GE Appliances AEE24 Operating instructions

GEAppliances.com
0
0_
0_
Safety Instructions ............. 2, 3
Operating Instructions
Controls ........................... 4-6
Care and Cleaning
Air Filter .............................. 6
Outdoor Coils ......................... 6
Installation Instructions ...... 7-13
Troubleshooting Tips ............ 14
Normal Operating Sounds ............ 14
Consumer Support
Consumer Support .......... Back Cover
Ownership Registration for
Customers in Canada only ........ 1S, 16
Warranty for Customers
in Canada ........................... 18
Warranty for Customers
in the U.SA........................... 17
AEE24
Climatiseur
La section franCaise commence 5 la page 19
Acondicionador
deaire
La secci6n en espaflol empieza en la p6gina 37
Write the model and serial numbers here:
Model #
Serial #
Find these numbers on a label on the sideof
the air conditioner.
In Canada, contact us at:
www.GEAppliances.ca 49-7667-1 12-10 GE

IMPORTANTSAFETYINFORMATION.
READALLINSTRUCTIONSBEFOREUSING.
WARNING!
Foryour safety, the information in this manual must be followed to minimize the risk of fire, electric shock
or personal injury.
SAFETYPRECAUTIONS
Usethis appliance only for its intended
purposeas described inthis Owner's
Manual.
Thisairconditioner must beproperly
installed in accordance with the Installation
Instructions before it isused.
Never unplug your air conditioner by pulling
on the power cord. Always grip plug firmly
and pull straight out from the receptacle.
Replaceimmediately allelectricservice
cordsthat have becomefrayed or otherwise
damaged.A damaged power supplycord
must bereplacedwith a new power supply
cord obtained from the manufacturer and
not repaired.Donot use a cord that shows
cracksor abrasiondamage along itslength
orat eitherthe plugor connector end.
Turn the unit OFFand unplug your air
conditioner before cleaning.
GEdoes not support any servicing of the
air conditioner. We strongly recommend
that you do not attempt to service the air
conditioner yourself.
For your safety...do not store or use
combustible materials, gasoline or other
flammable vapors or liquids in the vicinity
of this or any other appliance.
All air conditioners contain refrigerants,
which under federal law must be removed
prior to product disposal. If you are getting
rid of an old product with refrigerants, check
with the company handling disposal about
what to do.
If the receptacle does not match the plug,
the receptacle must be changed out by a
qualified electrician.
These R410A air conditioning systems
require contractors and technicians to
use tools, equipment and safety standards
approved for use with this refrigerant.
DO NOT use equipment certified for
R22 refrigerant only.
2
HOWTOCONNECTELECTRICITY
Do not, under any circumstances, cut or remove
the third (ground) prong from the power cord.
For personal safety, this appliance must be properly
grounded.
DONOT usean adapterplug with thisappliance.
The power cord of this appliance is equipped
with a 3-prong (grounding) plug which mates
with a standard 3-prong (grounding) wall outlet
to minimize the possibility of electric shock
hazard from this appliance.
Power cord includes a current interrupter device.
A test and reset button is provided on the plug
case. The device should be tested on a periodic
basis by first pressing the TESTbutton and
then the RESETbutton while plugged into the
outlet. If the TESTbutton does not trip or if the
RESETbutton will not stay engaged, discontinue
use of the air conditioner and contact a qualified
service technician.
Have the wall outlet and circuit checked by
a qualified electrician to make sure the outlet
is properly grounded.
Where a 2-prong wall outlet is encountered,
it isyour personal responsibility and obligation to
have it replaced with a properly grounded
3-prong wall outlet.
The air conditioner should always be plugged
into its own individual electrical outlet which has
a voltage rating that matches the rating plate.
This provides the best performance and also
prevents overloading house wiring circuits which
could cause a fire hazard from overheated wires.
See the Installation Instructions, Electrical
Requirements section for specific electrical
connection requirements.

