GE ASTAT XT QT 0008U Series User manual

GE Consumer & Industrial
ASTAT XT
User Manual

2 •Warnings
WARNINGS
1. DISCONNECT POWER BEFORE INSTALLING OR SERVICING.
2. HAZARDOUS VOLTAGES ARE PRESENT IN THE MOTOR CIRCUIT EVEN WHEN THE STARTER IS OFF. AN
ISOLATION CONTACTOR IS RECOMMENDED, CONFIGURED TO PROVIDE AUTOMATIC ISOLATION WHEN
THE MOTOR IS TURNED OFF.
3. UNIT MAY CONTAIN MORE THAN ONE LIVE CIRCUIT. DISCONNECT BOTH CONTROL AND MAIN CIRCUITS
BEFORE INSTALLING OR SERVICING.
4. SOFT STOP SHOULD NOT BE USED AS AN EMERGENCY STOP.
5. STOPPING MODE MUST BE SET TO MEET APPLICABLE STANDARDS FOR OPERATOR SAFETY.
6. SEPARATE MOTOR OVERCURRENT PROTECTION IS REQUIRED TO BE PROVIDED IN ACCORDANCE WITH
THE CANADIAN ELECTRICAL CODE, PART 1. ASTAT-XT PROVIDES SEPARATE MOTOR PROTECTION.
CAUTIONS
1. SEMI-CONDUCTOR FUSES SPECIFIED MAY NOT PROVIDE BRANCH CIRCUIT PROTECTION. REFER TO
LOCAL APPLICABLE ELECTRICAL CODES.
2. OVERLOAD RELAY SETTING SHOULD BE PROPERLY COORDINATED WITH MOTOR.
3. SLOW SPEED RUNNING WILL AFFECT THE MOTOR THERMAL CHARACTERISTIC DUE TO REDUCED
COOLING.
CARE MUST BE TAKEN WHEN OPERATING MOTOR UNDER THESE CONDITIONS.
4. ABNORMAL STARTING TIMES IN EXCESS OF 30 SECONDS, OR CLOSELY REPEATED OPERATIONS OF
ACCELERATION RAMP/DECELERATION RAMP, SLOW SPEED, MAY CAUSE MOTOR DAMAGE. CONTACT
MOTOR MANUFACTURER FOR PROPER MOTOR SELECTION.
5. IF CONTROL POWER IS LOST BETWEEN STARTS, THE OVERLOAD RELAY PROTECTION IS RESET TO COLD
START CONDITIONS.
REMARKS:
1. Read this manual thoroughly before using the ASTAT-XT and store in a safe place for reference.
2. Make sure that this manual is delivered to the end user.
3. The policy of GE Industrial Systems is one of continuous improvement.
The right is reserved to alter the design on any structural details of the products at any time without giving notice.

3 • Table of Contents
ASTAT-XT User Manual
1. Generalities..................................................................................................................................................... 7
1.1 Squirrel-Cage Motor Starting.................................................................................................................................................... 7
1.2 Advantages of the ASTAT-XT Solid State Soft Starters................................................................................................. 7
2. Types and Ratings ......................................................................................................................................... 8
2.1 IEC Ratings. Recommended Motor and Type Unit Ratings........................................................................................ 8
2.2 NEMA Ratings . Recommended Motor and Type Unit Ratings................................................................................. 9
2.3 Thermal Characteristics ............................................................................................................................................................10
3. Technical Specifications .............................................................................................................................11
3.1 General Specifications ...............................................................................................................................................................11
3.2 Weight................................................................................................................................................................................................13
3.3 I/O Terminal Board Specifications........................................................................................................................................13
3.4 I/O Wiring..........................................................................................................................................................................................17
3.5 Ordering Information..................................................................................................................................................................18
3.5.1 Ordering Accessories .................................................................................................................................................18
3.6 Operating Modes ..........................................................................................................................................................................19
4. Control Keypad.............................................................................................................................................20
4.1 LCD Arrangement.........................................................................................................................................................................20
4.2 Push-Buttons..................................................................................................................................................................................21
4.3 Status LEDs......................................................................................................................................................................................21
4.4 Reviewing and Modifying Parameters...............................................................................................................................21
4.5 Special Actions Performed in Test/Maintenance Mode.............................................................................................22
4.5.1 Run Self Test ...................................................................................................................................................................22
4.5.2 View Software Version...............................................................................................................................................22
4.5.3 Obtain Default Parameters .....................................................................................................................................22
4.5.4 Reset Statistical Data .................................................................................................................................................22
4.5.5 Calibrate Voltage and Current (Factory Use Only!) .....................................................................................23
4.6 Mode Pages.....................................................................................................................................................................................23
4.7 Overview of All Mode Pages and Factory Defaults......................................................................................................24
4.7.1 Display Mode – Page 0..............................................................................................................................................26
4.7.2 Main Settings – Page 1 ..............................................................................................................................................27
4.7.3 Start Settings – Page 2 ..............................................................................................................................................29
4.7.3.1 Soft Start Parameters.......................................................................................................................................32
4.7.4 Stop Settings – Page 3...............................................................................................................................................34
4.7.4.1 Soft Stop Parameters .......................................................................................................................................35
4.7.5 DUAL Settings Parameters – Page 4...................................................................................................................36
4.7.6 Slow Speed & Energy Save Parameters – page 5........................................................................................37
4.7.7 Fault Settings – Page 6..............................................................................................................................................38
4.7.8 I/O Settings Parameters – Page 7........................................................................................................................40
4.7.8.1 Terminal 7 and 8 Programming..................................................................................................................41
4.7.9 COMM. Parameters – Page 8 – With the Modbus standard PCB..........................................................42
4.7.10 Comm. Parameters – Page 8 – With the Profibus optional PCB............................................................42
4.7.11 Comm. Parameters – Page 8 – With the DeviceNet Optional PCB ......................................................43
4.7.12 Statistical Data – page 9...........................................................................................................................................44
4.8 Non Adjustable Protection and Fault Reset.....................................................................................................................45
4.8.1 Under/Over Frequency .............................................................................................................................................45
4.8.2 Phase Loss.......................................................................................................................................................................45
4.8.3 Phase Sequence ...........................................................................................................................................................45
4.8.4 Wrong Connection ......................................................................................................................................................45
4.8.5 Shorted SCR ....................................................................................................................................................................45
4.8.6 Heat-Sink Over Temperature .................................................................................................................................45
4.8.7 External Fault .................................................................................................................................................................45
4.8.8 Fault and Reset .............................................................................................................................................................45
4.8.9 Auto Reset........................................................................................................................................................................46
4.9 Timing Occurrence Table..........................................................................................................................................................46

