gefran eView HD IP67 Series Instruction Manual

OPERATING INSTRUCTIONS MANUAL
codice: 80588_10-2019 - ENG
This document is the property of GEFRAN and may not be reproduced or transferred to third parties without authorization.
eView HD IP67
ATTENTION!
This manual must always be available to operators of the
devices described here.
Always make sure that you have the latest version of the
manual, which is available for free download from the GEFRAN
website (www.gefran.com).
Installers and/or maintenance personnel are required to read
this manual and to precisely follow the instructions contained
in it and in its attachments.
GEFRAN will not be liable for any damage to persons and/or
property, or to the product itself, caused by failure to follow
the instructions and observe the warnings given below.
This manual and its attachments may be freely reproduced
as long as they are not changed in any way and every copy
contains this warning and the declaration of ownership by
Gefran S.p.A.

280588_eView HD IP67_02-2019_ENG
REVISION DOCUMENTS
DATE CODE UPDATE N. pages of the document
Copyright © 2018 Gefran Soluzioni
Subject to change without notice
The information contained in this document is provided for informational purposes only. While eorts were made to verify the accuracy of
the information contained in this documentation, it is provided “as is” without warranty of any kind.
Third-party brands and names are the property of their respective owners.
www.gefran.com/en/gefran-soluzioni

380588_eView HD IP67_02-2019_ENG
TABLE OF CONTENTS
1. PRODUCT OVERVIEW................................................... 5
2. STANDARDS AND APPROVALS .................................. 5
3. TECHNICAL SPECIFICATIONS..................................... 7
4. TECHNICAL DATA.......................................................... 9
4.1. Dimensions.............................................................. 10
4.2. Installation Environment and procedure ................ 12
4.3. Safety instruction .................................................... 12
5. CONNECTIONS............................................................ 13
5.1. Ethernet Port ........................................................... 13
6. POWER SUPPLY, GROUNDING AND SHIELDING..... 14
7. BATTERY ...................................................................... 15
8. SPECIAL INSTRUCTION FOR USE ............................ 17
9. GETTING STARTED ..................................................... 17
10. SYSTEM SETTINGS................................................... 18
11. UNPACKING AND PACKING INSTRUCTIONS......... 20

480588_eView HD IP67_02-2019_ENG
INTRODUCTION
The operational guidelines described below is information
which relates to the device, installation, transportation,
storage, assembly, use and maintenance.
This Operating Instruction describes the main features of the
Gefran Soluzioni srl operator panels. The Manual refers to the
following models
The manual contains safety standards that must be respected
for the personal safety and to avoid damage.
Indications of attention are divided into three levels of severity:
DANGER: indicates a failure to observe safety
rules and such failure may cause death or serious
injuries.
SAFETY GUIDE
ATTENTION: indicates a failure to observe safety
rules and that deciency may cause damage.
CAUTION: indicates a failure to observe safety
rules and that deciency may cause defects to the
equipment or inconsistencies.
eView HD 101 IP67 Field-ready HMI 10.1” color TFT, PCAP touchscreen, Ethernet port PoE
eView HD 156 IP67 Field-ready HMI 15.6” color TFT, PCAP touchscreen, Ethernet port PoE
eView HD 215 IP67 Field-ready HMI 21.5” color TFT, PCAP touchscreen, Ethernet port PoE