WARNING!
USEOFEXTENSIONCORDS
RISK OF FIRE. Could cause serious injury or
death.
•DO NOT use an extension cord with this
Window Air Conditioner.
•DO NOT use surge protectors or multi-outlet
adaptors with this Window Air Conditioner.
GEAppliances.com
READAND FOLLOWTHISSAFETYINFORMATIONCAREFULLY
SAVETHESEINSTRUCTIONS

About the controlson the air conditioner.
Features and appearance will vary.
Warmer Cooler
off
Hi h__ Hi
HeaI'1oo,
Low\\ I I J/Low
Heat _",,,,...___.._/ Cool
Fan
Only
TEMP CONTROL
0MODE CONTROL
0
Controls
OTemp Control
The temp control is used to maintain
the room temperature. The compressor
will cycle on and off to keep the room at
the same level of comfort. Turn the knob
clockwise to Cooler (blue) and the indoor
air will become cooler. Turn the knob
counterclockwise to Warmer (red)and
the indoor air will become warmer.
Mode Control
Hi Cool Gnd Low Cool provide cooling with
different fan speeds.
Hi Heat and Low Heat provide heating with
different fan speeds.
Fan Only setting provides air circulation
and filtering without cooling or heating.
NOTE: If you move the mode control
from a cool setting to Off, a fan setting
or a heat setting, wait at least 3minutes
before switching back to a cool setting.
Cooling Descriptions
For Normal Cooling-Select Hi Cool
or Low Cool with the temp control at
midpoint.
For Maximum Cooling--Select Hi Cool with
the temp control turned clockwise as far as
possible.
For Quieter and Nighttime Cooling-Select
Low Cool with the temp control at midpoint.
Heating Descriptions
For Normal Heating--Select Hi Heat
or Low Heat with the temp control at
midpoint.
For Maximum Heating--Select Hi Heat with
the temp control turned counterclockwise
GsfGr Gspossible.
For Quieter & Nighttime Heating--Select
Low Heat with the temp control c]t
midpoint.
4

Additional important information.
Air Direction
Usethe leverto adjust the airdirection left and right
only.
Fingertip pressure on the horizontal louvers
adjusts the air direction up or down.
GEAppliances.com

Careand cleaning of the air conditioner.
Grille and Case
Turn the air conditioner off and removethe plug from Toclean,usewater and a mild detergent.
the wall outlet before cleaning. Donot usebleach or abrasives.
Air Filter
Theair filter behind the front grille should be checked
and cleaned at least every :30days or more often if
necessary.
Toremove:
Open the inlet grille by pulling downward on the tabs
at the top upper corners of the inletgrille untilthe
grille isin a 45° position. Removethe filter.
Cleanthe filter with warm, soapy water. Rinseand let
the filter dry before replacing it. Do not clean the filter
in a dishwasher.
4kCAUTION: ooNoToperate theair
conditioner without a filter because dirt and lint
will clog it and reduce performance.
Outdoor Coils
Thecoilson the outdoor sideof the air conditioner
should be checked regularly. If they are clogged with
dirt or soot,they may be professionallycleaned.
Normal Operating Sounds
You may hear a pinging noise caused by
water being picked up and thrown against the
condenser on rainy days or when the humidity
ishigh. This design feature helps remove
moisture and improve efficiency.
You may hear the thermostat click when the
compressor cycles on and off.
iiiiiiiiiiii_iii
iiiiiiiiiiii_iii
Water will collect in the base pan during
high humidity or on rainy days. Thewater
may overflow and drip from the outdoor side
of the unit.
The fan may run even when the compressor
does not.
6

]l.s,a,,a:io".s,ruc,,o.s] ,irCo.di,io.er]
jr-_- I Questions? Call 800.GE.CARES(800.432.2737)or Visit our Website at: GEAppliances.com
|
In Canada, call 1.800.561.3344or visit www.GEAppliances.ca I
BEFOREYOU BEGIN
Read these instructions completely
and carefully.
• IMPORTANT- Savetheseinstructions
for local inspector's use.
•IMPORTANT--Observe all governing
codes and ordinances.
•Note to Installer- Be sure to leave these
instructions with the Consumer.
•Note to Consumer - Keep these instructions for
future reference.
•Skill level - Installation of this appliance
requires basic mechanical skills.
•Completion time - Approximately 1 hour
• We recommend that two people install
this product.
• Proper installation is the responsibility
of the installer.
• Product failure due to improper installation is not
covered under the Warranty.
• You MUST use all supplied parts and use proper
installation procedures as described in these
instructions when installing this air conditioner.
_ELECTRICALREQUIREMENTS
Some models require a 115/120-volt AC,
(_ 0-Hz grounded outlet protected with a
15-amp time-delay fuse or circuit breaker.
The 3-prong grounding plug minimizes the
possibility of electric shock hazard. If the wall outlet
you plan to use is only a 2-prong outlet, it isyour
responsibility to have it replaced with a properly
grounded 3-prong wall outlet.
©
@
Some models require 230/208-volt AC,
protected with a time-delay fuse or circuit
breaker. These models should be installed on
their own single brunch circuit for best
performance and to prevent overloading
house or apartment wiring circuits, which
could cause a possible fire hazard from
overheating wires.
ZI,CAUTION:
Do not, under any circumstances, cut or remove
the third (ground) prong from the power cord.
Do not change the plug on the power cord
of this air conditioner.
Aluminum house wiring may present special
problems--consult a qualified electrician.
TOOLSYOUWILL NEED
Phillips head screwdriver
Flat-blade screwdriver
Pencil Ruler or tape measure
Level Scissors or knife
Power cord includes u current interrupter device. A
test and reset button is provided on the plug case. The
device should be tested on a periodic basis by first
pressing the TEST button and then the RESET button
while plugged into the outlet. If the TEST button does
not trip or if the RESET button will not stay engaged,
discontinue use of the air conditioner and contact a
qualified service technician.

