GE AF-650 GP Series User manual

AF-650 GPTM
General Purpose Drive
(230V to 50HP, 460/575V to 100HP)
Operating Instructions
The instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be
desired or should particular problems arise which are not covered suciently for the purchaser’s purposes, the
matter should be referred to the GE company.
AF-650 GP is a trademark of the General Electric Company.
GE
41 Woodford Avenue
Plainville, CT 06062
www.geelectrical.com/drives
130R0356 *MG34F202* DET-607B
GE

Safety
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when
connected to AC mains input power. Installation, start up,
and maintenance should be performed by qualified
personnel only. Failure to perform installation, start up, and
maintenance by qualified personnel could result in death
or serious injury.
High Voltage
Frequency converts are connected to hazardous mains
voltages. Extreme care should be taken to protect against
shock. Only trained personnel familiar with electronic
equipment should install, start, or maintain this equipment.
WARNING
UNINTENDED START!
When the frequency converter is connected to AC mains,
the motor may start at any time. The frequency converter,
motor, and any driven equipment must be in operational
readiness. Failure to be in operational readiness when the
frequency converter is connected to AC mains could result
in death, serious injury, equipment, or property damage.
Unintended Start
When the frequency converter is connected to the AC
mains, the motor may be started by means of an external
switch, a serial bus command, an input reference signal, or
a cleared fault condition. Use appropriate cautions to
guard against an unintended start.
WARNING
DISCHARGE TIME!
Frequency converters contain DC link capacitors that can
remain charged even when AC mains is disconnected. To
avoid electrical hazards, remove AC mains from the
frequency converter before doing any service or repair and
wait the amount of time specified in Table 1.1. Failure to
wait the specified time after power has been removed
prior to doing service or repair on the unit could result in
death or serious injury.
Voltage (V) Minimum waiting time (minutes)
415
200 - 240 1/3 - 5HP 7.5 - 50HP
380 - 480 1/2 - 10HP 15 - 100HP
525 - 600 1/2 - 10HP 15 - 100HP
525 - 690 15 - 100HP
High voltage may be present even when the warning LEDs are
off!
Discharge Time
Symbols
The following symbols are used in this manual.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
CAUTION
Indicates a situation that may result in equipment or
property-damage-only accidents.
NOTE
Indicates highlighted information that should be regarded
with attention to avoid mistakes or operate equipment at
less than optimal performance.
Approvals
Safety AF-650 GP Operating Instructions

Safety AF-650 GP Operating Instructions

Contents
1 Introduction
4
1.1 Purpose of the Manual 6
1.2 Additional Resources 6
1.3 Product Overview 6
1.4 Internal Frequency Converter Controller Functions 6
1.5 Unit Sizes and Power Ratings 8
2 Installation
9
2.1 Installation Site Check List 9
2.2 Frequency Converter and Motor Pre-installation Check List 9
2.3 Mechanical Installation 9
2.3.1 Cooling 9
2.3.2 Lifting 10
2.3.3 Mounting 10
2.3.4 Tightening Torques 10
2.4 Electrical Installation 11
2.4.1 Requirements 12
2.4.2 Earth (Grounding) Requirements 12
2.4.2.1 Leakage Current (>3,5mA) 13
2.4.2.2 Grounding Using Shielded Cable 13
2.4.3 Motor Connection 13
2.4.4 AC Mains Connection 14
2.4.5 Control Wiring 14
2.4.5.1 Access 14
2.4.5.2 Control Terminal Types 15
2.4.5.3 Wiring to Control Terminals 16
2.4.5.4 Using Screened Control Cables 16
2.4.5.5 Control Terminal Functions 17
2.4.5.6 Terminal 53 and 54 Switches 17
2.4.5.7 Terminal 37 17
2.4.6 Serial Communication 20
3 Start Up and Functional Testing
21
3.1 Pre-start 21
3.1.1 Safety Inspection 21
3.1.2 Start Up Check List 22
3.2 Applying Power to the Frequency Converter 23
3.3 Basic Operational Programming 23
3.4 Auto Tune 24
3.5 Check Motor Rotation 24
Contents AF-650 GP Operating Instructions
1