4 • Table of Contents
5. Installation ....................................................................................................................................................47
5.1 Prior to Installation.......................................................................................................................................................................47
5.2 Mounting...........................................................................................................................................................................................47
5.3 Temperature Range & Heat Dissipation............................................................................................................................47
5.3.1 Forced Ventilation........................................................................................................................................................48
5.4 Main PCB and Optional PCBs..................................................................................................................................................48
5.5 Dip Switch Settings on the Main PCB..................................................................................................................................49
5.5.1 Switch # 1 – Display Modes ....................................................................................................................................49
5.5.2 Switch # 2 – Not used ................................................................................................................................................50
5.5.3 Switch # 3 – Main/ D.Set: Generator Parameters.........................................................................................50
5.5.4 Switches # 5, 6 – Language Selection................................................................................................................50
5.5.5 Switch # 7 – Expanded Settings............................................................................................................................50
5.5.6 Switch # 8 – Software Lock .....................................................................................................................................50
5.6 Internal Fan Control ....................................................................................................................................................................51
5.7 Analog I/O (Terminals T1, T2, Gnd, Out (-), Out (+)) ........................................................................................................51
5.8 Remote Key-Pad Installation..................................................................................................................................................52
6. Starting Procedure ......................................................................................................................................53
6.1 Standard Starting Procedure..................................................................................................................................................54
6.2 Examples of Starting Curves...................................................................................................................................................55
6.2.1 Light Loads - Pumps, Etc. .........................................................................................................................................55
6.2.2 High Inertia Loads: Crushers, Centrifuges, Mixers, Etc...............................................................................55
6.2.3 Special Starting Using DUAL Settings ................................................................................................................56
6.2.3.1 Special Starting – Using DUAL Settings – Wiring Diagram ............................................................57
6.2.4 Choosing a Suitable Pump Curve (Centrifugal Pumps)..............................................................................57
6.2.4.1 Starting Curve ......................................................................................................................................................57
6.2.4.2 Stopping Curve....................................................................................................................................................58
6.2.4.3 End Torque During Soft-Stopping a Pump Motor...............................................................................58
7. Trouble Shooting..........................................................................................................................................59
8. Application diagrams..................................................................................................................................62
8.1 Terminal 21 Connections With Various Mains................................................................................................................62
8.2 Control Supply, Control Input and Mains are From the Same Source, Neutral Connected to Terminal 21
63
8.3 Control Supply and Control Input From the Same Source, Neutral not Connected to Terminal 21....63
8.4 Control Supply and Control Input from Separate Sources ......................................................................................64
8.5 Soft Start, Soft Stop and Stop, Control Supply and Control Input from the Same Source........................64
8.6 Soft Start, Soft Stop and Stop, Control Supply and Control Input from Separate Sources ......................64
8.7 Soft Start and Immediate Stop (no Soft Stop).................................................................................................................65
8.8 Soft Start and Soft Stop.............................................................................................................................................................65
8.9 Soft Start, Soft Stop and Immediate Stop.........................................................................................................................65
8.10 Energy Save, Slow Speed or Reset.................................................................................................................................66
8.11 Slow Speed and Slow Speed Reverse ...........................................................................................................................66
8.12 External Fault............................................................................................................................................................................67
8.13 Line Contactor..........................................................................................................................................................................67
8.14 Bypass Contactor...................................................................................................................................................................68
8.15 Reversing with Two Line Contactors.............................................................................................................................69
8.16 Operating via Communication Links.............................................................................................................................70
8.17 D.Set: Generator Parameters Wiring.............................................................................................................................71
8.18 Short Circuit Protection........................................................................................................................................................72
8.18.1 Type 1 Coordination ...................................................................................................................................................72
8.18.1.1 Type 1 Coordination with GE Circuit Breakers: ....................................................................................72
8.18.1.2 Type 1 Coordination with Type aM Siba Fuses:...................................................................................72
8.18.2 Type 2 Coordination ...................................................................................................................................................72
8.19 Transient Protection ..............................................................................................................................................................73
8.20 Inside Delta Configuration..................................................................................................................................................74
8.20.1 General Information ...................................................................................................................................................74
8.20.2 Notes on Inside Delta Connection .......................................................................................................................74
8.20.3 Motor Connection and Terminals.........................................................................................................................75