Installation Instructions
PARTS INCLUDED
(Appearance may vary)
Top
mounting
rail \
Top rail gasket (1) Window
seal
Foam top window _u_,
gasket (1) _
Right
accordion
panel
Side rail(2)
V-supports (2)
Type A
screws (10)
Sillangle
bracket (2)
Type C
screws (5)
Window
locking bracket
(1)
Type Ebolt
with nut (4) Type Fbolt
with nut (2)
8

Installation Instructions
DWINDOW REQUIREMENTS
•These instructions are for astandard double-hung
window. You will need to modify them for other types
of windows.
• All supporting parts must be secured
to firm wood, masonry or metal.
• The electrical outlet must be within reach of the
power cord.
• Follow the dimensions in the table and illustration
for your model.
if. m
19 1/4;'
__ 29" - 41 "
(With accordion panels)
I
I
DSTORMWINDOW REQUIREMENTS
A storm window frame will not allow the air
conditioner to tilt toward the outside, and will keep it
from draining properly.
To adjust for this, attach a piece of wood to the sill.
WOODPIECES
WIDTH:2"
LENGTH:Long enough to fit inside the window
frame.
THICKNESS:To determine the thickness, place a
piece of wood on the sill to make it 1/2" higher
than the top of the storm window frame or the vinyl
frame.
Attach securely with nails or screws provided by the
installer.
1/2" higher
than storm
window
frame
Storm window
frame
1/2" higher
than vinyl frame
_ _(°ns°mewind°ws v/Woo d
=.T,,
-r'- Vinylframe I I
DPREPARETHEAIR CONDITIONER
[] Remove the two control knobs.
r_ Pull down the front panel and remove the filter.
Remove the front panel by lifting up at an
angle.
Remove the four front screws. Save them
for reinstalling the front housing.
D Grasp the lower corners of the grille while
pressing in on the case sides with your
finger tips. Pull out to release and lift it up.
NOTE: Do not pull the bottom edge
toward you more than 3" or you may
damage the tabs of the grille.
• •
9

Installation Instructions
DPREPARETHEAIR CONDITIONER
(continues)
[] Remove the shipping screws located on
the top of the case.
E_ Remove the ground screws from each
side of the case. Keep it in a safe location.
NOTE: Be sure te save this screw. Yeu will need
them later in the installatien.
DSlide the air conditioner from the case by
gripping the base pan handle and pulling
forward while bracing the case. Do not
pull or lift on the styrofoam discharge area.
Do not
pull
area i
damage
to the
unit may
result
FRONT
E_] Your unit may come with internal
packaging. This packaging must be
removed prior to installing the air
conditioner back into the cabinet.
DPREPARETHECASE
[_ Attach the top rail gasket to the bottom
of the top rail.
r_ Install the top mounting rail with 4 type A
screws from the inside of the case. Press
firmly to drive the screws into the gasket
and through the top mounting rail.
Top mounting rail
D Slide each side retainer onto the edge of
each according panel. The figure shows
the orientation of each accordion panel
and side retainer assembly relative to the
case from a top view of the unit.
WINDOW FILLER PANEL
D Slide the left and right accordion panels
into the top and bottom mounting rails.
Top_ight
Bottom mounting _a
0