580588_eView HD IP67_02-2019_ENG
1. PRODUCT OVERVIEW
eView HD IP67 products are ideal for eld installation in
critical areas. High-resolution displays and multitouch PCAP
touchscreen with a robust glass front.
Power-over-Ethernet (PoE) for maximum simplicity of
connection using standard shielded CAT 5 wiring. Full IP
protection with the use of dedicated connectors for the
maximum exibility of installation, from mounting arm to a
simple M22 hole. The product includes environment and
motion sensors to make this device a true IIoT edge device
for Industry 4.0 applications.
The eView HD IP67 product family has been optimized for
use as an embedded browser or as a GF designer HD device.
• Open platform for Linux applications
• Performing HTML5-compatible browser with graphic
accelerator
• Runtime with OPC UA Server and Client
• Built-in sensors (temperature and acceleration)
2. STANDARDS AND APPROVALS
The products have been designed for use in an industrial environment in compliance with the 2014/53/EU
Directive.
The products have been designed in compliance with:
EN 61000-6-4
EN 61000-6-2
EN 61000-6-3
EN 61000-6-1
ETSI EN 301 489-1
ETSI EN 301 489-17
ETSI EN 300 328
EN 62311 *
EN 61010-1
EN 61010-2-201
* Standard radio signal and minimum distance from the body calculated according to EN 62311
Standard radio signal WiFi 2,4GHz
Minimum distance form the body (cm)* 2
* The WiFi antenna is positioned behind the black band above the display.
The products are in compliance with the Restrictions on Certain Hazardous Substances (RoHS) Directive
2011/65/EU
In compliance with the above regulations the products are CE marked.

680588_eView HD IP67_02-2019_ENG
product model name eView HD101-52-00-67
year/week of production 1924
serial number AA00013TF123456789AA
manufacturer address Gefran Soluzioni Srl
Via Sebina, 74
25050 Provaglio d’Iseo (BS)
Product Identication
The product may be identied by the indications in the back
cover. You will have to know the type of unit you are using
for correct usage of the information contained in the guide.
An example of the information reported is shown below:

780588_eView HD IP67_02-2019_ENG
3. TECHNICAL SPECIFICATIONS
Touchscreen technology Projected capacitive - Multitouch
Back-up battery 3V 7mAh Vanadium-Lithium, rechargeable, not user-replacea ble, model VL1220.
Flash 4GB (8GB for eView HD 156 IP67 and eView HD 215 IP67)
RAM 1GB (2GB for eView HD 156 IP67 and eView HD 215 IP67)
Hardware clock Clock/Calendar with back-up battery
Accuracy RTC (at 25°C) <100ppm
ENVIRONMENTAL CONDITIONS
Operating temperature
(surrounding air temperature)
-20 ÷ +55°C (vertical installation) EN 60068-2-14
Storage temperature -30 ÷ +80°C (eView HD 101 IP67)
-20 ÷ +70°C (eView HD 156 IP67, eView HD 215 IP67)
EN 60068-2-1
EN 60068-2-2
EN 60068-2-14
Operating and storage humidity 5 ÷ 85 % RH not-condensing EN 60068-2-30
Vibrations 5 ÷ 9 Hz, 7 mm
9 ÷ 150 Hz, 1 g
EN 60068-2-6
Shock ± 50 g, 11 ms, 3 pulses per axis EN 60068-2-27
Protection class IP67 (requires appropriate connectorisand cables) EN 60529
ELECTROMAGNETIC COMPATIBILITY (EMC)
Radiated disturbance test Class A CISPR 22
CISPR 16-2-3
Electrostatic discharge
immunity test
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic eld immunity
test
80 MHz ÷ 1 GHz, 10V/m
1,4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test ± 2 KV dc power port
± 1 KV signal line
EN 61000-4-4
Surge immunity test ± 0,5 KV dc power port (line to earth)
± 0,5 KV dc power port (line to line)
± 1 KV signal line (line to earth)
EN 61000-4-5
Immunity to conducted
disturbances inducted by
radiofrequency eld
0.15 ÷ 80 MHz, 10V EN 61000-4-6
Power frequency magnetic eld
immunity test
Enclosure, 50/60Hz, 30A/m EN 61000-4-8

