40℃
Relative
humidity
5~95%, no condensation
Vibration
Less than 5.9m/s2 (0.6g)
Storage
temperature
-20℃~+70℃
Others
Efficiency
Rated power≥93%
Installation
Wall-mounted or Flange mounting
IP grade
IP20
Cooling
method
Fan cooled
2.4 Parts Drawing
Upper case
FR100 Keypad
Terminal Cover
Stringing board
Holes for
Grounding Wire
Fan
Cooling air inlet
Cooling air outlet
Radiator
Nameplate
Dust cover
(Optional )
Mounting holes
Middle case
Dust cover
Fig 2-3-a 0.75~2.2kW Outline
This manual suits for next models
54