3.6 Local-control Test 24
3.7 System Start Up 25
4 User Interface
26
4.1 Keypad 26
4.1.1 Keypad Layout 26
4.1.2 Setting Keypad Display Values 27
4.1.3 Display Menu Keys 27
4.1.4 Navigation Keys 28
4.1.5 Operation Keys 28
4.2 Back Up and Copying Parameter Settings 28
4.2.1 Uploading Data to the Keypad 29
4.2.2 Downloading Data from the Keypad 29
4.3 Restoring Default Settings 29
4.3.1 Recommended Initialisation 29
4.3.2 Manual Initialisation 29
5 About Frequency Converter Programming
30
5.1 Introduction 30
5.2 Programming Example 30
5.3 Control Terminal Programming Examples 33
5.4 International/North American Default Parameter Settings 33
5.5 Parameter Data Check 34
5.6 Parameter Menu Structure 35
5.6.1 Main Menu Structure 36
5.7 Remote Programming with DCT-10 39
6 Application Set-Up Examples
40
6.1 Introduction 40
6.2 Application Examples 40
7 Status Messages
46
7.1 Status Display 46
7.2 Status Message Definitions Table 46
8 Warnings and Alarms
49
8.1 System Monitoring 49
8.2 Warning and Alarm Types 49
8.3 Warning and Alarm Displays 49
8.4 Warning and Alarm Definitions 50
8.4.1 Fault Messages 52
9 Basic Troubleshooting
58
Contents AF-650 GP Operating Instructions
2

1Introduction
Illustration 1.1 Exploded View Unit Sizes 12-13, IP20
1 Keypad 10 Motor output terminals 96 (U), 97 (V), 98 (W)
2 RS-485 serial bus connector (+68, -69) 11 Relay 1 (01, 02, 03)
3 Analog I/O connector 12 Relay 2 (04, 05, 06)
4 Keypad input plug 13 Brake (-81, +82) and load sharing (-88, +89) terminals
5 Analog switches (A53), (A54) 14 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
6 Cable strain relief / PE ground 15 USB connector
7 Decoupling plate 16 Serial bus terminal switch
8 Grounding clamp (PE) 17 Digital I/O and 24 V power supply
9 Shielded cable grounding clamp and strain relief 18 Control cable cover plate
Introduction AF-650 GP Operating Instructions
4
1
1

Illustration 1.2 Exploded View Unit Sizes 2X and 3X, IP55/66
1 Keypad 11 Relay 2 (04, 05, 06)
2Cover 12Liftingring
3 RS-485 serial bus connector 13 Mounting slot
4 Digital I/O and 24 V power supply 14 Grounding clamp (PE)
5 Analog I/O connector 15 Cable strain relief / PE ground
6 Cable strain relief / PE ground 16 Brake terminal (-81, +82)
7 USB connector 17 Load sharing terminal (DC bus) (-88, +89)
8 Serial bus terminal switch 18 Motor output terminals 96 (U), 97 (V), 98 (W)
9 Analog switches (A53), (A54) 19 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
10 Relay 1 (01, 02, 03)
Introduction AF-650 GP Operating Instructions
5
11