Installation Instructions
I-_ PREPARETHECASE(continues)
[] Attach the side retainers to the case using 6
type A screws.
DPREPARETHEWINDOW AND INSTALL
THECASE
r_ cut the window sash seal to the proper length.
Peel off the backing and attach the seal to the
underside of the window sash.
r_Open the window and mark the center of
the window sill.
['_ Carefully slide the case into the window
and center the case. Lower the window
behind the top mounting rail. Pull the
bottom of the case forward so that the
bottom mounting rail is tight against the
back of the window stool. Mount the case
to the window sill using 2 type C screws.
Drill pilot holes, if necessary.
Stool
DPREPARETHEWINDOW AND INSTALL
THECASE(continues)
r_ Assemble the V-support and V-support
bracket with Type F nut and bolt
Type Ebolt
nut
Left
ml
D
Sillangle
bracket __ _
V-supporLType
Fbolt and nut
Right
Position the V-supports
on the case bottom so
that they will be near
the outside wall. Attach
a V-support to each side
of the bottom of the case
with Type E bolts, 2 for
each support.
Adjust sill angle brackets to rest on sill.
tpport
D Extend the left and right accordion panels
to the vertical window sashes. Drill pilot
holes and attach the top corners with 2 type
C screws.
_L__IL_CJI
Type C
screw screw
11

Installation Instructions
r_IPREPARETHEWINDOW AND INSTALL
THECASE(continues)
[] CAUTION:
To prevent broken Vinyl
glass or damage to
windows, on vinyl or
other similarly
constructed windows,
attach the window
locking bracket to the window side jamb.
Attach the window locking Wood
bracket with one Type C
screw.
D Cut the foam top window gasket to the
window width.
[_ Stuff the foam
between the
glass and the
window to
prevent air and
insects from getting into the room.
NOTE: If the gasket supplied does not fit
your window, obtain appropriate material
locally to provide a proper installation seal.
INSTALL THE AIR CONDITIONER
IN THE CASE
Slide the air conditioner into the case by
the base pan. Do not push on the controls,
styrofoam air discharge housing or the finned
coils. Make sure the air conditioner is firmly
seated.
Do not presson
these areas-
damage to the unit
may result
Base Pan
INSTALL THE AIR CONDITIONER
IN THE CASE (continues)
FB] Replace the 2 screws removed earlier, one
on each side of the case.
IMPORTANT: THE GROUND SCREWS MUST BE
REINSTALLEDTO ENSURE PROPERGOUND.
Attach the front grille to the case by inserting
the tabs on the grille into the slots on the
front top of the case. Push the grille in.
[] Replace the screws.
r_ Install the filter and the front grille.
r_ Plug in the air conditioner.
12

Through-the-Wall Installation Instructions--Optional
The case may be installed through-the-wall
in both existing and new construction.
Read completely, then follow step-by-step.
NOTE: Obtain all materials locally for
mounting the air conditioner through-
the-wall.
ITI IMPORTANT (cont.)
FD1Secure with 14 wood screws anchored at
least an inch into the wall support structure.
NOTE: Drill pilot holes, if necessary, for
proper installation. If the frame is oversized,
use shims to prevent case distortion.
ITI IMPORTANT
Through-the-wall installation is not
appropriate if any of the side or top louvers
in the case will be obstructed by the wall.
All side and top louvers in the case must
project on the outdoor side of the wall.
The room side of the case must project
into the room far enough to maximize the
balance of the unit.
The case must be installed level from side-
to-side and with a slight tilt from front to
rear. Use a level; no more than a 1/2 bubble
will be the correct case slant to the outside.
Lintel angle is required to support bricks or
blocks above opening.
Flashing is required and should extend the
length of the opening to ensure no inside
cavity leakage occurs.
_-1 Remove the air conditioner from the case.
For specific instruction, refer to the Window
Installation Instructions.
[_] Make certain that a wall receptacle is
available close to the hole location or make
arrangements to install a receptacle.
[] Place the case in the wall opening and
place wood support strips between the case
bottom and the flashing on both sides of the
bottom rail. They should be the same height
as the bottom rail and the same length as
the wall openin.q. 13
FINISH THE WALL OPENING
[_] Caulk all four sides on the outdoor side of
the case to prevent moisture from getting
through to the interior wall. Use of flashing
(drip rail) will further prevent water from
dripping inside the wall and down the
outside of the building.
Caulking [_ Plaster line
I1 Trim molding (if
•II """ desired)
OUTSIDE
Air louvers (top /
and sides must/
project on thev
outdoor side of
the wall)
INSIDE
Bottom rail
J
Wood filler and
caulking (above an
below the flashinc
Flashing
(Drip rail)
Bottom
rail
Flashing
(Drip rail) Wood support strips
FB1Place the air conditioner into the case.
For specific instruction, refer to the Window
Installation Instructions.