880588_eView HD IP67_02-2019_ENG
Durability information
Backlight service life 40000 Hrs. or more
(LED type) (Time of continuos operation until the brightness of the backlight reaches 50% of the
rated value when the surrounding air temperature is 25°C) - see Note 1
Note 1: Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.
Viewing angles
For the viewing angles values (U,D,R,L) of the display types, see the technical data of the respective device.
The viewing angles are specied for the horizontal (L,R) and vertical (U,D) axes in reference to the vertical axis of the display.
The specied viewing angles above always refer to the standard mounting orientation.
Surface resistance
Chemical resistance of the front glass for an exposure time of 24 hours without visible changes:
• Betadine (10% Povidone Solution)
• Cola
• Electrode Gel/Paste
• Hydrogen Peroxide (3% Solution)
• NaCl (0.9% Solution)
• Coee
• Dextrose (5% Glucose Solution)
• Hydrogen chloride (0.5% Solution PH=1)
• Isopropyl Alcohol
• Sodium Hypochlorit
• Ethyl Alcohol (70%-90%)
• Quaternary ammonium compound
Properties multitouch PCAP touchscreen
Number of ngers 5
Glove operation Yes
Passive stylus pens Yes
Active stylus pens No
Hardened front glass Yes
Operation with gloves
Projected capacitive touch screens (PCAP) are suitable for operation with or without gloves.
A large number of gloves (rubber gloves, light/heavy leather gloves, disposable latex gloves, etc.) are supported.
Due to the variety of commercially available gloves, however, Gefran Soluzioni cannot guarantee all types.
Legend: Display viewing angle
UFrom top
D From bottom
LFrom left
R From right

980588_eView HD IP67_02-2019_ENG
4. TECHNICAL DATA
Model eView HD 101 IP67 eView HD 156 IP67 eView HD 215 IP67
Display / Backlight TFT Color / LED
Colors 16M
Resolution 1280X800 1366X768 1920X1080
Diagonal (inches) 10.1” widescreen 15.6” widescreen 21.5” widescreen
Viewing angles
horizontal
Direction L / Direction R
Typ. 85°
Direction L / Direction R
Typ. 80°
Direction L / Direction R
Typ. 89°
Viewing angles
vertical
Direction U / Direction D
Typ. 85°
Direction U / Direction D
Typ. 80°
Direction U / Direction D
Typ. 89°
Dimming yes to 0% yes
CPU ARM Cortex-A9 dual core
800 MHz
Operating System Linux RT
Flash 4GB 8GB
RAM 1GB 2GB 2GB
Ethernet port 10/100 PoE 802.3af/at
USB port 1 (Host v. 2.0, request special connector)
Battery rechargeable
Real Time Clock yes
Power supply 802.3af
Current consumption 12W 19W 32W
Weight 1.2 Kg 4.0 Kg 6.0 Kg

10 80588_eView HD IP67_02-2019_ENG
4.1. Dimensions
MODEL A B C D
eView HD 101 IP67 183.1mm/7.20” 264.5mm/10.41” 16,5mm/0.64” 17mm/0.66”
MODEL A B C D
eView HD 156 IP67 248mm/9.76” 398.6mm/15.69” 26,5mm/1.04” 17mm/0.66”

11 80588_eView HD IP67_02-2019_ENG
MODEL A B C D
eView HD 215 IP67 325.6mm/12.81” 534.1mm/21.02” 26,5mm/1.04” 17mm/0.66”
Rear view

12 80588_eView HD IP67_02-2019_ENG
4.2. Installation Environment and procedure
Avoid prolonged exposition to direct sunlight to avoid the risk
of overheating the device.
The equipment is not intended for installation in contact with
corrosive chemical compounds. Check the resistance of the
front panel to a specic compound before installation.
Do not use tools of any kind (screwdrivers, etc.) to operate
the touch screen of the panel.
The IP67 is guaranteed only if:
• max deviation from the plane surface to the cut-out: O0.5mm
• thickness of the case where is mounted the equipment:
from 1,5mm to 6mm
• max surface roughness where the gasket is applied: O120
um
CAUTION
Tightening torque: 1000Ncm for nut, 130Ncm
for screws
4.3. Safety instruction
For all installation notes, please refer to the
Installation Guide provided with the product.