5 • Table of Contents
8.20.4 ASTAT-XT Connected Inside Delta w/Bypass Contactor and Inside Delta Contactor ................76
8.20.5 ASTAT-XT Connected Inside Delta - Reverse Speed....................................................................................77
9. Dimensions....................................................................................................................................................78
9.1 UL cUL Approved Models..........................................................................................................................................................78
9.2 Non UL cUL Approved Models................................................................................................................................................82
Appendix A - MODBUS RTU Protocol......................................................................................................................86
A.1. Introduction.....................................................................................................................................................................................86
A.2. Basic Structure of the Serial Link Frame ...........................................................................................................................87
A.3. SYNC (Silent Interval) ...................................................................................................................................................................87
A.4. Serial Link No. (Slave Address)...............................................................................................................................................87
A.5. Function ............................................................................................................................................................................................87
A.6. List of Functions Supported By The ASTAT-XT ...............................................................................................................87
A.7. Actual Data (3X References & 4X References)................................................................................................................89
A.8. Parameter Settings (4X References)....................................................................................................................................91
A.9. Control Register Write (4X Reference) ................................................................................................................................94
A.10. Discrete Commands (Coils, 0x References)...............................................................................................................95
A.11. Discrete Hardwired Inputs (1x References)...............................................................................................................97
A.12. Diagnostics ................................................................................................................................................................................98
A.13. Exception Responses ............................................................................................................................................................99
Appendix B - Profibus..............................................................................................................................................101
B.1. Operation Mode in PROFIBUS:.............................................................................................................................................101
B.1.1. Structure of the ASTAT-XT Receiving Frame................................................................................................ 101
B.1.2. Structure of the ASTAT-XT Transmitting Frame ......................................................................................... 101
B.1.2.1. Selection of the DPV0 Registers through Data Request (DPV1)................................................ 101
B.1.3. Read and Write from Random Registers via Data Request ................................................................. 102
B.2. Configure the PROFIBUS in the ASTAT-XT......................................................................................................................103
B.3. Watch Dog Definition ..............................................................................................................................................................103
B.4. Actual Data Register Numbers (decimal).......................................................................................................................104
B.5. Setting Parameters Registers for Data Request.........................................................................................................106
Appendix C - DeviceNet™ to Modbus™ Gateway..............................................................................................108
C.1. Introduction..................................................................................................................................................................................108
C.1.1. Overview........................................................................................................................................................................ 108
C.1.2. Definitions..................................................................................................................................................................... 108
C.1.3. Reference Documents............................................................................................................................................ 108
C.1.4. Open DeviceNet Vendor Association, Inc. (ODVA) ..................................................................................... 108
C.1.5. Rotary Switch Configuration ............................................................................................................................... 109
C.1.6. LED Indicators............................................................................................................................................................. 109
C.2. Identity Object (01HEX - 1 Instance) .....................................................................................................................................111
C.2.1. Class Attributes (Instance 0)................................................................................................................................. 111
C.2.2. Instance Attributes (Instance 1) ......................................................................................................................... 111
C.2.3. Common Services ..................................................................................................................................................... 111
C.3. Message Router Object (02HEX - 1 Instance) ...................................................................................................................111
C.4. DeviceNet Object (03HEX - 1 Instance)................................................................................................................................111
C.4.1. Class Attributes (Instance 0)................................................................................................................................. 111
C.4.2. Instance Attributes (Instance 1) ......................................................................................................................... 111
C.4.3. Common Services ..................................................................................................................................................... 111
C.5. Assembly Object (04HEX –4 Instances) ............................................................................................................................112
C.5.1. Class Attributes (Instance 0)................................................................................................................................. 112
C.5.2. Output (O2T) Instance Attributes – Register 40752 .................................................................................. 112
C.5.2.1. Output Instance 112 (0x70) – Control Output.................................................................................... 112
C.5.3. Input (T20) Instance Attributes – Register 40257....................................................................................... 112
C.5.3.1. Input Instance 60 (0x3C) – Basic Softstart Input .............................................................................. 112
C.5.3.2. Input Instance 61 (0x3D) – Extended Softstart Input ..................................................................... 112
C.5.3.3. Input Instance 100 (0x64) – Status ......................................................................................................... 112
C.5.4. Common Services ..................................................................................................................................................... 113
C.6. Connection Object (05HEX –2 Instances) ..........................................................................................................................113

6 • Table of Contents
C.6.1. Class Attributes (Instance 0)................................................................................................................................. 113
C.6.2. Instance Attributes (Instances 1-2) Explicit, Polled I/O............................................................................ 113
C.6.3. Common Services ..................................................................................................................................................... 115
C.7. Softstart Object (2DHEX - 1 Instance)...................................................................................................................................115
C.7.1. Class Attributes (Instance 0)................................................................................................................................. 115
C.7.2. Instance Attributes (Instance 1) ......................................................................................................................... 115
C.7.2.1. Extended AtReference Values................................................................................................................... 115
C.7.2.2. Extended StartMode Values....................................................................................................................... 115
C.7.3. Common Services ..................................................................................................................................................... 115
C.8. Control Supervisor Object (29HEX - 1 Instances)............................................................................................................ 115
C.8.1. Class Attributes (Instance 0)................................................................................................................................. 115
C.8.2. Instance Attributes (Instance 1) ......................................................................................................................... 115
C.8.3. Common Services ..................................................................................................................................................... 116
C.9. Modbus / Serial Object (65HEX –1 Instance).................................................................................................................... 116
C.9.1. Class Attributes (Instance 0)................................................................................................................................. 116
C.9.2. Instance Attributes (Instance 1) ......................................................................................................................... 116
C.9.3. Common Services ..................................................................................................................................................... 117
C.10. Input Object (70HEX –1 Instance) ....................................................................................................................................117
C.10.1. Class Attributes (Instance 0) ............................................................................................................. 117
C.10.2. Instance Attributes (Instance 1) ...................................................................................................... 117
C.10.3. Common Services.................................................................................................................................. 118
C.11. Main Parameter Object (71HEX –1 Instance).............................................................................................................118
C.11.1. Class Attributes (Instance 0) ............................................................................................................. 118
C.11.2. Instance Attributes (Instance 1) ...................................................................................................... 118
C.11.3. Common Services.................................................................................................................................. 119
C.12. Start Settings Object (72HEX –1 Instance)................................................................................................................... 119
C.12.1. Class Attributes (Instance 0) ............................................................................................................. 119
C.12.2. Instance Attributes (Instance 1) ...................................................................................................... 119
C.12.3. Common Services.................................................................................................................................. 119
C.13. Stop Settings Object (73HEX –1 Instance) ...................................................................................................................119
C.13.1. Class Attributes (Instance 0) ............................................................................................................. 119
C.13.2. Instance Attributes (Instance 1) ...................................................................................................... 119
C.13.3. Common Services.................................................................................................................................. 119
C.14. Dual Settings Object (74HEX –1 Instance)...................................................................................................................119
C.14.1. Class Attributes (Instance 0) ............................................................................................................. 119
C.14.2. Instance Attributes (Instance 1) ...................................................................................................... 120
C.14.3. Common Services.................................................................................................................................. 120
C.15. Slow SP & Saving Parameters Object (75HEX –1 Instance).................................................................................120
C.15.1. Class Attributes (Instance 0) ............................................................................................................. 120
C.15.2. Instance Attributes (Instance 1) ...................................................................................................... 120
C.15.3. Common Services.................................................................................................................................. 120
C.16. Fault Settings Object (76HEX –1 Instance) .................................................................................................................. 120
C.16.1. Class Attributes (Instance 0) ............................................................................................................. 120
C.16.2. Instance Attributes (Instance 1) ...................................................................................................... 120
C.16.3. Common Services.................................................................................................................................. 121
C.17. I/O Settings Object (77HEX –1 Instance) ......................................................................................................................121
C.17.1. Class Attributes (Instance 0) ............................................................................................................. 121
C.17.2. Instance Attributes (Instance 1) ...................................................................................................... 121
C.17.3. Common Services.................................................................................................................................. 121
C.18. Communication Parameter Object (78HEX –1 Instance) .....................................................................................121
C.18.1. Class Attributes (Instance 0) ............................................................................................................. 121
C.18.2. Instance Attributes (Instance 1) ...................................................................................................... 121
C.18.3. Common Services.................................................................................................................................. 122