1.1 Purpose of the Manual
This manual is intended to provide detailed information for
the installation and start up of the frequency converter.
Chapter 2 Installation provides requirements for
mechanical and electrical installation, including input,
motor, control and serial communications wiring, and
control terminal functions. Chapter 3 Start Up and
Functional Testing provides detailed procedures for start
up, basic operational programming, and functional testing.
The remaining chapters provide supplementary details.
These include user interface, detailed programming,
application examples, start-up troubleshooting, and specifi-
cations.
1.2 Additional Resources
Other resources are available to understand advanced
drive functions and programming.
•
The Programming Guide DET-618 provides
greater detail on working with parameters and
many application examples.
•
The Design Guide DET-619 is intended to provide
detailed capabilities and functionality to design
motor control systems.
•
Optional equipment is available that may change
some of the procedures described. Be sure to see
the instructions supplied with those options for
specific requirements.
1.3 Product Overview
A frequency converter is an electronic motor controller
that converts AC mains input into a variable AC waveform
output. The frequency and voltage of the output are
regulated to control the motor speed or torque. The
frequency converter can vary the speed of the motor in
response to system feedback, such as position sensors on a
conveyor belt. The frequency converter can also regulate
the motor by responding to remote commands from
external controllers.
In addition, the frequency converter monitors the system
and motor status, issues warnings or alarms for fault
conditions, starts and stops the motor, optimizes energy
efficiency, and offers many more control, monitoring, and
efficiency functions. Operation and monitoring functions
are available as status indications to an outside control
system or serial communication network.
1.4 Internal Frequency Converter Controller
Functions
Below is a block diagram of the frequency converter's
internal components. See Table 1.1 for their functions.
Illustration 1.3 Block Diagram
Introduction AF-650 GP Operating Instructions
6
1
1

Area Title Functions
1Mainsinput
•
Three-phase AC mains power
supply to the drive
2Rectifier
•
The rectifier bridge converts
the AC input to DC current to
supply inverter power
3DCbus
•
The frequency converter's
intermediate DC-bus circuit
handles the DC current
4 DC reactors
•
Filter the intermediate DC
circuit voltage
•
Prove line transient protection
•
Reduce RMS current
•
Raise the power factor
reflected back to the line
•
Reduce harmonics on the AC
input
5 Capacitor bank
•
Stores the DC power
•
Provides ride-through
protection for short power
losses
6Inverter
•
Converts the DC into a
controlled PWM AC waveform
for a controlled variable
output to the motor
7 Output to motor
•
Regulated three-phase output
power to the motor
8 Control circuitry
•
Input power, internal
processing, output, and motor
current are monitored to
provide efficient operation
and control
•
User interface and external
commands are monitored and
performed
•
Status output and control can
be provided
Table 1.1 Internal Components
Introduction AF-650 GP Operating Instructions
7
11

1.5 Unit Sizes and Power Ratings
Unit sizes
IP20 / Open Chassis IP55 / Nema 12 and IP66 / Nema 4/4X Indoor
Volts 12 13 23 24 33 34 15 21 22 31 32
200-240 1/3-3 HP 5 HP 7.5-10 HP 15-20 HP 25-30 HP 40-50 HP 1/3-5 HP 7.5-10 HP 15 HP 20-30 HP 40-50 HP
380-480 1/2-5 HP 7.5-10 HP 15-20 HP 25-40 HP 50-60 HP 75-100 HP 1-10 HP 15-20 HP 25-30 HP 40-60 HP 75-100 HP
525-600 - 1-10 HP 15-20 HP 25-40 HP 50-60 HP 75-100 HP 1-10 HP 15-20 HP 25-30 HP 40-60 HP 75-100 HP
525-690 - - - - - - - - 15-30 HP - 40-100 HP
Introduction AF-650 GP Operating Instructions
8
1
1

