Cooling Model AZ85W12DACW
DISCONNECT POWER BEFORE SERVICING
IMPORTANT - RECONNECT ALL GROUNDING DEVICES
All parts of this appliance capable of conducting electrical current are
grounded. If grounding wires, screws, straps, clips, nuts or washers used to
complete a path to ground are removed for service, they must be returned
to their original position and properly fastened.
WARNING DISCONNECTUNIT FROM ELECTRICAL POWER SUPPLY
BEFORE MAKING ANY ELECTRICAL CHECKS.
MAXIMUM CURRENT LEAKAGE: 0.75 MILLIAMP
MAXIMUM GROUND PATH RESISTANCE: 0.1 OHM
IMPORTANT SAFETY NOTICE
Thisinformationisintendedforusebyindividualspossessingadequatebackgrounds
of electrical, electronic and mechanical experience. Any attempt to repair a major
appliance may result in personal injury and property damage. The manufacturer
or seller cannot be responsible for the interpretation of this information, nor can it
assume any liability in connection with its use.
RUN CAPACITOR CHECK
1.Replaceunitruncapacitorwith
a known good test capacitor
which may be 10 MFD higher
WKDQVSHFL¿HGDQGDWWHPSWWR
start compressor.
2. If compressor starts, install a
new run capacitor which has
DUDWLQJVSHFL¿HGIRUWKHXQLW
MODEL RATED
VOLTAGE VOLTAGE
LIMITS EVAPORATOR
AIR TEMP IN °F EVAP AIR OUT °F AIR TEMP
CONDENSER IN °F COOLING CURRENT
MIN. MAX. MIN. MAX.
AZ85W09DACW1
208V
187-253
70
80
90
74
83
90
82
89
98
80
95
110
3.5
3.9
3.9
3.9
4.4
4.6
230V 70
80
90
74
83
90
82
89
98
80
95
110
3.2
3.6
3.6
3.6
4.1
4.2
AZ85W12DACW1
208V
187-253
70
80
90
74
82
89
82
90
96
80
95
110
4.4
4.8
5.4
5.1
5.7
6.5
230V 70
80
90
74
82
89
82
90
96
80
95
110
4.1
4.4
5.0
4.7
5.3
6.0
POWER SUPPLY AND TEMPERATURE CHECK
RUNNING CURRENT
With unit in case, operate for ten minutes on Hi-Cool. See Power
Supply and Temperature Check table for normal limits.
CONDENSER
1. Check for blockage with dirt, or other material.
2. Check for corrosion.
FILTER
Check for cleanliness.
TEMPERATURE DIFFERENTIAL - COOLING
Unit must operate for one hour with thermostat at coldestsetting
prior to measuring air temperatures. See Power Supply and
Temperature Check table for normal limits.
SEALED SYSTEM
MODEL COMPRESSOR REFRIG.
R410A CAPILLARY
OD x ID x LENGHT (PC)
AZ85W09D Rechi 27.5 oz. .106" x .051" x 23.62" (1)
AZ85W12D Rechi 27.5 oz. .106" x .059" x 25.59" (1)
.106" x .055" x 15.75" (2)
Temperature limiting during COOL mode
(all temperatures shown in °F)
UP Down Min. Max.
NONE 1,2,3 60° 85°
1 2,3 64° 85°
1,2 3 66° 85°
2 1,3 68° 85°
2,3 1 70° 85°
1,2,3 NONE 72° 85°
1,3 2 74° 85°
3 1,2 76° 85°
TL1 (C) (Temp. Limit 1 - Cool)
TL2 (C) (Temp. Limit 2 - Cool)
TL3 (C) (Temp. Limit 3 - Cool)
TL1 (H) (Temp. Limit 1 - Heat)
TL2 (H) (Temp. Limit 2 - Heat)
TL3 (H) (Temp. Limit 3 - Heat)
ALL I'R (All Electric Heat
(Heat-pump models only)
FREEZ S (Freeze Sentinel)
CONST FAN (Constant ON Fan)
OCCUPIED (Occupancy Sensor)
DUCT (Blower Fan)
No Function
(Reserved for future use)
WARNING: Risk of electric shock. Can cause injury
or death: Read all instructions and safety information
before servicing this product.
WIRING - COMPRESSOR DIRECT CHECK
CAUTION: Risk of injury. Keep
head clear of terminal area when
cover is removed.
&KHFNZLQGLQJV¿UVW,IRSHQRU
grounded, DO NOT apply power to
compressor terminals.