7 • Generalities
1. GENERALITIES
1.1 Squirrel-Cage Motor Starting
There are numerous applications where soft starting and limited current peak are needed, thereby making direct
starting of squirrel-cage motors impossible. Traditionally in such cases other types of starting with reduced stator
voltage have been resorted to. The best-known are star-delta starters, autotransformer starters, stator resistance
starters or using part winding motors.
Any reduced starting voltage imposes a current limitation, thus reducing the starting torque, but there will always
be peaks during the change from one point or state to another which can damage the machine being driven.
Note that in general, all reduced voltage starts reduce torque in squared proportion to the current in the phases of
the motor (not on the line) and the latter in turn is reduced in linear proportion to the voltage. From this it can be
deduced that any start with reduced voltage reduces the torque in squared proportion to the voltage per motor
phase. From this point of view soft starting produces just like any other reduced voltage start, a reduction in starting
torque, according to the adjusted parameters. The advantage is the ease with which this ramp can be controlled to
produce a soft start in accordance with the actual requirement of the machine.
1.2 Advantages of the ASTAT-XT Solid State Soft Starters
Increase in productivity and reliability with the use of static soft
starters
Starting and stopping the motor without steps or transitions lengthens the life
of power-driven machine mechanical elements, greatly reducing stress on
transmission and coupling parts.
Consequently, overhauling times are reduced and machine and facility
lifespans are lengthened.
Improvement in acceleration / deceleration characteristics
Being able to start by using the voltage ramp or alternatively by limiting
current lets acceleration fit the load characteristics. Application of a pulse
start may also be selected in cases of high static friction load.
Stopping may be made by cutting-off power or by soft stop ramp.
Protected motor
The soft starter protects the motor from overloads as well as from incorrect
operating conditions such as loss of an input or output phase, blocked rotor,
thyristor short circuit, etc.
Digital technology
The control system is based on the use of a highly specialized microcontroller
by which signals are treated digitally, thereby avoiding deratings and
adjustments common to analogue circuits and obtaining excellent precision
and speed of execution.
The control board is made with the technology of surface mounting devices
(SMD), which increases equipment reliability.
High level of immunity
Design of the unit was closely tied to the conditions of supply lines, which
handle more disturbances every day. The control signals are
opto-electronically isolated and various levels of protection have been set up
in the circuits to immunize the equipment against external disturbance and its
effects.
Easy to run and adjust
This unit can be used for a wide range of applications.
Adjustments are very easy to make and diverse options maybe selected for
have equipment capabilities suited to application needs every time.
Easy maintenance due to full monitoring
The alphanumeric display and the LEDs on its front overlay makes the
equipment working conditions known at any time.
Pump control
The ASTAT-XT includes several soft stop curves which is more effective than
the standard soft stop, reducing fluid surges or hammering in a pipe line
system. This method reduces the motor speed, by controlling internal
parameters in the motor as well as the output voltage in a close-loop system.
Advanced functions
The ASTAT-XT includes advanced functions, like linear acceleration ramp,
forward and reverse jog, programmable I/O or connection to a control system
via Modbus protocol included as standard and other optional protocols.
These functions allow the incorporation of the soft starter to a distributed
control net, in automated plant processes, together with other soft starters,
programmable controllers, variable speed drives, etc.

8 • Types and Ratings
2. TYPES AND RATINGS
2.1 IEC Ratings1. Recommended Motor and Type Unit Ratings.
Light
Duty
Normal Duty (IEC Class 10)
Recommended Motor Ratings
Heavy Duty (IEC Class 20)
Recommended Motor Ratings
Type Unit
Max
Current
Rating
Current
rating2
230V 400V
415V
480V
500V
575V 690V Current
rating3
230V 400V
415V
480V
500V
575V 690V
A A kW kW kW HP kW A kW kW kW HP kW
8 8 2 3.0 4 5 5.5 8 1.5 3.0 4 5 5.5 QTx0008Uxxxx
17 17 4 7.5 7.5 15 15 12 3 5.5 5.5 10 8 QTx0017Uxxxx
34 31 8 15 18.5 15 22 31 8 15 18.5 25 22 QTx0031Uxxxx
54 44 11 22 30 40 37 44 11 22 30 40 37 QTx0044Uxxxx
65 58 15 30 37 50 55 55 15 30 37 50 45 QTx0058Uxxxx
72 72 22 37 45 60 55 66 18.5 37 45 60 55 QTx0072Uxxxx
104 85 22 45 55 75 75 80 22 45 55 75 75 QTx0085Uxxxx
130 105 30 55 55 100 90 99 30 55 55 100 90 QTx0105Uxxxx
156 145 45 75 90 150 132 130 37 55 90 125 90 QTx0145Uxxxx
170 170 55 90 110 150 160 134 37 75 90 125 132 QTx0170Uxxxx
248 210 55 110 132 200 200 203 55 110 132 200 200 QTx0210Nxxxx
361 310 90 160 200 300 250 310 75 160 200 300 250 QTx0310Nxxxx
390 390 110 200 250 300 355 344 110 160 250 350 315 QTx0390Nxxxx
480 460 132 250 315 450 400 432 132 250 315 450 400 QTx0460Nxxxx
480 460 132 250 315 450 400 432 132 250 315 450 400 QTx0460Uxxxx
610 580 160 315 400 500 560 488 160 250 355 500 400 QTx0580Nxxxx
610 580 160 315 400 500 560 552 160 315 400 560 QTx0580Uxxxx
820 650 200 355 400 630 552 160 315 400 560 QTx0650Nxxxx
820 820 250 400 560 800 690 200 400 500 710 QTx0820Uxxxx
1180 950 315 560 630 900 950 315 560 630 900 QTx0950Nxxxx
1375 1100 355 630 800 1000 1076 355 630 800 1000 QTx1100Nxxxx
1750 1400 400 800 1000 1400 400 800 1000 QTx1400Nxxxx
Note:
Select the appropriate ASTAT-XT, according to the main power supply and motor voltage rating.
Use QT1xxxx units for power supply and motors rated at 230V-500V
Use QT2xxxx units for power supply and motors rated at 460V-600V
Use QT3xxxx units for power supply and motors rated at 690V
1Ratings in Amps. given for ambient temperature up to 40°C and 1000m altitude.
For higher ambient temperature between 40°C and 50°C, derate the current by 2.5% for each °C that is above 40°C.
2Normal duty ratings, only IEC Class 10 protection is allowed.
3Heavy duty ratings, IEC Class 10 and 20 protections are allowed.