2 Installation
2.1 Installation Site Check List
•
The drive relies on the ambient air for cooling.
Observe the limitations on ambient air
temperature for optimal operation
•
Ensure that the installation location has sufficient
support strength to mount the drive
•
Keep the drive interior free from dust and dirt.
Ensure that the components stay as clean as
possible. In construction areas, provide a
protective covering. Optional IP55 (NEMA 12)
enclosures may be necessary.
•
Keep the manual, drawings, and diagrams
accessible for detailed installation and operation
instructions. It is important that the manual is
available for equipment operators.
•
Locate equipment as near to the motor as
possible. Keep motor cables as short as possible.
Check the motor characteristics for actual
tolerances. Do not exceed
•
300m (1000ft) for unshielded motor
leads
•
150m (500ft) for shielded cable.
2.2 Frequency Converter and Motor Pre-
installation Check List
•
Compare the model number of unit on the
nameplate to what was ordered to verify the
proper equipment
•
Ensure each of the following are rated for same
voltage:
Mains (power)
Drive
Motor
•
Ensure that drive output current rating is equal to
or greater than motor full load current for peak
motor performance
Motor size and drive power must match
for proper overload protection
If drive rating is less than motor, full
motor output cannot be achieved
2.3 Mechanical Installation
2.3.1 Cooling
•
To provide cooling airflow, mount the unit to a
solid flat surface or to the optional back plate
(see 2.3.3 Mounting)
•
Top and bottom clearance for air cooling must be
provided. Generally, 100-225mm (4-10in) is
required. See Illustration 2.1 for clearance
requirements
•
Improper mounting can result in over heating
and reduced performance
•
Derating for temperatures starting between 40°C
(104°F) and 50°C (122°F) and elevation 1000m
(3300ft) above sea level must be considered. See
the equipment Design Guide for detailed
information.
Illustration 2.1 Top and Bottom Cooling Clearance
Size 12-15 21-24 31, 33 32, 34
a/b (mm) 100 200 200 225
Table 2.1 Minimum Airflow Clearance Requirements
Installation AF-650 GP Operating Instructions
9
2
2

2.3.2 Lifting
•
Check the weight of the unit to determine a safe
lifting method
•
Ensure that the lifting device is suitable for the
task
•
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
•
For lifting, use hoist rings on the unit, when
provided
2.3.3 Mounting
•
Mount the unit vertically
•
The drive allows side by side installation
•
Ensure that the strength of the mounting location
will support the unit weight
•
Mount the unit to a solid flat surface or to the
optional back plate to provide cooling airflow
(see Illustration 2.2 and Illustration 2.3)
•
Improper mounting can result in over heating
and reduced performance
•
Use the slotted mounting holes on the unit for
wall mounting, when provided
Illustration 2.2 Proper Mounting with Back Plate
Item A is a back plate properly installed for required
airflow to cool the unit.
Illustration 2.3 Proper Mounting with Railings
NOTE
Back plate is needed when mounted on railings.
2.3.4 Tightening Torques
See 10.4.1 Connection Tightening Torques for proper
tightening specifications.
Installation AF-650 GP Operating Instructions
10
2
2

2.4 Electrical Installation
This section contains detailed instructions for wiring the drive. The following tasks are described.
•
Wiring the motor to the drive output terminals
•
Wiring the AC mains to the drive input terminals
•
Connecting control and serial communication wiring
•
After power has been applied, checking input and motor power; programming control terminals for their intended
functions
Illustration 2.4 Basic Wiring Schematic Drawing.
A=Analog, D=Digital
Terminal 37 is used for Safe Stop. For Safe Stop installation instructions, refer to the Design Guide.
*The brake chopper factory option must be ordered to use dynamic braking resistors
**This is available when ordering the brake chopper option on unit size 23 and above drives.
Installation AF-650 GP Operating Instructions
11
2
2

