20 INF-TN5FCXA2V5e-E
4.2.1 Menu list
The following are the menu items. Adjust each setting as required.
Item
ODUJHFODVVL¿FDWLRQ Item name Description
Page
1 TAG No. 1. TAG Display and setting of TAG No. (*1) 22
2 Model code 2. TYPE Display and setting of type (*1) 23
3 Serial No. 3-1. SERIAL N Display of serial No. 24
3-2. VER Display of transmitter software version 24
4
Engineering unit
4. UNIT Display and change of engineering unit (*1) 25
5 Range limit 5. URL Display of maximum measuring range 25
6 Measuring range
6-1. LRV Change of LRV
(lower range value of measuring range = 0% point) (*1) 26
6-2. URV Change of URV (upper range value of measuring range = 100% point)
(*1) 27
7 Damping 7. DAMP Change of damping time constant (*1) 28
8 Output mode
8-1. OUT Md Change of output mode (*3) (*1) 29
8-2. CUT Pt 6HWWLQJRIORZÀRZUDWHFXWSRLQW 29
8-3. CUT Md 6HWWLQJRIORZÀRZUDWHFXWPRGH 30
9Direction and value of
burnout
9-1. BURNOT Change of burnout direction (*1) 31
9-2. OVER Chang of output value when burnout direction =
OVERSCALE (*4) (*1) 31
9-3. UNDER Chang of output value when burnout direction =
UNDERSCALE (*5) (*1) 33
A Zero/span calibration A-1. ZERO Zero calibration (*6) (*2) 33
A-2. SPAN Span calibration (*6) (*2) 34
B Output circuit calibration
b-1. 4mAAdj 4 mA calibration (*8) (*2) 35
b-2. 20mAAdj 20 mA calibration (*8) (*2) 35
b-3. FIXcur Constant current output (*8) 35
D Self-diagnosis d-1. AMPTMP Display of internal temperature of transmitter 36
d-2. ALMCHK Display of self diagnosis. 36
FLocking of adjustment
functions F. LOCK Locking and unlocking of the adjusting screw and the adjustment func-
tion in the setting mode (*1) 37
GLCD display
range setting
G-1. LDV LDV (Lower Display Value) setting (*1) 38
G-2. UDV UDV (Upper Display Value) setting (*1) 39
G-3. DP DP (number of digit after Decimal Point) setting (*1) 39
G-4. LcdUnit LcdUnit (LCD Unit Code) setting (*1) 40
G-5. LcdoOpt LcdOpt (LCD Option) setting (*1) 40
IInput-output range ad-
justment
I-1. LRVAdj Zero adjustment by range (LRV) change (*6) (*2) 41
I-2. URVAdj Span adjustment by range (URV) change (*6) (*2) 42
JValue and specification
of saturation current
J-1. SAT LO Change of saturation current value (lower limit) (*7) (*1) 43
J-2. SAT HI Change of saturation current value (upper limit) (*7) (*1) 43
J-3. SPEC Selection (Nomal specification/expanded specification) of specifica-
tions of burnout & saturation current (*1) 44
KProtective function of
set value K. GUARD Setting and cancellation of set value protection (write protect) (*9) 45
L History information
L-1. HisZERO Display of zero calibration data for users 46
L-2. HisSPAN Display of span calibration data for users 46
L-3. HisCLEAR Clearing of zero/span calibration data (*1) 46
L-4. HisAMP 'LVSOD\RIPLQPD[RIDPSOL¿HUWHPSHUDWXUHKLVWRU\LQIRUPDWLRQ 46
L-5. HisCELL Display of min/max of cell temperature history information 46
*1: If the write protect is selected at “K. GUARD,” the display for selecting whether the setting will be performed does not appear, but “GUARD”
appears. You cannot change the value in this condition.
*2: If the adjustment function is locked at “F.Lock” or the write protect is selected at “K. GUARD,” the item names is not displayed.
*3: Only differential pressure transmitters have this function. Other transmitters do not display the item name.
*4: This item is valid only if when the burnout direction = “OVERSCALE.” If not, the item name is not displayed.
*5: This item is valid only if when the burnout direction = “UNDERSCALE.” If not, the item name is not displayed.
*6: This item is valid only if polygonal line correction is invalid. If the polygonal line correction is valid or the equipment is defective, the item
name is not displayed.
<RXFDQQRWFKDQJHWKHYDOXHLIWKHQRPDOVSHFL¿FDWLRQLVVHOHFWHGDW³-63(&´
*8: In the multidrop mode, this item is invalid and the item name is not displayed.
*9: If the write protect function (with a password) is selected by the HHC, the item name is not displayed.