13 80588_eView HD IP67_02-2019_ENG
5. CONNECTIONS
5.1. Ethernet Port
The Ethernet port have two status indicators. Please see description in gure.
Reserved
Pin Description
1 TX+
2 TX-
3 RX+
4 n/c
5 n/c
6 RX-
7 n/c
8 n/c
Red
OFF: Valid link has NOT been detected
ON: Valid link has been detected
Green
ON: No activity
BLINKING: Activity

14 80588_eView HD IP67_02-2019_ENG
Use a shielded CAT 5 cable or higher
Note: Ensure that the power supply has enough power
capacity for the operation of the equipment.
The unit must always be grounded to earth with shielded
CAT 5 cable. Grounding helps limit the eects of noise due to
electromagnetic interference on the control system.
The earth connection can also be made using the screws
located near the connector. A label helps identify the ground
connection.
All the electronic devices in the control system must be
properly grounded. Grounding must be performed according
to applicable regulations.
6. POWER SUPPLY, GROUNDING AND SHIELDING
The power supply terminal block is shown in the gure below.
Fig. 6.1

15 80588_eView HD IP67_02-2019_ENG
7. BATTERY
These devices are equipped with rechargeable Lithium battery,
not user-replaceable.
The following information is maintained by the battery:
• hardware real-time clock (date and time)
Charge:
At rst installation must be charged for 48 hours.
When the battery is fully charged, it ensures a period of 3
months of date and time back-up at 25°C.
Battery
Fig. 7.3: eView HD 101 IP67
Fig. 7.4: eView HeView HD 156 IP67

16 80588_eView HD IP67_02-2019_ENG
Fig. 7.5: eView HD 215 IP67
ATTENTION
Dispose of batteries according to local
regulations.
ATTENTION
This device cannot be disposed of as a
domestic waste but according to WEEE
European Directive 2012/19/EU

17 80588_eView HD IP67_02-2019_ENG
- The equipment shall only be used in an area of not more than
pollution degree 2, as dened in IEC/EN 60664-1.
- The equipment shall be installed in an enclosure that provides
a degree of protection not less than IP 54 in accordance with
IEC/EN 60079-15.
- Transient protection shall be provided that is set at a level
not exceeding 140 % of the peak rated voltage value at the
supply terminals to the equipment.
- Install the HMI device according to the accompanying
installation instructions.
- Ground the HMI device according to the accompanying
installation instructions.
- Only qualied personnel may install the HMI device or
repair it.
- Care shall be taken not to allow layers of dust to form on the
graphic panel in a way that might cause the accumulation of
static charges. Keep the faceplate of the HMI device clean:
the equipment must be cleaned only with a soft cloth and
neutral soap product. Do not use solvents.
- This device should not be used for purposes and methods
other than indicated in this document and in the
documentation accompanying the product.
eView HD IP67 HMI products delivery configuration is
based on a loader. Use the services of the loader to install
applications on the device such as GF Designer HD runtime
or browsers.
GF Designer HD or higher is required. GF Designer HD is a
software tool that must be properly installed on a computer
running Microsoft Windows.
There are two options to transfer a GF Designer HD application
project to a HMI device:
Ethernet Connect the HMI device to the computer with
an Ethernet network. In GF Designer HD select
the command Run/Download to target. You may
have to ensure that the proper rewall policy has
been congured in the computer to allow GF
Designer HD to access the network.
USB Create an Update Package using GF Designer
HD and copy it to a USB Flash drive (to transfer
via USB, use the dedicated accessory cable).
9. GETTING STARTED
8. SPECIAL INSTRUCTION FOR USE