2.4.1 Requirements
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous.
All electrical work must conform to national and local
electrical codes. It is strongly recommended that instal-
lation, start up, and maintenance be performed only by
trained and qualified personnel. Failure to follow these
guidelines could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three
separate metallic conduits or use separated shielded cable
for high frequency noise isolation. Failure to isolate power,
motor and control wiring could result in less than
optimum frequency converter and associated equipment
performance.
For your safety, comply with the following requirements.
•
Electronic controls equipment is connected to
hazardous mains voltage. Extreme care should be
taken to protect against electrical hazards when
applying power to the unit.
•
Run motor cables from multiple frequency
converters separately. Induced voltage from
output motor cables run together can charge
equipment capacitors even with the equipment
turned off and locked out.
Overload and Equipment Protection
•
An electronically activated function within the
frequency converter provides overload protection
for the motor. The overload calculates the level of
increase to activate timing for the trip (controller
output stop) function. The higher the current
draw, the quicker the trip response. The overload
provides Class 20 motor protection. See
8 Warnings and Alarms for details on the trip
function.
•
Because the motor wiring carries high frequency
current, it is important that wiring for mains,
motor power, and control are run separately. Use
metallic conduit or separated shielded wire.
Failure to isolate power, motor, and control
wiring could result in less than optimum
equipment performance.
•
All frequency converters must be provided with
short-circuit and over-current protection. Input
fusing is required to provide this protection, see
Illustration 2.5. Fuses must be provided by the
installer as part of installation. See maximum fuse
ratings in 10.3 Fuse Tables.
Illustration 2.5 Fuses
Wire Type and Ratings
•
All wiring must comply with local and national
regulations regarding cross-section and ambient
temperature requirements.
•
GE recommends that all power connections be
made with a minimum 75°C rated copper wire.
•
See 10.1 Power-dependent Specifications for
recommended wire sizes.
2.4.2 Earth (Grounding) Requirements
WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground drive
properly in accordance with national and local electrical
codes as well as instructions contained within these
instructions. Ground currents are higher than 3,5mA.
Failure to ground drive properly could result in death or
serious injury.
NOTE
It is the responsibility of the user or certified electrical
installer to ensure correct grounding (earthing) of the
equipment in accordance with national and local electrical
codes and standards.
•
Follow all local and national electrical codes to
ground electrical equipment properly
•
Proper protective grounding for equipment with
ground currents higher than 3,5mA must be
established, see Leakage Current (>3,5mA)
•
A dedicatedground wire is required for input
power, motor power and control wiring
Installation AF-650 GP Operating Instructions
12
2
2

•
Use the clamps provided with on the equipment
for proper ground connections
•
Do not ground one drive to another in a “daisy
chain” fashion
•
Keep the ground wire connections as short as
possible
•
Use of high-strand wire to reduce electrical noise
is recommended
•
Follow motor manufacturer wiring requirements
2.4.2.1 Leakage Current (>3,5mA)
Follow national and local codes regarding protective
earthing of equipment with a leakage current > 3,5mA.
Drive technology implies high frequency switching at high
power. This will generate a leakage current in the earth
connection. A fault current in the drive at the output
power terminals might contain a DC component which can
charge the filter capacitors and cause a transient earth
current. The earth leakage current depends on various
system configurations including RFI filtering, screened
motor cables, and drive power.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3,5mA.
Earth grounding must be reinforced in one of the
following ways:
•
Earth ground wire of at least 10mm
2
•
Two separate earth ground wires both complying
with the dimensioning rules
See EN 60364-5-54 § 543.7 for further information.
Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:
Use RCDs of type B only which are capable of
detecting AC and DC currents
Use RCDs with an inrush delay to prevent faults
due to transient earth currents
Dimension RCDs according to the system configu-
ration and environmental considerations
2.4.2.2 Grounding Using Shielded Cable
Earthing (grounding) clamps are provided for motor wiring
(see Illustration 2.6).
Illustration 2.6 Grounding with Shielded Cable
2.4.3 Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency
converters separately. Induced voltage from output motor
cables run together can charge equipment capacitors even
with the equipment turned off and locked out. Failure to
run output motor cables separately could result in death
or serious injury.
•
For maximum wire sizes see 10.1 Power-dependent
Specifications
•
Comply with local and national electrical codes
for cable sizes
•
Motor wiring knockouts or access panels are
provided at the base of IP21 and higher (Nema 1,
12, and 4/4X Indoor) units
•
Do not install power factor correction capacitors
between the frequency converter and the motor
•
Do not wire a starting or pole-changing device
between the frequency converter and the motor
•
Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W)
•
Ground the cable in accordance with grounding
instructions provided
•
Torque terminals in accordance with the
information provided in 10.4.1 Connection
Tightening Torques
Installation AF-650 GP Operating Instructions
13
2
2

