Type
Cassette
Inverter, Heat pump
Model name AUU30RGLX AUU36RGLX
Power supply 208/230 V~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Capacity
Cooling
Rated kW 8.79 10.55
Btu/h 30,000 36,000
Min.—Max. kW 2.81—10.26 2.81—11.43
Btu/h 9,600—35,000 9,600—39,000
Heating
47 °FDB
(Outdoor temp.)
Rated kW 9.38 10.55
Btu/h 32,000 36,000
Min.—Max. kW 2.70—11.43 2.70—14.07
Btu/h 9,200—39,000 9,200—48,000
17°FDB
(Outdoor temp.) *1
Rated kW 5.92 6.80
Btu/h 20,200 23,200
Max. kW 8.88 11.08
Btu/h 30,300 37,700
5°FDB
(Outdoor temp.) *2Rated kW 7.62 7.80
Btu/h 26,000 26,600
Input power
Cooling Rated
kW
2.57 3.60
Min.—Max. 0.60—3.33 0.60—3.94
Heating
47°FDB
(Outdoor temp.)
Rated 2.38 2.73
Min.—Max. 0.52—3.27 0.52—4.19
17°FDB
(Outdoor temp.) *1Rated 1.96 2.25
5°FDB
(Outdoor temp.) *2Rated 3.31 3.36
Fan
HIGH
W
52 87
MED 39 52
LOW 31 39
QUIET 20 23
Current Cooling Rated A 11.5 16.1
Heating 10.7 12.2
EER2 Cooling kW/kW 3.42 2.92
Btu/hW 11.7 10.0
COP2 Heating kW/kW 3.96 3.86
Btu/hW 13.5 13.2
SEER2 Btu/hW 18.7 18.0
HSPF2 10.4 9.7
Power factor Cooling %97
Heating 97
Moisture removal pints/h (L/h) 6.3 (3.0) 7.8 (3.7)
Maximum operating current *3Cooling A15.6 17.6
Heating 16.1 19.1
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
942 (1,600) 1,118 (1,900)
MED 824 (1,400) 936 (1,590)
LOW 748 (1,270) 836 (1,420)
QUIET 677 (1,150) 695 (1,180)
Heating
HIGH 942 (1,600) 1,118 (1,900)
MED 824 (1,400) 936 (1,590)
LOW 748 (1,270) 836 (1,420)
QUIET 677 (1,150) 695 (1,180)
Type × Qty Turbo fan × 1
Motor output W 81
Sound pressure level *4
Cooling
HIGH
dB (A)
40 44
MED 38 41
LOW 36 38
QUIET 33 34
Heating
HIGH 40 44
MED 38 41
LOW 36 38
QUIET 33 34
Heat exchanger type
Dimensions
(H × W × D) in (mm) Main 1: 9-15/16 × 83-3/4 × 1/2 (252 × 2,127 × 13.3)
Main 2: 9-15/16 × 81-1/8 × 1/2 (252 × 2,061 × 13.3)
Fin pitch FPI 21
Rows × Stages 2 × 12
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net in (mm) 11-5/16 × 33-1/16 × 33-1/16 (288 × 840 × 840)
Gross 13-3/8 × 37-13/16 × 37-3/8 (340 × 960 × 950)
Weight Net lb (kg) 57 (26)
Gross 66 (30)
Connection pipe Size Liquid in (mm) Ø3/8 (9.52)
Gas Ø5/8 (15.88)
Method Flare
Drain hose Material PVC
Tip diameter in (mm) Ø1 (25) (I.D.), Ø1-1/16 (26.6) (O.D.)
Operation range Cooling °F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 86 (16 to 30)
Cassette grille
(Option)
Material PS
Color
UTG-GCGF: White
Approximate color of Munsell N 9.25/
UTG-LCGVCB: Black
Approximate color of Munsell N 2
Dimensions
(H × W × D)
Net in (mm) 2-1/16 × 37-3/8 × 37-3/8 (53 × 950 × 950)
Gross 4-5/16 × 39-3/8 × 39-3/4 (110 × 1,000 × 1,010)
Weight Net lb (kg) 13 (6)
Gross 22 (10)
Remote controller (Option) Wireless, Wired
- 4 - 1. Specifications
CASSETTE TYPE
AUU18-36RGLX
CASSETTE TYPE