18 80588_eView HD IP67_02-2019_ENG
10. SYSTEM SETTINGS
eView HD IP67 HMI products have a system settings interface
to allow conguration of system options.
The user interface of System Settings is based on HTML
pages accessible from the HMI screen or remotely using a
Web browser Chrome v44 or higher using port 443. To connect
enter the address https://IP/machine_cong where IP is the
IP address of the HMI device. Default username is “admin”,
default password is “admin”. Use navigation menu on the left
side of the screen to browse through the available options.
The active item of menu is highlighted on the left side of the
screen. The right side shows related information and settings.
Depending on the size of the HMI screen, both menu and
content of selected item may be shown on screen at the same
time or not.
System Settings has two modes of operation:
User Mode
System Mode
GF Designer HD runtime is running or the
HMI device is in “factory default” status.
GF Designer HD runtime is not running
or the HMI device has a software failure.
System Mode includes all options
available in User Mode and additionally
includescommands dedicated to system
upgrade and recovery not available when
running in User Mode.
Activation of System Settings in User Mode:
Factory default
status
GF Designer HD
runtime running
Press “System Setting” button on the
HMI screen
Recall context menu and select “System
Settings”. To recall the context menu
click and hold any unused area of the
touchscreen for a few seconds. Default
hold time is 2 seconds.
Activation of Systems Settings in System Mode:
Normal
operation
If GF Designer HD runtime is not running:
Press “System Setting” button on the
device screen to recall System Settings
in User Mode. Select “Restart” -> “Cong
OS” to reboot in System Mode.
If GF Designer HD runtime is running:
recall context menu and select “System
Settings”.
To recall the context menu click and hold
any unused area of the touchscreen for
a few seconds. Default hold time is 2
seconds to enter in System Settings in
User Mode. Select “Restart” -> “Cong
OS” to reboot in System Mode.
Recovery
operation
If device is not responsive, use the so-
called “tap-tap” procedure.
This procedure consists in tapping the
surface of the touchscreen during the
device power-up phase. Tapping frequency
must be high.
You have to start tapping the touchscreen
as soon as power has been applied
to the device. When the sequence has
been recognized, the system shows the
message: “TAP-TAP DETECTED”. At this
point release touch to boot in User Mode
without running GF Designer HD runtime
or press and hold few seconds (selecting
so “RESTART: CONFIG OS”) to boot in
System Mode.
System Settings includes options for basic settings of the
device:
Language
System
Configure language used for System
Setting menu only.
Show information about platform, status
and timers (like System on time, backlight
on time).
Logs
Date & Time
Enable persistent log for BSP and allows
exporting it.
Change the device date and time, including
time zone and NTP Server

19 80588_eView HD IP67_02-2019_ENG
Network Congure IP Address of Ethernet interface
and the other network settings like DNS,
Gateway, DHCP, Hostname, routing and
bridging.
Services Enable/disable services. Examples of
services are: OpenSSH server, Bridge,
Cloud, Router, SNMP and logging.
Management Update of BSP components (Main OS,
Cong OS, Boot loader, XLoader), check
for partitions consistence, update of splash
screen, information about usage and size
of partitions. The update of Main OS is
available only in System Mode, the update
of Cong OS is only in User Mode.
Display Adjust display brightness, configure
automatic backlight turno and select HMI
orientation (90°, 180°, 270° and 360°).
Restart Restart the device. “Main OS” option
restarts the device in User Mode, “Cong
OS” option restarts the device in System
Mode showing System Settings.
Authentication Configure password for administrator
(“admin”) and for the standard user
(“user”). Administrator has full access to
System Settings (updates of BSP and
other system components). Standard user
has some limitations.
Note: Additional informations on System Settings are
available in dedicated manual.

20 80588_eView HD IP67_02-2019_ENG
11. UNPACKING AND PACKING INSTRUCTIONS
Fig. 11.1: eView HD 101 IP67
Fig. 11.2: eView HD 156 IP67, eView HD 215 IP67
To repack the unit, please follow the instructions backwards.
Other manuals for eView HD IP67 Series
1
This manual suits for next models
4
Table of contents
Other gefran Control Panel manuals
Popular Control Panel manuals by other brands

Frick
Frick QUANTUM LX Control Panel Maintenance manual

Honeywell
Honeywell Notifier NFS-320 Document

Nordelettronica
Nordelettronica NE274 instruction manual

Extron electronics
Extron electronics ACP 100 Setup guide

Telemotive
Telemotive Remote Control Touch Startup guide

See Water
See Water WS Series Installation and operator's manual