•
Follow motor manufacturer wiring requirements
Illustration 2.7 represents mains input, motor, and earth
grounding for basic frequency converters. Actual configu-
rations vary with unit types and optional equipment.
Illustration 2.7 Example of Motor, Mains and Earth Wiring
2.4.4 AC Mains Connection
•
Size wiring based upon the input current of the
drive. For maximum wire sizes see 10.1 Power-
dependent Specifications.
•
Comply with local and national electrical codes
for cable sizes.
•
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see Illustration 2.7).
•
Depending on the configuration of the
equipment, input power will be connected to the
mains input terminals or the input disconnect.
•
Ground the cable in accordance with grounding
instructions provided in 2.4.2 Earth (Grounding)
Requirements
•
All frequency converters may be used with an
isolated input source as well as with ground
reference power lines. When supplied from an
isolated mains source (IT mains or floating delta)
or TT/TN-S mains with a grounded leg (grounded
delta), set SP-50 RFI Filter to OFF. When off, the
internal RFI filter capacitors between the chassis
and the intermediate circuit are isolated to avoid
damage to the intermediate circuit and to reduce
earth capacity currents in accordance with IEC
61800-3.
2.4.5 Control Wiring
•
Isolate control wiring from high power
components in the frequency converter.
•
If the frequency converter is connected to a
thermistor, for PELV isolation, optional thermistor
control wiring must be reinforced/double
insulated. A 24 VDC supply voltage is
recommended.
2.4.5.1 Access
•
Remove access cover plate with a screw driver.
See Illustration 2.8.
•
Or remove front cover by loosening attaching
screws. See Illustration 2.9.
Tightening torque for front cover is 2.0Nm for
unit size 15 and 2.2Nm for unit sizes 2X and 3X.
130BT248
Illustration 2.8 Control Wiring Access for IP20 / Open chassis
enclosures
130BT334.11
Illustration 2.9 Control Wiring Access for IP55 / Nema 12 and
IP66 / Nema 4/4X Indoor
Installation AF-650 GP Operating Instructions
14
2
2

2.4.5.2 Control Terminal Types
Illustration 2.10 and shows the removable frequency
converter connectors. Terminal functions and default
settings are summarized in Table 2.2.
Illustration 2.10 Control Terminal Locations
Illustration 2.11 Terminal Numbers
•
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24V
DC terminal supply voltage, and a common for
optional customer supplied 24V DC voltage. A
digital input for STO (Safe Torque Off) function.
•
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
•
Connector 3 provides two analog inputs, one
analog output, 10V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the DCT-10
•
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
•
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal description
Terminal Parameter
Default
setting Description
Digital inputs/outputs
12, 13 - +24V DC 24V DC supply
voltage. Maximum
output current is
200mA total for all
24V loads. Useable for
digital inputs and
external transducers.
18 E-01 [8] Start
Digital inputs.
19 E-02 [10] Reversing
32 E-05 [0] No
operation
33 E-06 [0] No
operation
27 E-03 [0] No
operation
Selectable for either
digital input or
output. Default setting
is input.
29 E-04 [14] JOG
20 - Common for digital
inputs and 0V
potential for 24V
supply.
37 - Safe Torque
Off (STO)
Safe input. Used for
STO.
Analog inputs/outputs
39 -
Common for analog
output
42 AN-50 [0] No
operation
Programmable analog
output. The analog
signal is 0-20mA or
4-20mA at a
maximum of 500
Ω
50 - +10V DC 10V DC analog supply
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
53 AN-1# Reference Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
54 AN-2# Feedback
55 -
Common for analog
input
Installation AF-650 GP Operating Instructions
15
2
2