9 • Types and Ratings
2.2 NEMA Ratings4. Recommended Motor and Type Unit Ratings.
Light Duty
Nema 10
Normal Duty
Nema 20
Heavy Duty
Nema 30
Type Unit
Current
rating5
230V 460V 575V Current
rating6
230V 460V 575V Current
rating7
230V 460V 575V
A HP HP HP A HP HP HP A HP HP HP
8 2 5 5 8 2 5 5 8 2 5 5 QTx0008Uxxxx
17 5 10 15 17 5 10 15 12 3 7.5 10 QTx0017Uxxxx
34 10 25 30 31 10 20 25 31 10 20 25 QTx0031Uxxxx
54 20 40 50 44 15 30 40 44 15 30 40 QTx0044Uxxxx
65 20 50 60 58 20 40 50 55 20 40 50 QTx0058Uxxxx
72 25 50 60 72 25 50 60 66 20 50 60 QTx0072Uxxxx
104 40 75 100 85 30 60 75 80 30 60 75 QTx0085Uxxxx
130 50 100 125 105 40 75 100 99 40 75 100 QTx0105Uxxxx
156 60 125 150 145 50 100 150 130 50 100 125 QTx0145Uxxxx
170 60 125 150 170 60 125 150 134 50 100 125 QTx0170Uxxxx
262 100 200 250 210 75 150 200 203 75 150 200 QTx0210Uxxxx
387 150 300 400 310 100 250 300 310 100 250 300 QTx0310Uxxxx
414 150 350 400 390 150 300 400 361 150 300 300 QTx0390Uxxxx
480 200 400 500 460 150 350 400 432 150 350 400 QTx0460Uxxxx
610 250 500 580 200 400 400 552 200 400 500 QTx0580Uxxxx
820 820 250 500 500 690 250 500 QTx0820Uxxxx
Note:
Select the appropriate ASTAT-XT, according to the main power supply and motor voltage rating.
Use QT1xxxxUxxxx units for power supply and motors rated at 230V-500V
Use QT2xxxxUxxxx units for power supply and motors rated at 460V-600V
4Ratings in Amps. given for ambient temperature up to 40°C and 1000m altitude.
For higher ambient temperature between 40°C and 50°C, derate the current by 2.5% for each °C that is above 40°C.
5Light duty ratings, only NEMA Class 10 protection is allowed.
6Normal duty ratings, NEMA Class 10 and 20 protections are allowed.
7Heavy duty ratings, NEMA Class 10, 20 and 30 protections are allowed

11 • Technical Specifications
3. TECHNICAL SPECIFICATIONS
3.1 General Specifications
General Information:
Supply Voltage: Line to line 230-690V (to be specified) + 10%-15%
Frequency: 45 – 65 Hz (fixed or variable frequency source)
Control Supply: Either 110VAC or 230VAC (to be specified) +10% - 15%
Control Inputs: Either 90-230VAC or 24VDC (to be specified)
Load: Three phases, three/six wires, squirrel cage induction motor
Connection type: Standard 3 wire U, V, W connection, or 6 wire Inside Delta (programmable)
Rated Insulation Voltage: 1,000V
Rated Impulse Voltage: 4kV
Form designation: Form 1
This product was tested for compliance with IEC 60947-4-2 for class A equipment.
Start-Stop Parameters:
Starter Current: ASTAT-XT’s rated current according to its nameplate.
Motor Current: Motor Full Load Ampere (Im) 50-125%8of Starter Current.
Start/Stop Curve 0
(Standard)
2 standard starting and stopping curves
Pump Control Curves (1!,
2!, 3!)
6 field selectable curves preventing over-pressure during start and water hammer
during stop
Torque Control Curve (4) 2 selectable curves preventing over-pressure during start and water hammer during
stop. In addition, these curves may be used for torque control starting of constant
torque applications.
Kick Start Duration: A pulse of 80% Un, for an adj. time 0.1-1 Sec, for starting high friction loads
Starting Voltage: 10-50% Un (5-80%9)
Initial Current: 100-400% In. A single current control starting curve. It appears when Starting
Voltage is displayed, the up arrow is pressed and Starting Voltage has
reached its max.
Current Limit: 100-700% of Motor Current
Ramp UP Time: 1-30 Sec (1-90 sec9)
Ramp DOWN Time: 1-30 Sec (1-90 sec9)
DUAL Settings Parameters: Secondary start stop characteristic for: Starting Voltage, Starting Current, Current
Limit, Ramp UP, Ramp DOWN and Motor Current.
Energy Saving: Energy save for lightly loaded motors
Slow Speed Torque: Torque while motor is at 1/6 nominal speed
Motor Protection:
Too Many Starts: Maximum number of starts, range: Off or 1-10, during a time period 1-60 min.
Starts Inhibit: Time period 1-60 min, when starting is prevented, after too many starts fault
Long Start Time (stall
protection):
Maximum allowable starting time 1-30 sec. (1-250 Sec9)
Over Current (JAM Fault): Three trip functions:
At all time - If I > 850% of Starter Current it trips the ASTAT-XT within 1 cycle
(overrides the value of the O/C – JAM Delay setting).
At starting process - If I > 850% of Motor Current it trips the ASTAT-XT after O/C
JAM Delay (see here after)
At run time - If I > O/C – JAM Fault setting of Im it trips the ASTAT-XT after O/C
JAM Delay
Electronic Overload: Can be set as IEC Class 10, 20 or NEMA Class 10, 20 or 30.
Can be set to operate at all times, disabled or operate during Run only.
Under Current: Trips when current drops below 20-90% of Motor Current, time delay 1-40 sec.
Optional auto reset after time delay.
Under Voltage: Trips when main voltage drops below 120-600V, time delay 1-10 Sec. Optional Auto
Reset.
Over Voltage: Trips when main voltage increase above 250-750V, time delay 1-10 sec.
8Refer to sections 2.1 page 8 and 2.2 page 9 for detailed information.
9Refer to section 5.5.5 page 50 for expanded setting.