TroubleshootingTips.
Possible Causes What To Do
Theair conditioner •Hake surethe air conditioner plug ispushed
doesnotstart _sunplugged, completely into the outlet.
Thefuse isblown/circuit .Check the housefuse/circuit breaker box and replace
breaker istripped, the fuse or resetthe breaker.
Power failure. .The unitwill automatically restart in the settings last
usedafter the power is restored.
•There is a protective time delay (approximately
:3minutes) to prevent tripping of the compressor
overload. For this reason, the unit may not start
normal cooling for :3minutes after it isturned
back on.
The current interrupter • Pressthe RESETbutton located on the power cord plug.
device istripped. • Ifthe RESETbutton will not stay engaged, discontinue
use of the air conditioner and contact a qualified
service technician.
Airconditionerdoes Airflow isrestricted. • Make surethere are no curtains, blindsor furniture
notcoolasitshould blocking the front of the air conditioner.
Thetemp control may • Inthe Coolmode, pressthe Decrease•pad.
not be set correctly.
Theair filter is dirty. .Clean the filter at least every 30 days.
Seethe CareandCleaningsection.
Theroom may have been hot. .When the air conditioner isfirst turned on,you need
to allow time for the room to cool down.
Coldair isescaping. .Check for open furnace registersand cold air returns.
Cooling coils have iced up. .See "Air conditionerfreezingup"below.
Aircondtioner Ice blocks the air flow • Setthe controls at HighFanor HighCooland set the
freezingup and stops the air conditioner thermostat to a higher temperature.
from cooling the room.
Theremotecontrol Thebatteries areinserted .Check the position of the batteries.They should be
isnotworking incorrectly, inserted in the opposite (+)and (-) direction.
Thebatteries may be dead. • Replacethe batteries.
Water dripsoutside Hot,humid weather. .This isnormal.
Water dripsindoors The air conditioner is not • Forproper water disposal,make surethe air conditioner
tilted to the outside, slants slightlyfrom the case front to the rear.
Moisture removed from air
and drains into base pan.
WaterCollectsin
basepan • This isnormal for a short period in areas with little
humidity; normal for a longer period invery humid areas.
Normal Operating Sounds
You may hear apinging noisecaused by
water being picked up and thrown against the
condenser on rainy days orwhen the humidity
is high.Thisdesign feature helps remove
moisture and improve efficiency.
You may hearthe thermostat click when the
compressor cycles on and off.
iiiiiiiiiiii_iii
iiiiiiiiiiii_iii
Water will collect inthe base pan during
high humidity or on rainy days.Thewater
may overflow and drip from the outdoor side
of the unit.
Thefan may runeven when the compressor
does not.
14

Notes.
15

Notes.
16

GEAir Conditioner--One YearLimited Warranty.(For customers in the U.S.A.)
All warranty service provided by our Factory Service Centers,
or an authorized Customer Care_ technician. To schedule service,
visit us on-line at GEAppliances.com, or call 800.GE.CARES
(800.432.2737).Have serial number and model number available
when calling for service.
Staple your receipt here.
Proof of the original purchase date
is needed to obtain service under
the warranty.
Fromthe dateofthe
originalpurchase
GEWill Replace:
Anypartof the air conditioner which fails dueto a defect in materials or workmanship.
Duringthis limitedone-yearwarranty,GEwill also provide, freeofcharge,all labor and related
serviceto replace the defective part.
Service trips to your home to teach you how to use the
product.
Improper installation, delivery or maintenance. If you
have an installation problem, or if the air conditioner
is of improper cooling capacity for the intended use,
contact your dealer or installer. You are responsible for
providing adequate electrical connecting facilities.
Failure of the product resulting from modifications to
the product or due to unreasonable use including failure
to provide reasonable and necessary maintenance.
In commercial locations, labor necessary to move the
unit to a location where it is accessible for service by an
individual technician.
Replacement of house fuses or resetting of circuit
breakers.
Failure due to corrosion on models not corrosion-
protected.
Damage to the product caused by improper power
supply voltage, accident, fire, floods or acts of God.
Incidental or consequential damage caused by possible
defects with this air conditioner.
Damage caused after delivery.
EXCLUSION OFIMPLIED WARRANTIES--Your sole and exclusive remedy is product repair as provided in this
Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a
particular purpose, are limited to one year or the shortestperiod allowed bylaw
This warranty is extended to the original purchaser and any succeeding owner for products purchased for
home use within the USA. If the product is located in an area where service by a GE Authorized Servicer is
not available, you may be responsible for a trip charge or you may be required to bring the product to an
Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls
to your home.
Some states do not allow the exclusion or limitation of incidental or consequential damages. This warranty
gives you specific legal rights, and you may also have other rights which vary from state to state. To know
what your legal rights are, consult your local or state consumer affairs office or your state's Attorney General.
Warranton General Electric Company. Louisville, KY 40225
17