Terminal description
Terminal Parameter
Default
setting Description
Serial communication
61 -
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing
EMC problems.
68 (+) O-3# RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-) O-3#
Relays
01, 02, 03 E-24
[0] No
operation
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
04, 05, 06 E-24 [0] No
operation
Table 2.2 Terminal Description
2.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
drive for ease of installation, as shown in Illustration 2.10.
1. Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Illustration 2.12.
2. Insert the bared control wire into the contact.
3. Remove the screwdriver to fasten the control wire
into the contact.
4. Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See 10.1 Power-dependent Specifications for control terminal
wiring sizes.
See 6 Application Set-Up Examples for typical control wiring
connections.
Illustration 2.12 Connecting Control Wiring
2.4.5.4 Using Screened Control Cables
Correct screening
The preferred method in most cases is to secure control
and serial communication cables with screening clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the earth potential between the frequency converter and
the PLC is different, electric noise may occur that will
disturb the entire system. Solve this problem by fitting an
equalizing cable next to the control cable. Minimum cable
cross section: 16 mm
2
.
50/60Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the screen-to-
ground with a 100nF capacitor (keeping leads short).
Avoid EMC noise on serial communication
This terminal is connected to earth via an internal RC link.
Use twisted-pair cables to reduce interference between
conductors. The recommended method is shown below:
Alternatively, the connection to terminal 61 can be
omitted:
Installation AF-650 GP Operating Instructions
16
2
2

2.4.5.5 Control Terminal Functions
Drive functions are commanded by receiving control input
signals.
•
Each terminal must be programmed for the
function it will be supporting in the parameters
associated with that terminal. See Table 2.2 for
terminals and associated parameters.
•
It is important to confirm that the control
terminal is programmed for the correct function.
See 4 User Interface for details on accessing
parameters and for details on programming.
•
The default terminal programming is intended to
initiate drive functioning in a typical operational
mode.
2.4.5.6 Terminal 53 and 54 Switches
•
Analog input terminals 53 and 54 can select
either voltage (-10 to 10V) or current (0/4-20mA)
input signals
•
Remove power to the drive before changing
switch positions
•
Set switches A53 and A54 to select the signal
type. U selects voltage, I selects current.
•
The switches are accessible when the Keypad has
been removed (see Illustration 2.13). Note that
some option cards available for the unit may
cover these switches and must be removed to
change switch settings. Always remove power to
the unit before removing option cards.
•
Terminal 53 default is for a speed reference signal
in open loop set in DR-61 Terminal 53 Switch
Setting
•
Terminal 54 default is for a feedback signal in
closed loop set in DR-63 Terminal 54 Switch
Setting
130BT310.10
Illustration 2.13 Location of Terminals 53 and 54 Switches and
Bus Termination Switch
2.4.5.7 Terminal 37
Terminal 37 Safe Stop Function
The AF-650 GP and is available with safe stop functionality
via control terminal 37. Safe stop disables the control
voltage of the power semiconductors of the drive output
stage which in turn prevents generating the voltage
required to rotate the motor. When the Safe Stop (T37) is
activated, the drive issues an alarm, trips the unit, and
coasts the motor to a stop. Manual restart is required. The
safe stop function can be used for stopping the drive in
emergency stop situations. In the normal operating mode
when safe stop is not required, use the frequency
converter’s regular stop function instead. When automatic
restart is used – the requirements according to ISO
12100-2 paragraph 5.3.2.5 must be fulfilled.
Liability Conditions
It is the responsibility of the user to ensure personnel
installing and operating the Safe Stop function:
•
Read and understand the safety regulations
concerning health and safety/accident prevention
•
Understand the generic and safety guidelines
given in this description and the extended
description in the Design Guide
•
Have a good knowledge of the generic and safety
standards applicable to the specific application
User is defined as: integrator, operator, servicing,
maintenance staff.
Installation AF-650 GP Operating Instructions
17
2
2
Other manuals for AF-650 GP Series
11
Table of contents
Other GE Controllers manuals
Popular Controllers manuals by other brands

BTF LIGHTING
BTF LIGHTING SP107E instructions

Watlow
Watlow EZ-ZONE PM Express user manual

Venmar
Venmar 40455 Installation and owner's guide

Carel
Carel WB000S series quick start guide

Vacon
Vacon 100X series Installation and maintenance manual

Mitsubishi Electric
Mitsubishi Electric MELSEC Q Series user manual