12 • Technical Specifications
Phase Loss, Under/over
Frequency:
Trips when one or two phases are missing, or frequency is < 40Hz or > 65Hz.
Optional auto reset.
Phase Sequence: Trips when phase sequence is wrong
Long Slow Speed Time: Trips if operating at slow speed TRQ for more than 1-30 sec (1-250 sec9)
Wrong Connection: Prevents starting, trips if motor is not connected / incorrectly connected to the
ASTAT-XT (not active in D.Set: Generator Parameters)
Shorted SCR: Trips if one or more SCRs have been shorted
(not active in D.Set: Generator Parameters)
Heat Sink Over
Temperature:
Trips when heat-sink temperature rises above 85°C
External Fault: Trips when an external contact closes for 2 sec.
Motor Thermistor: Trip level setting 1-10KΩ, trips when resistance decreases below the level set
Control:
Displays: LCD in 4 – Field selectable languages and 8 LEDs
Keypad: 6 keys for easy setting
Aux Contact – Immediate: 1 C/O, 8A, 250VAC, 2000VA
Aux Contact – End Of
Ramp:
1 C/O, 8A, 250VAC, 2000VA
Fault Contact: 1 C/O, 8A, 250VAC, 2000VA
Communication: RS 485 with Modbus protocol for full control and supervision
Communication (optional): Profibus DPV1 for full control and supervision
Communication (optional): DeviceNettm for full control and supervision
Temperatures Operating: -10° to 50°C
Storage: -20° to 70°C
Standards:
Dielectric Test: 2500VAC
Degree of Protection: IP 20 for QTx0008 - QTx0072 ; IP 00 for QTx0085 – QTx1400
Pollution Degree: 3
EMC Emissions: EN 61000-6-4 CISPR 11 Class A
Immunity: EN 61000-6-2 ESD 8KV air, IEC 801-2;
Electric RF field 10 V/m, 20-1000Mhz, IEC 801-3
Fast transients 2KV, IEC 801-4
Safety: EN IEC 600947-4-2 and EN IEC 60947-1 Related to safety requirements.
UL508C
Rated Operational Current AC:53a:4-30: 50-4
Normal Service Conditions:
Altitude: Up to 1000m.
Humidity: 95% at 50°C or 98% at 45˚C
Fan and Control Consumption Ratings:
QTx0008 to QTx0031:No fan Total approximate consumption: 150VA
QTx0044 to QTx0072:Fan 35 VA Total approximate consumption 185VA
QTx0085 to QTx0170 :Fan 60 VA Total approximate consumption 210VA
QTx0210 to QTx0390 : Fans 105 VA (35VA x 3) Total approximate consumption 255VA
QTx0460 to QTx1400A : Fans 150 VA (50VA x 3) Total approximate consumption 300VA

13 • Technical Specifications
3.2 Weight
Model Weight
Kg Lbs
QTx0008Uxxxx 4.2 9.3
QTx0017Uxxxx 4.2 9.3
QTx0031Uxxxx 5.3 11.7
QTx0044Uxxxx 6.7 14.8
QTx0058Uxxxx 6.7 14.8
QTx0072Uxxxx 6.7 14.8
QTx0085Uxxxx 15.2 33.5
QTx0105Uxxxx 15.2 33.5
QTx0145Uxxxx 15.2 33.5
QTx0170Uxxxx 15.2 33.5
QTx0210Nxxxx 32.7 72.1
QTx0210Uxxxx 46.5 102.5
QTx0310Nxxxx 32.7 72.1
QTx0310Uxxxx 46.5 102.5
QTx0390Nxxxx 32.7 72.1
QTx0390Uxxxx 46.5 102.5
QTx0460Nxxxx 58.4 128.7
QTx0460Uxxxx 61.8 136.2
QTx0580Nxxxx 63.2 139.3
QTx0580Uxxxx 69.5 153.2
QTx0650Nxxxx 64.8 142.9
QTx0820Uxxxx 69.5 153.2
QTx0950Nxxxx 86.7 191.1
QTx1100Nxxxx 169.8 374.3
QTx1400Nxxxx 175.5 386.9
3.3 I/O Terminal Board Specifications
Refer to drawing on page 17.
Terminal Function Description
1L1, 3L2, 5L3 Connection to mains voltage up
to 690V
Thyristor’s PIV rating, internal circuitry and insulation defines
three voltage levels:
QT 1 x : for 230-500V +10%/ -15% 50/60Hz
QT 2 x: for 460-600V +10% /-15% 50/60Hz
QT 3 x: for 690V +10% /-15% 50/60Hz
Each ASTAT-XT is suitable for one of the above levels & for
50/60 Hz.
A, B, C Preparation for bypass
connection
Bypass preparation is standard in all models.
All models from ASTAT-XT 950A and up must be operated
with a bypass contactor.
Refer to section 5.3 page 47 for more details.
2T1, 4T2, 6T3 Connection to motor
Connect motor’s terminals to these terminals/busbars.
G Connection to ground For proper operation and for safety reasons soft ASTAT-XT
must be properly grounded.
Terminal L Control phase The control voltage operates the electronic circuitry and the
fans (when they exist).
Terminal N Control neutral (return) Two control voltages are available:
QT x xxxx x 1 x x S for 110V +10%/-15% 50/60Hz
QT x xxxx x 2 x x S for 230V +10%/-15% 50/60Hz