GEAir Conditioner--One-YearLimited Warranty. Forc,stomeri, Ca,ada
All warranty service provided by our Factory Service Centers,
or an authorized Customer Care®technician. For service, call
1.800.561.3344.Please have serial number and model number
available when calling for service.
Staple your receipt here.
Proof of the original purchase date
is needed to obtain service under
the warranty.
!!
Fromthedate0fthe
originalpurchase
Mabe Will Replace:
Anypartofthe air conditioner which fails due to a defect in materials or workmanship.
During this limited one-yearwarranty, IVlabewill also provide, freeofcharge,all labor and related
serviceto replacethe defective part.
Service trips to your home to teach you how to usethe
product.
Improper installation, delivery or maintenance. If you
have an installation problem, or if the air conditioner
is of improper cooling capacity for the intended use,
contact your dealer or installer. You are responsible for
providing adequate electrical connecting facilities.
Failure of the product resulting from modifications to
the product or due to unreasonable useincluding failure
to provide reasonable and necessary maintenance.
In commercial locations, labor necessary to move the
unit to a location where it is accessible for service by an
individual technician.
Replacement of house fuses or resetting of circuit
breakers.
Failure due to corrosion on models not corrosion-
protected.
Damage to the product caused by improper power
supply voltage, accident, fire, floods or acts of God.
Incidental or consequential damage caused by possible
defects with this air conditioner.
Damage caused after delivery.
EXCLUSIONOFIMPLIED WARRANTIES--Your sole and exclusive remedy isproduct repa# as provided in this
Limited Warranty. Any implied warranties, including the implied warranties ofmerchantability or fitness for a
particular purpose, are limited to one year or the shortestperiod allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased in Canada
for home use within Canada. In-home warranty service will be provided in areas where it is available and
deemed reasonable by Mabe to provide.
Some provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above
exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights
which vary from province to province. To know what your legal rights are in your province, consult your local or
provincial consumer affairs o_ce.
Warrantor'. Mabe Canada Inc.,
Burlington, Ontario
18

Consignes de s@curit@............. 2o,21
Consignesd'utilisation
Commandes ..........................22-24
Entretien et nettoyage
Filtre (_air ................................ 24
Serpentins ext6rieurs ..................... 24
Instructions de montage .......... 2s-sl
Conseils de d@pannage .............. s2
Bruits normaux de fonctionnement ........ 32
Assistance _la client@le
Assistonce (_Ioclientele ................... 36
Garantie .................................. 35
Enregistrement du titre
de propri6t6 ........................... 33, 34
AEE24
Inscrivez ici les num@rosde mod@leet de s@rie:
Num@rode mod@le:
Num@ro de S_rie :
Vous trouverez ces num@os sur 1'6tiquette
oppos6e sur le c6t6 du climotiseur.
Au Conodo, visitez-nous au •
www.electromenagersge.ca
19

