
– 8 –
Thermistors are used to sense small changes in
temperature to give excellent room control and
allow the microprocessor to monitor and react to
changing conditions.
Electric Resistance Heat Lock-Out
To maximize the savings of the heat pump
operation, the Zoneline heat pumps do not
utilize the resistance heater when the outdoor
temperature is above 46°F during normal operation.
The resistance heat is used in the Quick Heat
Recovery feature.
Automatic Emergency Heat
This feature automatically uses electric resistance
heat if the heat pump output is not sufficient to
maintain selected room temperature.
Reverse Cycle Heat Pump Defrost System
This feature is standard on all Zoneline 6100 Series.
It enables the heat pump to operate at lower
temperatures when other systems switch to more
expensive electric resistance heat.
High Temperature Heat Pump Operation
Protection
This feature protects the compressor if heat pump
is operated with high outdoor temperatures. The
power to the outdoor fan is turned off if the indoor
coil gets too hot during heat pump operation to
prevent damage to the compressor.
Quick Heat Recovery – Heat Pump Units
When the unit operation is changed from STOP or
COOL to HEAT, the electric resistance heaters are
used to warm the room to the thermostat set point.
This provides a faster room temperature increase
for greater guest comfort.
Fan Motors – Permanently Lubricated
All units have 2 fan motors for quiet operation
and maximum operating efficiency. Motors are
permanently lubricated to reduce the need for
maintenance, and they are totally enclosed to keep
dirt and water out of the motor windings.
2-Speed Outdoor Fan
The unit automatically selects the most efficient
speed for the outdoor fan. The operating sound
level is lower when the outdoor fan can operate in
low speed, yet there are situations where it must
operate in high speed. The unit changes the fan
speed automatically.
Indoor Fan Speed Selections – HIGH/LOW
The unit may be operated in HIGH HEAT or LOW
HEAT or HIGH COOL or LOW COOL.
(Continued next page)
Features and Benefits
Standard Physical Dimensions
GE has maintained the same dimensions for
Zoneline air conditioners since 1961 – 42 inches
wide x 16 inches high x 13 3/4inches deep.
Replacement of older units is made easy.
Weather-Protected Electrical Components
Vital electrical components are protected from the
weather by locating them on the indoor side of the
weather barrier.
Weather-Resistant Super Seal
The properly installed unit in a nondistorted case
keeps air leakage to a minimum - 7 cubic feet per
minute (CFM), air infiltration with 25 MPH wind.
Industry specification is 19 CFM of air infiltration.
Heater Sizes to Meet Room Requirements
All units are equipped with a universal heater. The
resistance heat output is determined by a power
connection kit.
230/208-Volt - Line Cord Connected Units
• 2.40/2.32 KW with RAK3153 - 15-amp circuit
• 3.30/3.20 KW with RAK3203 – 20-amp circuit
• 4.70/4.53 KW with RAK3303*– 30-amp circuit
*Not approved for use on 7000 BTU models.
230/208-Volt - Sub-Base Connected Units
• 2.40/2.32 KW with RAK204D15P – 15-amp circuit
• 3.30/3.20 KW with RAK204D20P – 20-amp circuit
• 4.70/4.53 KW with RAK204D30P* – 30-amp circuit
*Not approved for use on 7000 BTU models.
265-Volt
• 2.40 KW with RAK5172 – 15-amp circuit
• 3.40 KW with RAK5202 – 20-amp circuit
• 4.80 KW with RAK5302 – 30-amp circuit
Unit Controls
The 6100 Series has touch pads and LCD display for
temperature and operation selection.
Highly Featured Microprocessor Controls
The microprocessor controls are programmed to
interface with the temperature sensors to maximize
comfort conditions for the room occupant and
provide outstanding features.