14 • Technical Specifications
Terminal Function Description
Terminal F Fan control An internal jumper, connected between the fan and
terminal 2 enables three modes of operation (refer to section
5.6 page 51).
For fan power consumption, see technical specification in
section 3 page 11.
Terminal 4 Input – STOP command.
•Input from a N.C. contact
•To stop the motor, disconnect
Control Input voltage from
terminal 4 for at least
250mSec. (no SOFT STOP)
•Control Input voltage (STOP, SOFT STOP, START, terminal
inputs 7 and 8) can be the same as Control Supply
(terminals 1, 3) or voltage from a different source.
•The Control Inputs are opto-coupled and isolated from the
microprocessor circuitry.
Terminal 5 Input – SOFT STOP command10.
•Input from a N.C. contact
•To SOFT STOP the motor
disconnect Control Input
voltage from terminal 5 for at
least 250mS
Control Input voltages available:
QT x xxxx x x 1 x S for 90-230V +10%/-15% 50/60Hz.
QT x xxxx x x 2 x S for 24VDC +10%/-15%.
Terminal 6 Input – START command11.
•Input from a N.O. contact.
•To SOFT START the motor,
connect Control Input voltage
to terminal 4 for at least
250mSec.
Terminal 7 Programmable input – Energy
Save / Slow Speed / Reset
Refer to section 4.7.8.1 page 41.
Terminal 8 Programmable input – Dual Set
/ Reverse / Reset
Terminal 9 12 Common to terminals 4-8.
This terminal is a reference for terminals 4, 5, 6, 7 &
8.
Terminal 10 Immediate Relay (N.O.) Immediate Relay (RUN relay) is the immediate output relay.
•Voltage free 8A, 250VAC, 2000VA max.
Terminal 11 Immediate Relay (N.C.) •The relay is energized upon the START signal.
Terminal 12 Immediate Relay (Common) •The relay is de-energized when one of the following occurs:
Fault, Control Supply outage or STOP signal.
•When SOFT STOP is operated - the relay is de-energized at
the end of the SOFT STOP process.
•The Immediate Relay (RUN relay) can be used for the
following purposes: Release a brake of a motor, Interlock
with other systems, Signalling, Delay the opening of a line
contactor at the end of SOFT STOP, thus allowing current to
decrease to zero before opening the contactor or to switch
to / from DUAL settings with a time delay from the START
signal (see Special Starting section 6.2.3.1 page 57).
•The relay incorporates ON and OFF delays of 0-3600 sec.
each. Refer to section 4.7.8 page 40 for Relay ON Delay
programming.
Terminal 13 Programmable Fault Output
relay (N.O.)
Voltage free 8A, 250VAC, 2000VA max. changes its position
upon fault.
Terminal 14 Programmable Fault Output
relay (N.C.)
The contact is programmable to function as At Fault
Close or At Fault Open.
10 If SOFT STOP is not required, connect a jumper between terminals 4 and 5.
11 Motor will start only if STOP (terminal 4) and SOFT STOP (terminal 5) terminals are connected to Control Input voltage.
To reset a fault the START command must be removed.
12 When Control Supply and Control Input voltage are from the same source, connect a jumper between terminals 3 and 9.

15 • Technical Specifications
Terminal Function Description
Terminal 15 Programmable Fault Output
relay (Common)
When the At Fault Close function is selected, the relay
is energized upon fault. The contact returns to its original
position when one of the following occurs:
•The fault has been removed and ASTAT-XT was reset.
•Disconnection of Control Supply
When the At Fault Open function is selected, the relay is
energized immediately when the Control Supply is connected
and de-energizes when one of the following occurs:
•Fault
•Control Supply disconnection
Refer to section 4.7.8 page 40 for PROG. Fault Relay
programming.
Terminal 16 Programmable EOR (End Of
Ramp) Output relay (N.O.)
Voltage free 8A, 250VAC, 2000VA max. changes its position at
the end of ramp, after an adjustable time delay (Contact
Delay), 0 – 120 sec.
Terminal 17 Programmable EOR (End Of
Ramp) Output relay (N.C.)
The contact returns to its original position when Energy
Save is operated, on Soft Stop or Stop signals, on Fault
condition, or upon voltage outage.
Terminal 18 Programmable EOR (End Of
Ramp) Output relay (Common)
The EOR (End Of Ramp) contact can be used for:
•Closing a bypass contactor
•Activating a valve after compressor has reached full speed
•Loading a conveyor after motor reached full speed.
Refer to section 4.7.3 page 29 for EOR Relay Delay
programming
Terminal 19 External Fault input Input from a N.O. contact that is connected between
terminals 19 and 21. The ASTAT-XT will trip 2 seconds after
the contact closes.
Notes:
•Wires connecting the External Fault contact to terminal 19
should not exceed 1 meter in length.
•External Fault can be used only when terminal 21 is
connected to neutral or ground.
•Only potential free contacts may be connected to terminal
19.
•Do not connect any voltage to terminal 19.
•Any connection of voltage to this terminal may disrupt
ASTAT-XT operation, and cause ASTAT-XT or motor damage.
•Refer to section 8.12 page 67 for the External Fault wiring
diagram.
Terminal 21 Neutral connection When a mains neutral wire is available, connect terminal 21
to neutral. Terminal 21 serves only as a voltage reference to
the control circuitry.
Caution:
•ASTAT-XT circuitry incorporates an internal artificial neutral,
which should only be used, when the mains system is not
grounded and mains neutral connection is not available.
•Only potential free contacts may be connected to terminal
21.
•Do not connect any voltage to terminal 21.
Any connection of voltage to this terminal may disrupt
ASTAT-XT operation, and cause ASTAT-XT or motor damage.
•Refer to section 8.1 on page 62 for terminal 21 connection.