IMPORTANTES CONSIGNES DE S 'CURIT '.
VEUILLEZ LIRE TOUTES LES CONSIGNES AVANT UTILISATION.
AVERTISSEMENT!
Pour votre s6curit6, les informations contenues dons ce manuel doivent #tre suivies afin de minimiser
les risques d'incendie, de chocs 61ectriques ou de blessures corporelles.
20
CONSIGNES DESf CURITf
N'utilisez cet appareil qu'aux fins pr6vues
d6crites dans le manuel d'utilisation.
Ce climatiseur doit #tre correctement
install# conform6ment aux Instructions
d'lnstallation avant toute utilisation.
Ne d6branchezjamais votre climatiseur en
tirant sur le cordon d'alimentation. Prenez
toujours fermement la fiche en main et tirez
pour la sortir de la prise.
Remplacez imm#diatement tout cordon
#lectrique us# ou endommag#. Un
cordon d'alimentation endommag# doit
#tre remplac# par un nouveau cordon
d'alimentation obtenu du fabricant. Ne
r#parez pas le cordon endommag#. N'utilisez
pas un cordon fissur# ou pr#sentant des
dommages dus aux frottements soit sur sa
Iongueur ou aux extr#mit#s du c6t# de la
fiche ou du raccord.
Eteignez votre climatiseur et d6branchez-le
avant de le nettoyer.
GE n'offre pas de service d'entretien pour
les climatiseurs. Nous vous recommandons
de ne pas essayer d'effectuer I'entretien de
votre climatiseur vous-m#me.
BRANCHEMENTSELECTRIQUES
Ne coupez pas ou n'enlevez pas, sous aucun
pr6texte, la troisi#me broche de mise 6 Io terre
du cordon d'olimentation. Pour des raisons de
s6curit6, cet appareil dolt #tre correctement mis
6 la terre.
N'utilisez PASd'adaptateur avec cet appareil.
Le cordon d'alimentation de cet appareil est
#quip# d'une fiche 6 trois broches (pour une
mise 6 la terre) qui s'adapte 6 la prise de courant
standard 6 3 broches (pour une mise 6 la terre)
pour minimiser les risques de chocs #lectriques
par cet appareil.
Le cordon d'alimentation est #quip# d'un
dispositif d'interruption du courant. Un bouton
d'essai et de r#enclenchement est fourni
sur le battier de la prise. Vous devez tester le
m#canisme r#guli#rement en appuyant d'abord
sur le bouton TEST(essai) puis sur le bouton
RESET(r#enclenchement)Iorsque I'appareil est
branch#. Si le bouton TEST(essai) ne bascule
pas ou si le bouton RESET(r#enclenchement)
ne reste pas enclench#, cessez d'utiliser votre
climatiseur et appelez un technicien de service
qualifi#.
Pour votre s#curit#, ne stockez pas et
n'utilisez pas de mat#riaux combustibles,
d'essence ou d'autres vapeurs et liquides
inflammables dons les parages de cet
appareil ou de tout autre appareil.
Tousles climatiseurs contiennent des
fluides frigorig_nes qui, conform#ment, 6 la
I#gislation f#d#rale doivent #tre retir#s avant
la mise au rebut de I'opporeil. Si vous mettez
ou rebus un ancien oppareil contenont des
fluides frigorig6nes, v#rifiez Io proc#dure 6
suivre aupr6s de la compagnie responsable
de I'#limination.
Si la prise de courant est d'un format
diff@ent de la fiche, cette prise doit #tre
chang6e par un 61ectricien qualifi6.
Ces syst_mes de climatisation R410A
n#cessitent que les entrepreneurs et
techniciens adoptent des outils, du mat#riel
et des normes de s#curit# approuv#s pour
utilisation avec ce r#frig#rant. N'utilisez pas
de mat#riel certifi# pour le r#frig#rant R22
uniquement.
Faites v#rifier la prise murale et le circuit
#lectrique par un #lectricien qualifi# pour
s'assurer que le syst6me est correctement mis 6
la terre.
Dansle cas d'une prise biphas#e,I'installateura
la responsabilit#et robligation de la remplacer
par une prisetriphas#e correctement mise e la
terre.
Le climatiseur doit toujours #tre branch# 6 sa
propre prise #lectrique d'une tension nominale
correspondant 6 celle indiqu#e sur sa plaque
signal#tique.
Ceci permet d'obtenir un meilleur rendement
du climatiseur et #vite de surcharger les circuits
#lectriques du domicile qui risque d'occasionner
un incendie en surchauffant.
Consultez les Consignes d'lnstallations, dans la
section E×igences Electriques pour les exigences
de branchements 61ectriques particuliers.
Other manuals for Appliances AEE24
3
Table of contents
Languages:
Other GE Air Conditioner manuals

GE
GE APFA08 Operating instructions

GE
GE Appliances AEE12 Operating instructions

GE
GE AJCH08ACC Operating instructions

GE
GE AZ28E12DAB Manual

GE
GE AJ806L Training manual

GE
GE AE1CD14DM Manual

GE
GE AEZ18 User manual

GE
GE Zoneline Installation instructions

GE
GE AJ806L Installation instructions

GE
GE AJCS10DCB Assembly instructions