16 • Technical Specifications
Terminal Function Description
Terminal SG No connection •Standard RS485, half duplex with Modbus protocol, baud
rate 1200, 2400, 4800, 9600 BPS.
Terminal D- RS-485 communication (-) •Twisted shielded pair should be used.
Connect shield to ground on the PLC/Computer side.
Terminal D+ RS-485 communication (+) •Terminals 4 & 5 must be wired to Control Supply for
operation in communication mode (refer to section 8.16
page 70 for wiring diagram).
•Up 32 units can be connected for Modbus RS485
communication. For reliable communication, units should
be installed in the vicinity of 200m maximum, from the first
to the last unit.
•Refer to section 4.7.9 page 42 for programming.
•Refer to Appendix A of this manual for Modbus protocol
manual.
Terminal 28 Thermistor input (T1) Thermistor input is programmable as a PTC or NTC type
thermistor. The trip value is adjustable between 1-10Kohm,
preset delay of 2 Sec.
Terminal 29 Thermistor input (T2)
Connect thermistor and/or Analog output shield to ground
terminal.
Terminal 30 Ground Analog output (0-10VDC or 0-20mA or 4-20mA)
Terminal 31 Analog output (-) Reflects motor current and is related to 2xIm. i.e., Full scale
(10VDC or 20mA) is related to 2xIm.
Terminal 32 Analog output (+) Note:
Refer to section 5.7 page 51 for analog output PCB dip switch
setting.
•Refer to section 4.7.8 page 40 for Analog Output
programming.
•Refer to section 4.7.7 page 38 for Thermistor Type and
Thermistor Trip programming.
D-9 connector Profibus communication
(optional)
•Profibus DPV0 and DPV1, up to 12 MBPS.
•D type 9 pin connector is applied.
•Control, monitoring and setting parameters can be achieved
via the Profibus connection.
•Setting is possible only when DPV1 is implemented.
•Refer to section 4.7.10 page 42 for programming.
•Refer to Appendix B of this manual for Profibus protocol
manual.
Terminal V- 0 Volt external power supply
Terminal CL Negative data line
Terminal Dr Cable shield
Terminal CH Positive data line
Terminal V+
DeviceNet communication
(optional)
+24V external power supply

17 • Technical Specifications
3.4 I/O Wiring

18 • Technical Specifications
3.5 Ordering Information
Notes:
cUL Certification
(*1) – ASTAT-XT up to 600V, and up to 170A (Cat Numbers up to to QT10170_ or QT20170) are always cUL
certified. Option “N” not available
- Units QT1 or QT2 from QTx0950_ up to QTxx1400 are not UL certified. Option “U” not available.
- Units QT3x, rated to 690V, are not UL certified. Option “U” not available
Control and Inputs Voltage
(*2) ASTAT XT standard Control Voltage configuration is option 2, Voltage 230VAC, +10%, -15%
(*3) ASTAT XT standard configuration for Inputs is option 1, Voltage 90-230VAC, +10%, -15%
3.5.1 Ordering Accessories
Catalog Number Description
QTAKPADKIT1 Keypad mounting kit for ASTAT-XT up to 72A
QTAKPADKIT2 Keypad mounting kit for ASTAT-XT above 72A

19 • Technical Specifications
3.6 Operating Modes
Operating Mode Key Description
Starting Voltage 1 5 to 80% Un. Adjustable via Starting Voltage parameter.
Kick Start 2 Fixed level of 80% Un with an adjustable time, 0-1 sec., via Kickstart
Time parameter.
Acceleration Ramp 3
1-30 sec. (1-9013 sec.). Adjustable via Ramp UP Time.
Secondary ramp 1-30sec. (1-9013 sec.). Adjustable via Ramp UP-2
parameter.
Ramp up modes available are:
Soft Start Curve 0 (Standard)
Soft Start Curve 1!!-3!!
Soft Start Curve 4(Torque) for linear torque control
4 Fast ramp (if the motor is up to speed before the end of normal ramp time)
Running mode 5 Nominal voltage
Soft stop mode 6
Deceleration ramp 1-30sec. (1-9013 sec.). Adjustable via Ramp DOWN Time.
Secondary ramp 1-30sec. (1-9013 sec.). Adjustable via Ramp DOWN-2
parameter.
Ramp down modes available are:
Soft Stop Curve 0 (Standard)
Soft Stop Curve 1!!-3!!
Soft Stop Curve 4(Torque) for linear torque control
7 Current limiting set point (100-500%xMotor Current)
8
Acceleration ramp (continuation after motor amps drop below the current
limit).
9 Standard stopping (coast to rest)
Starting by voltage ramp:
Starting by current limitation:
13 Refer to section 5.5.5 page 50 for expanded setting.

20 • Control Keypad
4. CONTROL KEYPAD
The control keypad is the interface between the ASTAT-XT and the user.
The ASTAT-XT control keypad features:
Eight indication LEDs (On, Start, Run, Soft Stop, Stop, Save/Slow Speed, Dual Set/Reverse, Fault)
Two lines of 16 alphanumeric characters each with selectable languages – English, Italian, German, and Spanish.
Six push-buttons - Mode, Reset, Select, Set, Up (▲) and Down (▼) keys.
ASTAT-XT control keypad
4.1 LCD Arrangement
Starting Voltage
30%
Upper line displays the function.
Lower line displays the setting and\or measured values.
(3)
(1)
(2)
This manual suits for next models
24
Table of contents
Other GE Controllers manuals

GE
GE PACSystems* RX3i User manual

GE
GE GPS2BHA User manual

GE
GE VersaMax IC200PWR001 User manual

GE
GE ASTAT XL User manual

GE
GE PMC423 Series Application guide

GE
GE Multilin F650 User manual

GE
GE Becker VRP-B-CH Series User manual

GE
GE Masoneilan 4700E User manual

GE
GE C30 User manual

GE
GE M5 Assembly instructions
Popular Controllers manuals by other brands

BTF LIGHTING
BTF LIGHTING SP107E instructions

Watlow
Watlow EZ-ZONE PM Express user manual

Venmar
Venmar 40455 Installation and owner's guide

Carel
Carel WB000S series quick start guide

Vacon
Vacon 100X series Installation and maintenance manual

Mitsubishi Electric
Mitsubishi Electric MELSEC Q Series user manual